Pentair MiniMax NT LN installation manual Reversible Inlet/Outlet Connection, cont’d

Page 10

Section III. Installation

10

 

 

Reversible Inlet/Outlet Connection, cont’d.

On the MiniMax NT LN Series heater there is insulation installed by the factory on the return head side of the heaters. This insulation is there so that if the heads are reversed in the field, during initial installation of the heater, the high limits will be insulated from the heat radiating from the flue collector.

6.Return head in position before removal. This view shows the insulation installed by the factory. Remove the 8 bolts holding the return head in place.

7.When heads are removed, replace the heat exchanger tube seal gaskets.

8.Exchange the inlet/outlet header with the return header. Lift the insulation to allow the main head to be installed. Align header with the heat exchanger. When head is placed into position, release the insulation; it will now shield the high limits from the heat produced by the flue collector. Install header bolts, and tighten snugly by hand. (This will help avoid cross threading.) When tightening, use a cross pattern starting from the center of the header. DO NOT over tighten.

9.Install the temperature sensing probe by passing the wires through the hole provided on the left side of the brace panel. Route wires through the support bracket.

10.Reconnect all the high limit wires and the pressure switch wiring, routing the wires through the same hole as the thermostat sensor wires.

11.Pump and bleed system to check the head for leaks.

12.Reinstall the two large inspection plates on the appropriate side.

Remember: The inlet and outlet markings

on the header are still correct.

Do not plumb the heater backwards.

P/N 472089

Rev. E 4-19-05

Image 10
Contents MiniMax NT LN Series Customer Service Table of Contents Heater Identification Information Heater Identification Information HINWarranty Information Important NoticesConsumer Information and Safety Code RequirementsInstallation Instructions SpecificationsPlumbing Connections Below Pool InstallationBelow or Above Pool Installation ValvesWater Connections Reversing HeadersReversible Inlet/Outlet Connection, cont’d GAS Connections GAS Line InstallationsSediment Traps GAS Pipe Sizing Pipe Sizing for GAS Line ConnectionsTesting GAS Pressure GAS Pressure RequirementsIndoor Venting General Requirements Indoor Installation USA only Outdoor Shelter Installation CanadaVent Adaptors Combustion AIR SupplyFits ALL Models Indoor Installations Minimax NT Venting Guidelines Outdoor Installation Venting Guidelines Side View Outdoor Vent KITElectrical Rating 60 Hz 120 / 240 Volts AC, single phase Electrical ConnectionsWire Color Basic System Operation Minimax NT LN HSI Electronic Ignition LIGHTING/OPERATIONWater Pressure Switch Safety ControlsVacuum AIR Pressure FAN Switch LOW GAS Pressure SwitchOperation of Ignition Module Heat ModeHigh Limits Failure to Light the BURNER-LOCK OUTDigital Display Temperature Controller Ddtc System Indicator LightsSection IV. Operation SET UP Temperature Setting Troubleshooting Instruction Troubleshooting DdtcTroubleshooting General Service CHECKS-IGNITION ModuleMaintenance Instruction Energy Saving TipsSpring and Fall Operation Winter OperationChemical Balance Pool and SPA WaterReplacement Parts NT LN w/DDTC Rev. E Rev. E Pentair Water Pool and Spa, Inc