Section III. Installation | 18 |
|
|
OUTDOOR INSTALLATION (Outdoor Shelter Installation in Canada, see page 15)
For outdoor installation with an exhaust grill, the heater must be placed in a suitable area on a level, noncombustible surface. Do not install the heater under an overhang with clearances less than 3 feet from the top of the heater. The area under an overhang must be open on three sides.
IMPORTANT!
•In an outdoor installation it is important to ensure water is diverted from overhanging eves with a proper gutter/drainage system. The heater must be set on a level foundation for proper drainage.
•Under certain conditions, “heavy rains or unusually high winds”, it may be necessary to install an outdoors vent. In this situation, use Outdoor Vent Kit, P/N 460424, (see below).
•This unit shall not be operated outdoors at temperatures below
OUTDOOR INSTALLATION
VENTING GUIDELINES
4' 3'
SIDE VIEW | 4' |
|
4 ft. | 4' |
| |
Window |
|
4 ft. | Exhaust Grill |
| (Vent) |
Building |
|
Heater | |
(side view) |
| Property Line |
| |||
|
|
|
|
| codes. |
|
|
| building | ents | |
Force |
|
| local | requirem | |
|
| setback |
|
| |
Air Inlet | Check |
|
|
| |
|
|
|
|
| |
| for |
|
|
|
|
Vent Termination:
Must be at least 3 ft. above any forced air inlet located within a 10 ft. radius.
Must be located 4 feet away from the building wall
Figure 13.openings, and at the following distances away from any door, window, or gravity air inlet:
4 ft. below,
4 ft. horizontally
OUTDOOR VENT KIT
1.Remove the six (6) retaining screws from the old exhaust grill and discard the screws, gasket, and exhaust grill as shown in Figure 14.
2.Install the Outdoor Vent Kit, (P/N 460424), as shown in Figure 15. Make sure the holes in the gasket, metal flange of the main vent assembly, and heater cover are aligned before securing into place using the six (6) screws provided in the Outdoor Vent Kit.
|
| EXHAUST GRILL | METAL FLANGE |
|
| SCREWS (6) | |
|
| SCREWS (6) | |
|
|
| |
| GASKET |
| GASKET |
|
|
| |
Figure 14. |
|
| Figure 15. |
CAUTION
If installing the heater next to or near an air conditioning unit or a heat pump, allow a minimum of 36 in. between the air conditioning unit and the heater.