Section III. Installation | 14 |
|
|
INDOOR VENTING — General Requirements
The vent pipe must be the same size or larger. The MiniMax NT LN heaters are capable of a
NOTE
The allowable vent runs for each vent pipe diameter are different and can not be exceeded.
Each
The MiniMax NT LN is a “Category III” appliance and is an
4 inch Vent Pipe
Number of | Maximum | ||
Elbows | |||
Vent Run | |||
|
| ||
90° | 45° | (Feet) | |
|
|
| |
1 | — | 22 | |
|
|
| |
1 | 1 | 18 | |
|
|
| |
1 | 2 | 14 | |
|
|
| |
2 | — | 14 | |
|
|
|
heater can be found on page 16. It is recommended that vent runs over 18 feet be insulated to reduce condensation related problems and/or the use of a condensate trap in the vent run close to the heater may be necessary in certain installations such as cold climates. The MiniMax NT LN heater is suitable for
Recommended sources for
CAUTION
Do NOT combine exhaust vent pipes to a common exhaust vent in multiple unit installations. Run separate vent pipes.
|
|
|
|
| Table 6. | |
|
|
|
|
|
| |
5 inch Vent Pipe | 5 inch Vent Pipe | |||||
|
|
|
|
|
| |
Number of | Maximum | Number of | Maximum | |||
Elbows | Elbows | |||||
Vent Run | Vent Run | |||||
|
|
|
| |||
90° | 45° | (Feet) | 90° | 45° | (Feet) | |
|
|
|
|
|
| |
0 | 2 | 45 | 2 | 2 | 29 | |
|
|
|
|
|
| |
1 | — | 45 | 2 | 3 | 25 | |
|
|
|
|
|
| |
1 | 1 | 41 | 2 | 4 | 21 | |
|
|
|
|
|
| |
1 | 2 | 37 | 3 | — | 29 | |
|
|
|
|
|
| |
1 | 3 | 33 | 3 | 1 | 25 | |
|
|
|
|
|
| |
2 | — | 37 | 3 | 2 | 21 | |
|
|
|
|
|
| |
2 | 1 | 33 | 4 | — | 21 | |
|
|
|
|
|
| |
|
|
|
|
| Table 7. |
THROUGH WALL VENT KITS FOR HEATERS
Part | Dim. A | Dim. B | Dim. C | Dim. D | Dim. E | Dim. F | |||||
Number | |||||||||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
471532 | 4 | in. Dia. | 6 | in. Dia. | 8½ in. | 6 5/16 in. | 12 | 5/8 in. | 10 | 5/8 in. | |
|
|
|
|
|
|
|
|
|
|
| |
471543 | 5 | in. Dia. | 8 | in. Dia. | 8½ in. | 8 in. | 12 | 5/8 in. | 10 | 5/8 in. | |
|
|
|
|
|
|
|
|
|
|
|
Table 8.
C F
B AE
D
Figure 5.
P/N 472089 | Rev. E |