Pentair MiniMax NT LN installation manual Indoor Installations Minimax NT Venting Guidelines

Page 17

Rev. E 4-19-05

P/N 472089

 

vent terminated at least 24"

 

above any object within 10 ft.

More Than10 ft.

Ridge

Vent Cap

 

2 ft. min.

 

3 ft. min.

 

Roof

Roof

Thimble

Jack

 

 

Chimney/Gas Vent

Vent for roof penetration installations:

must extend at least 3 ft. higher than the point at which it passes through the roof, or as permitted by local code.

must use a roof thimble through the roof penetration.

must terminate with an approved (listed) roof jack, storm collar, and vent/weather cap.

Vent pipe extension:

must be the same diameter as the vent connector.

must be suitable for use with category III appliances with flue gas temperature ratings less than 400 deg. F.

may use a single wall vent pipe with permanently sealed seams, joints and proper insulating materials.

INDOOR INSTALLATIONS

MINIMAX NT VENTING GUIDELINES

 

 

1'

min

.

 

 

Vent Hood

 

 

 

 

1'

min

.

4'

 

 

 

 

 

 

 

4'

 

 

 

 

Vent Hood

 

 

 

3'

 

4'

 

 

Force Air Inlet

 

 

 

1' min.

 

Vent Hood

above grade

7'

 

Walkway

Recommended sources for side wall Vent Hood;

see "Section Venting".

Vent termination for side wall installations:

must be not less than 7 ft. above public walkways.

must be at least 3 ft. above any outside air intake located within a 10 ft. radius.

must NOT be within 3 ft. of an inside corner of the structure. must be at least 1 ft. above grade.

must be located the following distances away from any door, window, or gravity air inlet:

4 ft. below

4 ft. horizontally 1 ft. above

Air Supply

Clearances indicated are for non-mechanical air supply inlet to the building.

 

For mechanical air supply inlet, a minimum horizontal clearance of 10 feet

 

should be maintained away from the vent termination.

Figure 12.

Section III. Installation

17

Image 17
Contents MiniMax NT LN Series Customer Service Table of Contents Heater Identification Information HIN Heater Identification InformationImportant Notices Warranty InformationCode Requirements Consumer Information and SafetySpecifications Installation InstructionsBelow or Above Pool Installation Below Pool InstallationPlumbing Connections ValvesReversing Headers Water ConnectionsReversible Inlet/Outlet Connection, cont’d Sediment Traps GAS Line InstallationsGAS Connections Pipe Sizing for GAS Line Connections GAS Pipe SizingGAS Pressure Requirements Testing GAS PressureIndoor Venting General Requirements Outdoor Shelter Installation Canada Indoor Installation USA onlyFits ALL Models Combustion AIR SupplyVent Adaptors Indoor Installations Minimax NT Venting Guidelines Outdoor Vent KIT Outdoor Installation Venting Guidelines Side ViewElectrical Connections Electrical Rating 60 Hz 120 / 240 Volts AC, single phaseWire Color Minimax NT LN HSI Electronic Ignition LIGHTING/OPERATION Basic System OperationVacuum AIR Pressure FAN Switch Safety ControlsWater Pressure Switch LOW GAS Pressure SwitchHigh Limits Heat ModeOperation of Ignition Module Failure to Light the BURNER-LOCK OUTSystem Indicator Lights Digital Display Temperature Controller DdtcSection IV. Operation SET UP Temperature Setting Troubleshooting Ddtc Troubleshooting InstructionService CHECKS-IGNITION Module Troubleshooting GeneralEnergy Saving Tips Maintenance InstructionWinter Operation Spring and Fall OperationPool and SPA Water Chemical BalanceReplacement Parts NT LN w/DDTC Rev. E Rev. E Pentair Water Pool and Spa, Inc