Pentair MiniMax NT LN installation manual High Limits, Operation of Ignition Module, Heat Mode

Page 23
Figure 25.
23
Diagnostic LED
1 Flash - Air Flow Fault
2 Flashes - Flame no Call for Heat
3 Flashes - Lock Out
Figure 24.

Section IV. Operation

SAFETY CONTROLS, (cont’d.)

Flame Current

Check Point

HIGH LIMITS

A “High Limit”, is a safety device that opens the electrical circuit and shuts off the heater based on a water temperature set point within the “High Limit Device”. The MiniMax NT LN series of heaters contains two (2) high limit devices which are located on the main inlet / outlet header, one sensing the inlet water temperature and one sensing the outlet water temperature.

OPERATION OF IGNITION MODULE

The Ignition Module, (see Figure 24), is microprocessor based and operates on 24 VAC supplied by the transformer. The

control utilizes a microprocessor to continually and safely monitor, analyze, and control the proper operation of the gas burners. The module with the presence of the flame sensor, using flame rectification, allows the heater to operate.

1. HEAT MODE

When a call for heat is received from the thermostat supplying 24 volts to the (TH) terminal, the module will check the pressure switch for normally open contact. The combustion blower is then energized and, once the air pressure switch contacts close, the 15-second "pre-purge" period begins. After pre-purge, the hot surface igniter is energized for approximately 40-second heat-up period, followed by the gas valve for the "trial for ignition" (TFI) period, for maximum of 7 seconds for the LN model.

When the flame is detected during the TFI period, through the flame sensor, the igniter is deactivated and the gas valve remains energized.

Note: After the pre-purge period the combustion blower slows down to half normal speed during the heat-up and TFI periods and continues thereafter for another 30 seconds at low speed, then return to full speed for the remainder of the heating cycle.

The thermostat, air pressure switch and burner flame are constantly monitored to assure that the system operates properly. When the thermostat is satisfied and the demand for heat ends, the gas valve is immediately de-energized, the module senses the loss of flame signal and initiates the 45-second "post-purge" period before de-energizing the combustion blower.

2. FAILURE TO LIGHT THE BURNER—LOCK OUT

Should the main burner fail to light, or the flame is not detected during the first TFI (try for ignition) cycle, the gas valve is de-energized and the ignition module performs an "inter-purge" delay (approximately 15 seconds) before attempting another TFI cycle. The module will attempt 2 additional TFI's cycles before locking out. The gas valve will be turned off immediately. The combustion blower will be turned off following 45 seconds "post-purge" period.

The module will automatically reset after one hour, if the thermostat is still calling for heat, and attempt a new TFI cycle.

3. FLAME FAILURE—RE-IGNITION

INTERNAL POWER SWITCH

If the established flame signal is lost while the burner is operating, the control will respond within .08 second. The gas valve is de-energized and the control

starts a new ignition sequence in an attempt to relight the burner. The ignition attempt will be repeated (3) times. If the burner does not relight, the control will go into lockout as previously described in the “Failure to Light the Burner—Lock Out”. If flame is reestablished, normal operation resumes.

Rev. E 4-19-05

P/N 472089

Image 23
Contents MiniMax NT LN Series Customer Service Table of Contents Heater Identification Information HIN Heater Identification InformationImportant Notices Warranty InformationCode Requirements Consumer Information and SafetySpecifications Installation InstructionsValves Below Pool InstallationBelow or Above Pool Installation Plumbing ConnectionsReversing Headers Water ConnectionsReversible Inlet/Outlet Connection, cont’d Sediment Traps GAS Line InstallationsGAS Connections Pipe Sizing for GAS Line Connections GAS Pipe SizingGAS Pressure Requirements Testing GAS PressureIndoor Venting General Requirements Outdoor Shelter Installation Canada Indoor Installation USA onlyFits ALL Models Combustion AIR SupplyVent Adaptors Indoor Installations Minimax NT Venting Guidelines Outdoor Vent KIT Outdoor Installation Venting Guidelines Side ViewElectrical Connections Electrical Rating 60 Hz 120 / 240 Volts AC, single phaseWire Color Minimax NT LN HSI Electronic Ignition LIGHTING/OPERATION Basic System OperationLOW GAS Pressure Switch Safety ControlsVacuum AIR Pressure FAN Switch Water Pressure SwitchFailure to Light the BURNER-LOCK OUT Heat ModeHigh Limits Operation of Ignition ModuleSystem Indicator Lights Digital Display Temperature Controller DdtcSection IV. Operation SET UP Temperature Setting Troubleshooting Ddtc Troubleshooting InstructionService CHECKS-IGNITION Module Troubleshooting GeneralEnergy Saving Tips Maintenance InstructionWinter Operation Spring and Fall OperationPool and SPA Water Chemical BalanceReplacement Parts NT LN w/DDTC Rev. E Rev. E Pentair Water Pool and Spa, Inc