Performing the gas leak tests

Make sure to check for gas leaks before completing the installation process (connecting the assembly pipe and hose between indoor unit and outdoor unit, insulating the cables, hose and pipe, and fixing the indoor unit to the installation plate).

A

B

Test part for outdoor unit

Tightening torque for body cap (Refer to the table)

Spindle

Charging core

R-22: Diameter of the screw - 7/16-20UNF

R-410A: Diameter of the screw - 1/2-20UNF

Tightening torque for charging port cap (Refer to the table)

C D

Test part for indoor unit

Before inspecting the leakage, use a torque wrench to close the cap for the service valve. (Comply with a tightening torque for each size of the diameter,and tighten the cap firmly to prevent any leakage.).

To check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the connection part of the indoor/outdoor units with soap lather or liquid for leakage test.

Outer

Tightening torque

Diameter

Body cap (N•m)

Charging port cap

(mm)

(N•m)

 

ø 6.35

20 ~ 25

 

ø 9.52

20 ~ 25

 

ø12.70

25 ~ 30

10 ~ 12

ø15.88

30 ~ 35

 

ø19.05

35 ~ 40

 

To check for gas leaks on the outdoor unit,

( 1 N•m = 10 kgf•cm )

Check the valve A and B using a leak detector.

 

To check for gas leaks on the indoor unit,

 

Check the flare nut C and D using a leak detector.

 

Leak test with nitrogen (before opening valves)

In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A.

Leak test (after opening valves)

Before opening valves, discharge all the nitrogen from the system and create vacuum according to page 49~51. After opening valves, check leaks using a leak detector for refrigerant.

Pump down (before disconnecting the refrigerant connections for unit repair, removal or disposal) Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit.

This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

Shut off the liquid valve with the Allen wrench.

Turn the system on in cooling with fan operating at high velocity.

(Compressor will immediately start, provided 3 minutes have elapsed since the last stop).

After 2 minutes of operation, shut the suction valve with the same wrench.

Turn the system off and switch mains supply off.

Disconnect tubing. After disconnection, protect valves and tubing ends from dust.

Compressor damage may occur if run at a negative suction pressure.

English-52

MG_BETTER_ON&OFF_A3050_IB&IM_EN_DB68-04534A.indd 52

2014/9/26 16:28:12

Image 52
Contents Air Conditioner Features of your new air conditioner Contents Safety precautions English-4For Power Supply English-5For Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9Operation ranges Checking before useEnglish-10 Technical Specifications English-11Checking the name of the parts Main partsDisplay English-12Remote controller buttons Checking the remote controllerEnglish-13 Remote controller display Low Battery warningStoring the remote controller Inserting the batteriesBasic function Press the button to set the desired fan speed Press the button to adjust the temperatureEnglish-16 Adjusting the air flow direction English-17Setting the On/Off timer Setting the On timerWhen the air conditioner is off English-18When the air conditioner is on Setting the Off timerEnglish-19 English-20 ModeAdditional options available Step cooling function When the air conditioner is operating in Cool modeEnglish-21 Using the Comfort function Using the Fast functionEnglish-22 Using the Single user function Single user function is only available in Cool modeEnglish-23 Blink and press the SET buttonUsing the Virus Doctor function When the air conditioner is operatingEnglish-24 Press the SET button to set the Virus Doctor functionChecking the usage time Using the Auto clean functionEnglish-25 Setting the Beep sound Resetting the Filter clean reminderSetting the Display option English-26Cleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger English-27Cleaning the Air filter Removing the Air filterEnglish-28 Remove the Air filter from the main bodyEnglish-29 Reassembling the Air filterTop of the Air filter into the main body.. ➀ Maintaining the air conditioner English-30Troubleshooting TemperatureAdjustment is not English-31Button or disconnect the power plug/switch Check the Drains have been cleared Regular MaintenanceError is indicated Heard when refrigerant flow movement changes. It is normalGeneral information English-33Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitOutdoor Unit Where sulfide gas existsEnglish-35 When installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-36  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case English-37Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsAssembling the hanger screw English-39This QR code for detail video of indoor unit installation Removing the screwsRemoving the Cover panel Before mounting the indoor unit English-40Assembling the Cover panel After mounting the indoor unit English-41Connecting the assembly cable Cable specificationConnecting the cable English-42Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryEnglish-43 English-44 Smooth the cut edgesCut off the remaining foam insulation TorqueCutting or extending the pipe Evacuating the indoor unitEnglish-45 Correct Inclined English-46Cracked Drain hose installation English-47Change the direction only when it is necessary English-48Shield Downwards as seen in the picture Evacuating the connected pipes English-49 Connect a drain hose to the drain plug Ensure that condensation draining is adequateEnglish-50 Adding RefrigerantOuter Torque English-51 Cylinder with siphonPlease fill in with indelible ink 1975Performing the gas leak tests English-52Outdoor unit installed on the wall by rack Fixing the outdoor unit in placeEnglish-53 18/24JR 660 340 18JQ 24JQ 645Smart Install mode English-54English-55 Off / Blinking / OnFinal check and trial operation English-56Packing and unpacking guide English-57How to connect your extended power cables English-58Apply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish-59 Questions or COMMENTS? 0211