Final check and trial operation

To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly.

Check the followings:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (follow the steps below)

1. Press the Power button and check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

2. Press the Mode button to select Cool or Heat (ARJQ) mode.

In Cool mode, use Temp hr. + or button and set the temperature at 16 °C.

In Heat mode, use Temp hr. + or button and set the temperature at 30 °C (ARJQ).

• Approximately 3~5 minutes later, outdoor unit will start to operate and the

Cool or Warm (ARJQ) air will blow out.

• After 12 minutes of stationary condition check the indoor unit air treatment.

Cooling mode (indoor unit check) Inlet air temp. - Outlet air temp: From 10 °C to 12 °C (indicative delta T)

Heating mode (indoor unit check) Outlet air temp. - Inlet air temp: From 11 °C to 14 °C (indicative delta T) (ARJQ)

In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space. (ARJQ)

3.Press the Air swing button and check the following:

The airflow blades work properly.

4.Press the Power button to stop the operation.

• When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe

place.

Pump down procedure (when removing the product)

1.Turn on the air conditioner and select Fast Cool mode. Please let the compressor run for more than 5 minutes. If the compressor does not operate for more than 5 minutes due to protection control, wait about 2 minutes, and then carry out the next procedure.

2 . Release the valve caps on High and Low pressure side.

3 . Use L wrench to close the valve on the high pressure side.

4 . After approximately 2 minutes, close the valve on the low pressure side.

5 . Stop operation of the air conditioner by pressing the Power button on the indoor unit or remote controller.

6 . Disconnect the pipes.

English-56

MG_BETTER_ON&OFF_A3050_IB&IM_EN_DB68-04534A.indd 56

2014/9/26 16:28:13

Image 56
Contents Air Conditioner Features of your new air conditioner Contents Safety precautions English-4For Power Supply English-5For Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9English-10 Checking before useOperation ranges Technical Specifications English-11Checking the name of the parts Main partsDisplay English-12English-13 Checking the remote controllerRemote controller buttons Remote controller display Low Battery warningStoring the remote controller Inserting the batteriesBasic function English-16 Press the button to adjust the temperaturePress the button to set the desired fan speed Adjusting the air flow direction English-17Setting the On/Off timer Setting the On timerWhen the air conditioner is off English-18English-19 Setting the Off timerWhen the air conditioner is on Additional options available ModeEnglish-20 English-21 When the air conditioner is operating in Cool modeStep cooling function English-22 Using the Fast functionUsing the Comfort function Using the Single user function Single user function is only available in Cool modeEnglish-23 Blink and press the SET buttonUsing the Virus Doctor function When the air conditioner is operatingEnglish-24 Press the SET button to set the Virus Doctor functionEnglish-25 Using the Auto clean functionChecking the usage time Setting the Beep sound Resetting the Filter clean reminderSetting the Display option English-26Cleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger English-27Cleaning the Air filter Removing the Air filterEnglish-28 Remove the Air filter from the main bodyTop of the Air filter into the main body.. ➀ Reassembling the Air filterEnglish-29 Maintaining the air conditioner English-30Troubleshooting TemperatureAdjustment is not English-31Button or disconnect the power plug/switch Check the Drains have been cleared Regular MaintenanceError is indicated Heard when refrigerant flow movement changes. It is normalGeneral information English-33Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitEnglish-35 Where sulfide gas existsOutdoor Unit When installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-36  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case English-37Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsAssembling the hanger screw English-39This QR code for detail video of indoor unit installation Removing the screwsRemoving the Cover panel Before mounting the indoor unit English-40Assembling the Cover panel After mounting the indoor unit English-41Connecting the assembly cable Cable specificationConnecting the cable English-42English-43 Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number English-44 Smooth the cut edgesCut off the remaining foam insulation TorqueEnglish-45 Evacuating the indoor unitCutting or extending the pipe Cracked English-46Correct Inclined Drain hose installation English-47Change the direction only when it is necessary English-48Shield Downwards as seen in the pictureEvacuating the connected pipes English-49Connect a drain hose to the drain plug Ensure that condensation draining is adequateOuter Torque Adding RefrigerantEnglish-50 English-51 Cylinder with siphonPlease fill in with indelible ink 1975Performing the gas leak tests English-52Outdoor unit installed on the wall by rack Fixing the outdoor unit in placeEnglish-53 18/24JR 660 340 18JQ 24JQ 645Smart Install mode English-54English-55 Off / Blinking / OnFinal check and trial operation English-56Packing and unpacking guide English-57How to connect your extended power cables English-58Apply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish-59 Questions or COMMENTS? 0211