Selecting the insulator of the refrigerant pipe

ffInsulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size.

ffThe standard condition for indoor temperature is 30°C with humidity less than 85%. If the condition is out of this standard condition, use the pipe that is one grade thicker.

Pipe diameter (mm)

Minimum thickness of the insulator

Remarks

PE material

EPDM material

 

 

ø 6.35~ø 19.05

13

10

If the installation place has high humidity (such as

ø 22.23~ø 31.75

19

13

basement of a building, seaside, near hot spring

ø 38.10~ø 44.45

25

19

or lake etc.) increase the minimum thickness to

 

 

 

next size up for each pipes.

-

32

25

 

Insulating refrigerant pipe

ffPipe insulation

-- Insulation of the gas and liquid pipes can be in contact with each other but they should not be pressing each other. -- When contacting the gas side and liquid side pipe, use thicker insulation.

ENGLISH

Insulation

Insulation

Gas pipe

Liquid pipe

 

• Make sure to install the insulation so that there is no gap or crack and use the adhesives on the connection part of it

CAUTION

to prevent moisture from entering.

• Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. (When winding the insulation

 

tape, make sure that the thickness of the insulator does not get any thinner.)

 

• Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe.

 

• If the thickness of the insulation gets thinner, use additional insulation.

Additional insulation

Hanger

a

a x 3

Insulation for

refrigerant pipe

39

PAC_아프리카 중동향AP80S0A_IBIM_34514A-02_EN.indd 39

2015-04-23 오후 2:18:59

Image 40
Contents Questions or COMMENTS? 08000-7267864Air Conditioner Thank you for purchasing this Samsung productFeatures of your new air conditioner ContentsSafety precautions Important safety symbols and precautionsXXFailing to do so may result in electric shock or fire XXThis may result in electric shock or fireFor Power Supply XXWhen there is fire, this may cause spread of fireDo not operate the appliance with wet hands Do not place objects or devices under the indoor unitXXThis may result in electric shock Do not clean the inside of the air conditioner by yourself Do not drink the water from the air conditionerUsing outdoor unit Checking the auxiliary power switchOperational temperature and humidity range Auxiliary power switch Elcb Earth Leakage Circuit BreakerMain parts Viewing the partsTo open the panel Locking the control panel Control panel and the displayUsing the air conditioner with the control panel Remote controller button Checking the remote controllerInstalling the batteries Basic operation CoolAuto DryPress Button to adjust the desired temperature Press Button to start the operation of the air conditionerAdjusting the air flow direction Turbo operationPress Operation will operate for 30 minutesTimer function Press the button when the air conditioner is onSmart saver operation You can turn the air conditioner off at your desired timeCleaning and maintaining the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Service centerCleaning the air filter Maintaining the air conditioner Periodical checksTroubleshooting Clean the air filter if it is dirty If the message See if the timer is already setFunction Accessing its internal components Installing the unitGeneral information Power supply line, fuse or circuit breaker Do not install the air conditioner in following placesMake sure that you earth the cables Complete, electric shock or fire may occurPreparation for installation When moving with a craneWhen moving with a fork lift Indoor outdoor unit type and combinationDeciding on where to install the product Indoor unitFix the wire on the ground Wires on the wallOutdoor unit Personal injury or property damageSelecting appropriate location for installation Wear protective goggles and mask before spraying When there are no tall obstacles around the outdoor unit When the air outlet is opposite the wallWhen 3 sides of the outdoor unit are blocked by the wall Space requirementsWhen installing 1 outdoor unit When there is tall obstacle around the outdoor unitPipe length between the indoor and the outdoor unit Preparing the installation Installing duct for horizontal exhaust dischargeInstalling the outdoor unit in harsh environments When installing ductsInstalling indoor unit Installing outdoor unit AP80S0XOutdoor unit base mount and anchor bolt position Connecting the pipes Refrigerant piping workRemoving the connection pipe InjuryOutdoor unit pipe connection AP80S0X Keep the pipe length as short as possibleSelecting refrigerant pipe Temper grade and minimum thickness of the refrigerant pipeModel name Liquid side mm Gas side mm Outer diameter mm/inch Minimum thickness mm Temper grade Direction of the pipe when brazing Storing refrigerant pipe Nitrogen flushing brazing Stored place Stored time Sealing typeOuter diameter Dmm Cutting or flaring the pipesCorrect Inclined Damaged surface Cracked Uneven thickness Connecting the drain hose Tightening flare connection partPipe bending Piping materialSelecting the insulator of the refrigerant pipe Insulating refrigerant pipeFfPipe insulation To prevent moisture from enteringWiring work Electrical workPower supply and wire specification 0Not includedConnecting power and communication cable AP80S0A / AP0AS0ASelecting solderless ring terminal Fixing the power cable Connecting the power terminalScrew Tightening torque kgf∙cm Grounding the power cable FfGrounding must be done by installation specialistWhen using the exclusive terminal for grounding Grounding workGrounding work procedure If you are using the grounding on the switching boardFfMake sure that grounding work is done in below procedure Procedure ExplanationGas leak test and vacuum drying Refrigerant charging How to add refrigerantAllowable refrigerant pipe length Setting the option switches & function keys Setting the option switch of the indoor unitSetting the main PCB option K1 K2 K3 K4Setting the outdoor unit KEY K2 Number of pressingSegment display Display PressingCheck lists after completing the installation Trial operation Inspection before trial operationTrial operation Make sure that all the indoor units are properly operatingError diagnosis Error displayError display Error description LED displayHow to connect your extended power cables Twist the wire cores together and push it in to the sleeveInsulation tape