Grounding work
Grounding must be done by a qualified installer for your safety.
Grounding the power cable
ffThe standard of grounding may vary according to the rated voltage and installation place of the air conditioner. ffGround the power cable according to the following table.
Installation place | High humidity | Average humidity | Low humidity |
Power condition |
|
|
|
Voltage of lower than 150V |
| Perform the grounding work | Perform the grounding work 2 if |
| 3. Note 1) | possible for your safety. Note 2) | |
|
| ||
|
|
|
|
Voltage of higher than 150V |
| Must perform the grounding work 3. Note 1) (Including the case where | |
| circuit breaker is installed) | ||
|
| ||
|
|
|
|
Note 1) Grounding work 3
ffGrounding must be done by installation specialist.
ffCheck if the grounding resistance is lower than 100Ω. When installing a circuit breaker that can cut the electric circuit in case of a short circuit, the allowable grounding resistance can be 30~500Ω.
Note 2) Grounding at dry place
ffThe grounding resistance is should be lower than 100Ω and even in worst case, it should be lower than 250Ω)
Performing the ground work
ffUse the grounding wire by referring to the specification of the electric cable for the outdoor unit.
❖❖ When using the exclusive terminal for grounding
AP80S0A |
| AP0AS0A |
ENGLISH
Exclusive terminal for grounding
Grounding resistance under 100Ω (Conventional facility)
Exclusive terminal for
grounding
Grounding resistance under 100Ω (Conventional facility)
❖❖ When using the exclusive terminal for grounding
AP80S0A |
| AP0AS0A |
Switching board
Switching board
Grounding resistance under | Grounding resistance under | |
100Ω (Conventional facility) | ||
100Ω (Conventional facility) | ||
|
45