Samsung AP0AS0ANXSG manual Refrigerant charging, Allowable refrigerant pipe length

Page 49

Refrigerant charging

Allowable refrigerant pipe length and amount of additional refrigerant charging

ffAir purge refrigerant for piping is not filled in this product.

ffMake sure to vacuum inside of the connection pipe using vacuum pump after connecting pipes.

Allowable refrigerant pipe length

Model name

Maximum allowable pipe length

Maximum height difference of the pipe

AP80S0A Series

50m

20~30m

AP0AS0A Series

 

 

How to add refrigerant

1.Connect manifold gauge to the gas side service valve.

2.Take the trial operation with the cooling trial operation mode.

3.Perform trial operation for longer than 10 minutes and add refrigerant based on the below pressure table.

❋❋Purpose of pressure table : If additional refrigerant filling is needed due to the leakage of the refrigerant or re-installation, add refrigerant using pressure table.

Pressure table for temperatures (Cooling operations)

 

 

AP0AS0A✴✴✴✴

 

 

 

 

AP80S0A✴✴✴✴

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Temp. (°C)

 

 

 

 

Outdoor Temp. (°C)

 

 

 

21

35

 

46

52

 

 

21

35

46

52

Indoor

21

3.5

4.2

 

4.5

4.7

Indoor

21

4.1

5.1

5.4

5.6

Temp.

27

4.2

4.9

 

5.2

5.4

Temp.

27

4.4

5.4

5.7

5.9

(°C)

32

4.8

5.5

 

5.8

6.0

(°C)

32

5.0

6.0

6.3

6.5

4. Check the stability of the pressure for 10 minutes.

Outdoor unit

Gas side

 

Liquid side

5. After adding refrigerant, fasten cap nuts firmly.

 

• Use prescribed amount of refrigerant if you need to charge additional refrigerant due to extended pipe length.

CAUTION

For accurate measure, use a digital scale.

48

PAC_아프리카 중동향AP80S0A_IBIM_34514A-02_EN.indd 48

2015-04-23 오후 2:19:00

Image 49
Contents 08000-7267864 Questions or COMMENTS?Thank you for purchasing this Samsung product Air ConditionerContents Features of your new air conditionerImportant safety symbols and precautions Safety precautionsXXFailing to do so may result in electric shock or fire XXThis may result in electric shock or fireXXWhen there is fire, this may cause spread of fire For Power SupplyDo not operate the appliance with wet hands Do not place objects or devices under the indoor unitXXThis may result in electric shock Do not drink the water from the air conditioner Do not clean the inside of the air conditioner by yourselfChecking the auxiliary power switch Using outdoor unitOperational temperature and humidity range Auxiliary power switch Elcb Earth Leakage Circuit BreakerMain parts Viewing the partsTo open the panel Control panel and the display Locking the control panelUsing the air conditioner with the control panel Remote controller button Checking the remote controllerInstalling the batteries Cool Basic operationAuto DryPress Button to start the operation of the air conditioner Press Button to adjust the desired temperatureTurbo operation Adjusting the air flow directionPress Operation will operate for 30 minutesPress the button when the air conditioner is on Timer functionSmart saver operation You can turn the air conditioner off at your desired timeCleaning the indoor unit Cleaning and maintaining the air conditionerCleaning the outdoor unit heat exchanger Service centerCleaning the air filter Periodical checks Maintaining the air conditionerTroubleshooting Clean the air filter if it is dirty If the message See if the timer is already setFunction Accessing its internal components Installing the unitGeneral information Do not install the air conditioner in following places Power supply line, fuse or circuit breakerMake sure that you earth the cables Complete, electric shock or fire may occurWhen moving with a crane Preparation for installationWhen moving with a fork lift Indoor outdoor unit type and combinationIndoor unit Deciding on where to install the productWires on the wall Fix the wire on the groundOutdoor unit Personal injury or property damageSelecting appropriate location for installation Wear protective goggles and mask before spraying When the air outlet is opposite the wall When there are no tall obstacles around the outdoor unitWhen 3 sides of the outdoor unit are blocked by the wall Space requirementsWhen installing 1 outdoor unit When there is tall obstacle around the outdoor unitPipe length between the indoor and the outdoor unit Installing duct for horizontal exhaust discharge Preparing the installationInstalling the outdoor unit in harsh environments When installing ductsInstalling outdoor unit AP80S0X Installing indoor unitOutdoor unit base mount and anchor bolt position Refrigerant piping work Connecting the pipesRemoving the connection pipe InjuryKeep the pipe length as short as possible Outdoor unit pipe connection AP80S0XTemper grade and minimum thickness of the refrigerant pipe Selecting refrigerant pipeModel name Liquid side mm Gas side mm Outer diameter mm/inch Minimum thickness mm Temper gradeStoring refrigerant pipe Direction of the pipe when brazingNitrogen flushing brazing Stored place Stored time Sealing typeOuter diameter Dmm Cutting or flaring the pipesCorrect Inclined Damaged surface Cracked Uneven thickness Tightening flare connection part Connecting the drain hosePipe bending Piping materialInsulating refrigerant pipe Selecting the insulator of the refrigerant pipeFfPipe insulation To prevent moisture from enteringElectrical work Wiring work0Not included Power supply and wire specificationAP80S0A / AP0AS0A Connecting power and communication cableSelecting solderless ring terminal Fixing the power cable Connecting the power terminalScrew Tightening torque kgf∙cm FfGrounding must be done by installation specialist Grounding the power cable When using the exclusive terminal for grounding Grounding workIf you are using the grounding on the switching board Grounding work procedureFfMake sure that grounding work is done in below procedure Procedure ExplanationGas leak test and vacuum drying Refrigerant charging How to add refrigerantAllowable refrigerant pipe length Setting the option switch of the indoor unit Setting the option switches & function keysSetting the main PCB option K1 K2 K3 K4K2 Number of pressing Setting the outdoor unit KEYSegment display Display PressingCheck lists after completing the installation Inspection before trial operation Trial operationTrial operation Make sure that all the indoor units are properly operatingError display Error diagnosisError display Error description LED displayTwist the wire cores together and push it in to the sleeve How to connect your extended power cablesInsulation tape