2 . Open the front grille.
3 . Remove the screw securing the connector cover.
4 . Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals. (Refer to the picture below)
• Each wire is labeled with the corresponding terminal number.
5 . Pass the other end of the cable through the 65mm hole in the wall.
6 . Close the connector cover by tightening the screw carefully.
7 . Close the front grille.
8 . Remove the terminal board cover on the side of the outdoor unit. 9. Connect the cables to the terminals as seen in the picture.
• Each wire is labeled with the corresponding terminal number.
Indoor unit |
|
|
|
|
|
|
|
|
| AQVPC | AQVPB |
|
|
| |||
| Indoor unit |
|
| Indoor unit |
|
|
| |
|
|
|
| 1(L) | 2(N) | F1 | F2 | |
| N(1) | 1 | 2 |
| ||||
|
|
|
|
|
| |||
| N(1)N1 | 1 | 2 |
| 1(L) | 2(N) | F1 | F2 |
Outdoor unit | N(1) | 1 | 2 |
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| F1 | F2 |
|
|
|
| N(1) | 1 | 2 |
| L | N |
|
|
|
|
|
|
|
| |||
| Outdoor unit |
|
| Outdoor unit |
|
|
|
• End of the wire must be circular.
• Also circular terminal must be matched with screw size in terminal black.
•After connecting the cables, make sure terminal numbers on the indoor/outdoor unit matches.
•Screws on terminal block must not be unscrewed with the torque less than 12kgf•cm.
10.Connect the grounding conductor to the grounding terminals.
11.Close the terminal board cover by tightening the screw carefully.
• In Russia and Europe, consult with the supply authority to determine the supply system impedance before
installation.
• Connect the wires firmly so that wires can not be pulled out easily. (If they are loose, it could cause
•Connect the wires according to color codes, referring to the wiring diagram.
•The power cable and the interconnection cable should be selected according to the specification in page 28.
ENGLISH
29