Samsung AQV09PWCNEUR, AQV12PWCXCEE Smooth the cut edges, Cut off the remaining foam insulation

Page 30

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies

 

 

according to the exit position of the pipe when facing the wall:

A

B

• Right(A)

 

 

• Left(B)

 

C

• Underside(C)

 

 

 

• Rear

 

 

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

• If you want to shorten or extend the pipes, refer to page 31~32.

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and purge the air, refer to page 34~36.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 37 for further details.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

30

Image 30
Contents Page Contents Follow directions Safety precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning Checking before use Operation rangesMain parts Power buttonChecking the name of the parts DisplayChecking the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasic function Button to adjust the temperature PressPress the Air swing button on the remote controller Adjusting the air flow directionUsing the Turbo function Vertical air flowMode When the air conditioner is on and in cool/heat modePress the button on the remote controller Press the Time Up or Time Down button to set the timeSetting the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode If the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer Turn off automaticallyUsing the Quiet function Using the Auto Clean functionWhen the air conditioner is turned on Cleaning the outdoor unit heat exchanger Cleaning the air conditionerCleaning the indoor unit Opening the panelOpen the panel and put the Air filter out Cleaning the air filterRemoving the Air filter Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Outdoor unit Heat exchanger during Heat mode in winter Flow movement changes. It is normalConnection General information Included Models RemarkAQV09P, AQV12P, AQV18P, AQV24P Power supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitSpace Requirements for Outdoor Unit When installing 1 outdoor unitWhen installing more than 1 outdoor unit Top view Side viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Each wire is labeled with the corresponding terminal number InstallationSmooth the cut edges Cut off the remaining foam insulationPass the pipe through the hole in the wall Unscrew the caps at the end of each pipe Purging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCracked Pipe 50 Pa. The joint must be accessible and serviceableCorrect Inclined Outer DiameterDrain hose installation Purging the connected pipes Connect a drain hose to the drain plugEnsure that condensation draining is adequate Adding Refrigerant Please fill in with indelible ink  the factory refrigerant charge of the product1975 To check for gas leaks on the indoor unit Performing the gas leak testsTo check for gas leaks on the outdoor unit Leak test with nitrogen before opening valvesThen place the indoor unit on the installation plate Fixing the indoor unit in placeFixing the outdoor unit in place Final Check and Trial Operation After tube contraction work is completed, wrap it with How to connect your extended power cablesApply heat to the contraction tube to contract it Insulation tape to finishPage 02-201-24-18 42 27Samsung 7267864, € 0.07/min 05 133Air Conditioner
Related manuals
Manual 41 pages 50.29 Kb Manual 41 pages 10.61 Kb Manual 43 pages 43.79 Kb Manual 39 pages 33.67 Kb Manual 43 pages 50.37 Kb Manual 41 pages 45.51 Kb Manual 23 pages 13.22 Kb Manual 43 pages 9.83 Kb