Samsung AQV12PWCNCEE manual Purging the connected pipes, Connect a drain hose to the drain plug

Page 34

Installing and connecting the drain hose of the outdoor unit

While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate. For adequate draining, do the following:

1. Insert the drain plug into the drain hole on the underside of the outdoor unit.

• To avoid drain plug from contacting the ground, secure gap between the

Drain hole

 

ground and the bottom surface of the outdoor unit.

Drain plug

 

 

 

 

Bottom surface of outdoor unit

2. Connect a drain hose to the drain plug.

Drain hole

 

Drain plug

Drain hose

Snow-proof hood

3. Ensure that condensation draining is adequate.

• In areas with heavy snow fall, piled snow could block the air intake.

 

 

 

 

 

 

 

 

To avoid this incident, install a frame that is higher than estimated snow

Estimated

fall. In addition, install a snow-proof hood to avoid snow from piling on the

snow

 

fall

 

 

 

 

outdoor unit.

 

Frame

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground

Purging the connected pipes

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

The outdoor unit is loaded with sufficient R410A refrigerant. Do not vent R410A into atmosphere: it is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975.

You should purge the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction of cooling capacity and malfunction. Refrigerant for air purging is not charged in the outdoor unit. Use Vacuum Pump as seen in the picture.

• When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first

before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle

abnormally high. It may cause explosion and injury.

1.Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.

2.Tighten the flare nut first with your hands, and then with a torque wrench, applying the following torque:

• Excessive torque can be cause of gas leakage.

• Make the electrical connection and leave the system into“stand by mode”. Do not turn on the system!

This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve - EEV -).

Outdoor unit

Indoor unit

 

Gas pipe side

 

Liquid pipe side

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

34

Image 34
Contents Page Contents Follow directions Safety precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning Checking before use Operation rangesMain parts Power buttonChecking the name of the parts DisplayChecking the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasic function Button to adjust the temperature PressPress the Air swing button on the remote controller Adjusting the air flow directionUsing the Turbo function Vertical air flowMode When the air conditioner is on and in cool/heat modePress the button on the remote controller Press the Time Up or Time Down button to set the timePress the On Timer/Off Timer button Setting the On/Off timerAdditional options available in On timer mode If the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer Turn off automaticallyUsing the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on Cleaning the outdoor unit heat exchanger Cleaning the air conditionerCleaning the indoor unit Opening the panelOpen the panel and put the Air filter out Cleaning the air filterRemoving the Air filter Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Flow movement changes. It is normal Outdoor unit Heat exchanger during Heat mode in winterConnection Included Models Remark General informationAQV09P, AQV12P, AQV18P, AQV24P Power supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitSpace Requirements for Outdoor Unit When installing 1 outdoor unitWhen installing more than 1 outdoor unit Top view Side viewAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsCable specification Connecting the assembly cableConnecting the cable Each wire is labeled with the corresponding terminal number InstallationCut off the remaining foam insulation Smooth the cut edgesPass the pipe through the hole in the wall Unscrew the caps at the end of each pipe Purging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCracked Pipe 50 Pa. The joint must be accessible and serviceableCorrect Inclined Outer DiameterDrain hose installation Connect a drain hose to the drain plug Purging the connected pipesEnsure that condensation draining is adequate Adding Refrigerant  the factory refrigerant charge of the product Please fill in with indelible ink1975 To check for gas leaks on the indoor unit Performing the gas leak testsTo check for gas leaks on the outdoor unit Leak test with nitrogen before opening valvesFixing the indoor unit in place Then place the indoor unit on the installation plateFixing the outdoor unit in place Final Check and Trial Operation After tube contraction work is completed, wrap it with How to connect your extended power cablesApply heat to the contraction tube to contract it Insulation tape to finishPage 02-201-24-18 42 27Samsung 7267864, € 0.07/min 05 133Air Conditioner