Samsung AQV09PWCNCEE, AQV09PWCNEUR, AQV12PWCXCEE, AQV09PWCXCEE, AQV12PWCNCEE Drain hose installation

Page 33

Drain hose installation

1.If necessary, connect the 2-meter extension drain hose to the drain hose.

2.If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.

3. Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.

• If you do not use the other drain hose hole, block it with a rubber stopper.

4.

Pass the drain hose under the refrigerant pipe, keeping the drain hose

Shield

 

tight.

 

 

 

5.

Pass the drain hose through the hole in the wall. Check if it slants

 

 

 

Drain hose

 

downwards as seen in the picture.

 

 

 

 

Drain hose hole

Extension drain hose

ENGLISH

• The hose will be fixed permanently into position after finishing the installation and the gas leak test; refer to page

37~38 for further details.

Make sure the installed direction of the drain hose is correct.

Inadequate installation may cause condensate water leakage.

If the drain hose is routed inside the room, insulate the hose so that dripping condensation does not damage the furniture or floors.

DO NOT WALL UP THE DRAIN HOSE CONNECTION !

Drain hose connection must be easy accessible and serviceable.

Changing direction of the drain hose

Change the direction only when it is necessary.

1.Detach the rubber cap with the plier.

2.Detach the drain hose by pulling it and turning to the left.

3.Insert the drain hose by fixing it with the screw into the groove of the drain hose and the outlet of the drain pan.

Screw hole

Screw

Drain hose

4.

Attach the rubber cap with a screwdriver by turning it to the right until it

Drain pan outlet

 

fixes to the end of the groove.

 

 

 

 

5.

Check for leakage on both side of the drain outlet.

Rubber cap

 

 

Pour the water in direction of arrow.

Direction of the drained water

 

Make sure the indoor unit is in upright position when you pour water to check for leakage.

Make sure that the water does not overflow onto the electrical part.

33

Image 33 Contents
Page Contents Important safety symbols and precautions Safety precautionsFollow directions Wall socketFor Using For Cleaning Operation ranges Checking before useChecking the name of the parts Power buttonMain parts DisplayRemote controller buttons Checking the remote controllerBattery changing time Remote controller displayStoring the remote controller Inserting the batteriesBasic function Press Button to adjust the temperatureUsing the Turbo function Adjusting the air flow directionPress the Air swing button on the remote controller Vertical air flowPress the button on the remote controller When the air conditioner is on and in cool/heat modeMode Press the Time Up or Time Down button to set the timeSetting the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode From the moment you have set the timer Using the Smart Saver functionIf the air conditioner is on If the air conditioner is off Turn off automaticallyUsing the Quiet function Using the Auto Clean functionWhen the air conditioner is turned on Cleaning the indoor unit Cleaning the air conditionerCleaning the outdoor unit heat exchanger Opening the panelRemoving the Air filter Cleaning the air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaPeriodical checks Maintaining the air conditionerTroubleshooting Outdoor unit Heat exchanger during Heat mode in winter Flow movement changes. It is normalConnection General information Included Models RemarkAQV09P, AQV12P, AQV18P, AQV24P Installing the unit Choosing the installation locationPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyOutdoor Unit Where sulfide gas existsWhen installing more than 1 outdoor unit When installing 1 outdoor unitSpace Requirements for Outdoor Unit Top view Side viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Installation Each wire is labeled with the corresponding terminal numberSmooth the cut edges Cut off the remaining foam insulationPass the pipe through the hole in the wall Cutting or extending the pipe Purging the indoor unitUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareCorrect Inclined Pipe 50 Pa. The joint must be accessible and serviceableCracked Outer DiameterDrain hose installation Purging the connected pipes Connect a drain hose to the drain plugEnsure that condensation draining is adequate Adding Refrigerant Please fill in with indelible ink  the factory refrigerant charge of the product1975 To check for gas leaks on the outdoor unit Performing the gas leak testsTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesThen place the indoor unit on the installation plate Fixing the indoor unit in placeFixing the outdoor unit in place Final Check and Trial Operation Apply heat to the contraction tube to contract it How to connect your extended power cablesAfter tube contraction work is completed, wrap it with Insulation tape to finishPage Samsung 7267864, € 0.07/min 42 2702-201-24-18 05 133Air Conditioner