Weil-McLain PLUS-E017-A/1206 manual Wiring a system circulator, Routing line voltage wiring

Page 31

Manual • Installation • Start-Up

• Usage • Maintenance • Parts

 

 

 

gas

 

 

 

B3 Field wiring —

 

Gas boilers only (continued)

Wiring a system circulator

1.For combined systems, to activate a system circu- lator when the Boiler circulator operates, wire as shown at bottom of Figure 17, page 30.

2.You must install a relay as shown. DO NOT wire in parallel with the Boiler circulator. See CAUTION in Figure 17.

4.Install a summer/winter switch (Figure 19, item 7) across terminals 1 and 2 to force fixed-temperature operation during summer months. (When the switch is closed, boiler will attempt to maintain constant temperature.)

5.Route sensor wires through the grommeted hole at right of the electrical entrance (see Figure 18).

Routing line voltage wiring

1.Route line voltage connections to the jacket open- ings shown in Figure 18.

Water heater thermostat

1.Connect PLUS water heater aquastat terminals

“C” and “1” to Gas boiler low voltage ter- minal strip between terminals 3 and 4 (Figure 9, item 3).

Low voltage connections

(Fig. 18)

1.Connect low voltage wiring to low voltage termi- nal strip (Figure 19, page 32, item 1) as shown in Figure 19 and the boiler wiring diagram.

2.Route all low voltage wires through grommeted jacket opening to right of low voltage terminal strip, as shown in Figure 18.

Room thermostat (space heating)

1.For combined space heating/water heating systems, connect Figure 19, item 2, room thermostat or end switch (isolated contact only) between terminals 5 and 6.

2.Install thermostat on inside wall away from influ- ences of drafts, hot or cold water pipes, lighting fixtures, television, sunrays, or fireplaces.

3.Thermostat anticipator (if applicable):

a.If connected directly to boiler, set for 0.1 amps.

b.If connected to relays or other devices, set to match total electrical power requirements of connected devices. See device manufacturers’ specifications and thermostat instructions for details.

Outdoor temperature sensor

1.Outdoor reset operation applies only to combined space heating/water heating systems.

2.Connect outdoor temperature sensor (Figure 19, item 6) between terminals 1 and 2 to enable out-

door reset operation of the Gasboiler. If fixed-temperature operation is required, do not install outdoor sensor.

3.Mount sensor on exterior wall, shielded from di- rect sunlight or flow of heat or cooling from other sources.

Additional limits

1.Connect additional limit controls and interlocks between the terminals shown in Figure 19.

2.Controls connected between terminals 6 and 7 (see Figure 19, item 4) will cause a soft lockout (automatic reset). When limit(s) closes, boiler will resume normal operation.

3.Controls connected between terminals 6 and 8 (see Figure 19, item 5). will cause a hard lockout (manual reset). The boiler will only restart after the Ultra display panel RESET switch is pressed.

Figure 18 Routing field wiring

Part Number PLUS-E017-A/1206

31

Image 31
Contents Plus Line Hazard definitions Read this page firstContents Zoning with pumps Gold Plus 30/40/60/80 or Plus 40/60/80 Plus 100/110/119 Multiple water heater applications Plus 100/110/119 see Figure A1 Pre-installationCodes Gold Plus 30/40/60/80 or Plus 40/60/80 see FigureCode restrictions National Standard Plumbing Code RestrictionsUniform Plumbing Code Water heater piping Temperature & pressure T & P relief valveAir vent Drain valve A2 Water heater piping Gold Plus 30/40/60/80 Or Plus 40/60/80 Option Plus 100/110/119 Option A2 Water heater piping General piping information Thermal expansion Water hammerBoiler water Water heater wiring Filling the inner domestic water tank A4 Water heater start-upA4 Water heater start-up  General notes A5 Adjusting water heater temperatureSetting the thermostat A5 Adjusting water heater temperature Gold Plus 30/40/60/80 Plus 100/110/119 Plus 40/60/80 Maintenance schedule annual service technician A6 Water heater maintenanceFilling Draining A6 Water heater maintenance Draining inner domestic water tank · Recirculation A7 Recirculation and heat tracing· Self-regulating heat tracing Components Gas-fired boiler applications B1. Install system water pipingSizing space heat system piping System water piping methodsExpansion tank and make-up water Boiler circulatorZoning with zone valves Install system water piping space heatingZoning with circulators B1 Install system water piping space heatingCombined space heating/water heating applications Install boiler-to-water heater pipingDedicated water heating-only applications For boilers other than Ultra Gas, see page 67 for ratings Wiring water heater circulator B3 Field wiring Gas boilers onlyInstallation must comply with Wiring boiler circulatorWater heater thermostat Wiring a system circulatorRouting line voltage wiring Outdoor temperature sensorLow voltage field wiring connections Water heater operation Follow boiler manual Water heater operation setupB4 Start-up Gas boilers only Set space heating operationOperating information Verify water heater operationReplace jacket front door Boiler-side piping except Gas Boiler-side piping except Gas  Wiring optionsPrimary/secondary piping 60 Pump relays and 3-way priority valve and priority relay 58 or , page 59 Priority using 2-way valve Tions Applications Multiple water heaters This diagram Special considerations Connecting water heater to steam boilerSteam boiler application Boiler-side wiring & controls except Gas Boiler Models Boiler-side wiring & controls except Gas Circulators Zone ValvesSystem piping Typical wiringPump zones Primary/secondary piping sys- temsBoiler-side wiring & controls except Gas  Zoning with pumps Using pump relays No domestic priority 39 using 2-way water heater zone valve and no priority valve Zoning with 4-wire zone Valves No domestic priority Zoning with 3-wire zone valves No domestic priority Plus 40/60/80 Boiler-side wiring & controls except Gas  39 using 2-way Water heater zone valve and no priority valve Boiler-side wiring & controls except Gas  Room Thermostat Pump relays Replacement parts Series 3 only Gold Plus 30/40/60/80 or Plus 40/60/80 Replacement parts Weil-McLain Part Description Size ManufacturerPlus 100/110/119 Replacement parts Plus 100/110/119 Series Dimensions PLUS-Line indirect water heaters, Series Water heater dimensionsMBH Water heater performance ratingsWeil-McLain Limited Warranties

PLUS-E017-A/1206 specifications

The Weil-McLain PLUS-E017-A/1206 is a high-performance heating boiler that reflects the brand's commitment to quality engineering and advanced technology. This model is renowned for its efficiency and reliability, making it a preferred choice for both residential and commercial heating applications.

One of the standout features of the PLUS-E017-A/1206 is its exceptional efficiency rating. The boiler employs advanced condensing technology, which allows it to utilize the latent heat in exhaust gases. This means it can achieve efficiency levels of over 90%, significantly reducing energy consumption and lowering utility bills. The unit also complies with stringent regulatory standards, making it an environmentally friendly heating solution.

The PLUS-E017-A/1206's compact design is another significant characteristic, allowing for easy installation even in limited spaces. It is built with durable materials that enhance its longevity and efficiency. The sleek appearance of the unit also makes it suitable for various settings, maintaining aesthetic appeal while delivering powerful heating performance.

This boiler is equipped with advanced controls and a user-friendly interface, offering precise temperature management and efficient operation. The control panel showcases a digital display, enabling easy monitoring of system performance. Additionally, it allows for integration with smart home systems, providing users with enhanced control over their heating systems remotely.

Safety features are paramount in the PLUS-E017-A/1206. It includes multiple safety mechanisms designed to prevent overheating and pressure issues, ensuring worry-free operation. These elements, combined with Weil-McLain’s reputation for durable construction, contribute to the boiler’s overall reliability.

The PLUS-E017-A/1206 is designed with ease of maintenance in mind. It features accessible components that can be easily serviced, minimizing downtime and reducing maintenance costs. With Weil-McLain’s extensive network of support, users can rely on expert assistance when needed.

Overall, the Weil-McLain PLUS-E017-A/1206 is a robust heating solution that combines efficiency, safety, and advanced technology. Its range of features makes it an excellent choice for those seeking a dependable boiler that delivers consistent performance and energy savings. Whether for a home or business, the PLUS-E017-A/1206 represents a smart investment in heating technology.