Weil-McLain PLUS-E017-A/1206 Connecting water heater to steam boiler, Special considerations

Page 44

PLUS LINEIndirect-Fired Water Heaters – Series 3

C Boiler-side piping (except Gas)continued

ON STEAM BOILER APPLICATIONS ONLY — You must replace the automatic air vent supplied with the water heater with a manual air vent. Failure to do so could result in severe personal injury, death or substantial property damage.

Connecting water heater to steam boiler

When designing steam and domestic hot water sys- tems, there are some key issues that must be taken into consideration during the initial design phase. By designing the system properly from the start, you can avoid problems and have a hot water loop in a steam boiler system.

Special considerations:

Keep the loop temperature below the flash point. Flashing can result in noise and circulator damage or shortened life.

Be sure the loop is completely closed, with no au- tomatic air vents or anything that could allow air to enter the system when the pump shuts off. Use manual air vents only to prevent the possibility of flooding the boiler.

Pipe supply from one side of the boiler, return to the opposite side.

Supply from a tapping that is high enough to prevent introducing sediment into the piping and circulator yet still positions the circulator below the water line. Avoid the mud leg of the boiler.

Use an all bronze circulator (avoid wet rotor circula- tors). This will reduce clogging and will resist the corrosion potential from the steam condensate.

Make sure the circulator is properly sized. If the pump runs too far out on the curve, cavitation potential increases significantly.

Return piping should be dedicated domestic re- turn.

Use (2) flow/check valves as shown to reduce the potential for gravity circulation. Do not use spring- loaded check valves in place of the flow/check valves shown in Figure 29 on page 45.

Installation and start-up of water heaters connected to steam boilers

See Figure 29, page 45, for suggested piping schematic. Pipe the domestic water connections to the water heater per Section A of this manual.

Boiler connections for the water heater must be below the water line.

For steam piping, refer to the boiler manual.

Replace the automatic air vent furnished with the water heater with a manual air vent.

Wire the water heater and circulator to the boiler per suggested wiring in Figure 29.

To fill the boiler and water heater:

Close isolation valves 5 and 6 (Figure 29) to isolate the boiler.

Fill the boiler to the recommended water level per the boiler manual. Fill the domestic side of the water heater per Section A of this manual.

To fill the water heater outer tank with boiler water, isolation valves 5 and 6 must remain closed. Valves 1 and 2 should be fully opened. Drain valves 3 and 4 should also be fully opened.

Open the water heater manual air vent to bleed the system of air.

Open the water heater manual air vent one turn only.

Fill the boiler/water heater system through drain valve 3 until a steady stream of water flows through drain valve 4, initially purging the system of air.

Continue to fill the boiler/water heater system while closing drain valve 4.

When drain valve 4 is fully closed and a steady stream of water is exiting at the air vent, close the manual air vent tightly. Drain valve 3 can now be closed.

Water may spray from the manual air vent.

Open isolation valve 5 (at the front of the boiler). Then open valve 6.

Start the boiler per instructions given in the boiler manual.

44

Part Number PLUS-E017-A/1206

Image 44
Contents Plus Line Read this page first Hazard definitionsContents Zoning with pumps Gold Plus 30/40/60/80 or Plus 40/60/80 Plus 100/110/119 Multiple water heater applications A1 Pre-installation CodesGold Plus 30/40/60/80 or Plus 40/60/80 see Figure Plus 100/110/119 see FigureUniform Plumbing Code RestrictionsCode restrictions National Standard Plumbing Code Air vent Temperature & pressure T & P relief valveWater heater piping A2 Water heater piping  Drain valveGold Plus 30/40/60/80 Or Plus 40/60/80 Option Plus 100/110/119 Option A2 Water heater piping Thermal expansion Water hammer General piping informationBoiler water Water heater wiring A4 Water heater start-up Filling the inner domestic water tankA4 Water heater start-up  A5 Adjusting water heater temperature General notesGold Plus 30/40/60/80 Plus 100/110/119 Plus 40/60/80 A5 Adjusting water heater temperature Setting the thermostat A6 Water heater maintenance Maintenance schedule annual service technicianDraining inner domestic water tank A6 Water heater maintenance Filling Draining · Self-regulating heat tracing A7 Recirculation and heat tracing· Recirculation Components B1. Install system water piping Gas-fired boiler applicationsSystem water piping methods Expansion tank and make-up waterBoiler circulator Sizing space heat system pipingInstall system water piping space heating Zoning with zone valvesB1 Install system water piping space heating Zoning with circulatorsDedicated water heating-only applications Install boiler-to-water heater pipingCombined space heating/water heating applications For boilers other than Ultra Gas, see page 67 for ratings B3 Field wiring Gas boilers only Installation must comply withWiring boiler circulator Wiring water heater circulatorWiring a system circulator Routing line voltage wiringOutdoor temperature sensor Water heater thermostatLow voltage field wiring connections Follow boiler manual Water heater operation setup B4 Start-up Gas boilers onlySet space heating operation Water heater operationReplace jacket front door Verify water heater operationOperating information Boiler-side piping except Gas Wiring options Boiler-side piping except Gas Primary/secondary piping 60 Pump relays and 3-way priority valve and priority relay 58 or , page 59 Priority using 2-way valve Tions Applications Multiple water heaters This diagram Connecting water heater to steam boiler Special considerationsSteam boiler application Boiler-side wiring & controls except Gas Boiler-side wiring & controls except Gas  CirculatorsZone Valves Boiler ModelsTypical wiring System pipingPrimary/secondary piping sys- tems Pump zonesBoiler-side wiring & controls except Gas  Zoning with pumps Using pump relays No domestic priority 39 using 2-way water heater zone valve and no priority valve Zoning with 4-wire zone Valves No domestic priority Zoning with 3-wire zone valves No domestic priority Plus 40/60/80 Boiler-side wiring & controls except Gas  39 using 2-way Water heater zone valve and no priority valve Boiler-side wiring & controls except Gas  Room Thermostat Pump relays Replacement parts Series 3 only Replacement parts  Gold Plus 30/40/60/80 or Plus 40/60/80Description Size Manufacturer Weil-McLain PartPlus 100/110/119 Replacement parts Plus 100/110/119 Series Water heater dimensions Dimensions PLUS-Line indirect water heaters, SeriesWater heater performance ratings MBHWeil-McLain Limited Warranties

PLUS-E017-A/1206 specifications

The Weil-McLain PLUS-E017-A/1206 is a high-performance heating boiler that reflects the brand's commitment to quality engineering and advanced technology. This model is renowned for its efficiency and reliability, making it a preferred choice for both residential and commercial heating applications.

One of the standout features of the PLUS-E017-A/1206 is its exceptional efficiency rating. The boiler employs advanced condensing technology, which allows it to utilize the latent heat in exhaust gases. This means it can achieve efficiency levels of over 90%, significantly reducing energy consumption and lowering utility bills. The unit also complies with stringent regulatory standards, making it an environmentally friendly heating solution.

The PLUS-E017-A/1206's compact design is another significant characteristic, allowing for easy installation even in limited spaces. It is built with durable materials that enhance its longevity and efficiency. The sleek appearance of the unit also makes it suitable for various settings, maintaining aesthetic appeal while delivering powerful heating performance.

This boiler is equipped with advanced controls and a user-friendly interface, offering precise temperature management and efficient operation. The control panel showcases a digital display, enabling easy monitoring of system performance. Additionally, it allows for integration with smart home systems, providing users with enhanced control over their heating systems remotely.

Safety features are paramount in the PLUS-E017-A/1206. It includes multiple safety mechanisms designed to prevent overheating and pressure issues, ensuring worry-free operation. These elements, combined with Weil-McLain’s reputation for durable construction, contribute to the boiler’s overall reliability.

The PLUS-E017-A/1206 is designed with ease of maintenance in mind. It features accessible components that can be easily serviced, minimizing downtime and reducing maintenance costs. With Weil-McLain’s extensive network of support, users can rely on expert assistance when needed.

Overall, the Weil-McLain PLUS-E017-A/1206 is a robust heating solution that combines efficiency, safety, and advanced technology. Its range of features makes it an excellent choice for those seeking a dependable boiler that delivers consistent performance and energy savings. Whether for a home or business, the PLUS-E017-A/1206 represents a smart investment in heating technology.