B4 Start-up

Gas boilers only

 

 

 

Follow boiler manual

Water heater operation setup

1.Follow all procedures in the Gas boiler manual to start up and verify operation of the boiler.

Set space heating operation

Verify space heating mode

1.Press the “Mode” button until the display shows “Para.” This is the parameter mode.

2.Press the “Step” button until the display first digit shows “3.”

3.The last digit must show “1.” If any other number displays, press the “+” button until “1” shows in the right-hand digit. Press the “Store” button to save this setting.

Set space heating target temperature

1.Press the control panel “Step” button until the display first digit shows “4.” The right 3 digits show the outlet water temperature setting.

2.Press the “+” or “-” button to change the setting to the desired outlet water temperature. (The factory default setting is 190 °F.)

a.Outdoor sensor installed — Setting is the target temperature for outdoor temperature at or below

32 °F. At higher outside temperatures, the PhD control module calculates the target temperature. (See Control Supplement for detailed discussion of outdoor reset.)

When a summer/winter switch is used, closing the switch will disable the boiler (space heating) circulator during summer operation.

b.Outdoor sensor not installed — Setting is the target temperature at all times.

3.Press the “Store” button to save the setting.

Water heater operation

1.The PLUS water heater thermostat must be con- nected to low voltage terminal strip terminals 3 and 4 as shown on page 10.

2.When the water heater thermostat calls for heat, the module shuts down the boiler circulator, acti- vates the water heater circulator and immediately sets target outlet water temperature to 190°F. This provides automatic priority heat allocation to the indirect water heater for maximum response and recovery.

3.The water heater circulator continues for 30 seconds after the heating cycle to deliver the most possible heat.

1.Go to step 2 if the control is in Parameter mode already. Press the “Mode” button until the display shows “Para” (parameter mode).

2.Press the “Step” button until the display first digit shows “2.”

3.The last digit must show “1.” If any other number displays, press the “+” button until “1” shows in the right-hand digit. Press the “Store” button to save this setting.

4.The PhD control module turns on the PLUS circulator when the indirect water heater operating control closes. The control module shuts off the boiler circulator (stops space heating) during calls for DHW heating.

Verify space heating operation

NOTE: “[ _ _ _ _ ]” in the following indicates the

characters that should show on the display panel. “180” in the right 3 places means the display shows the measured boiler water temperature. The number shown will not necessarily be 180.

1.Turn down aquastat on PLUS tank. If necessary, turn off power and remove one of the PLUS aqua- stat wires to ensure boiler will not receive a DHW heat call.

2.Turn off power to boiler at service switch.

3.Wait a few seconds, then turn on power to boiler.

[A180] (self-checkon power-up, for a few seconds) [0180] (no call for heat)

4.Raise room thermostat to call for heat.

[5180] (blower/circulator on) The blower and boiler circu- lator energize and the control checks for air flow.

[1180] (prepurge) After a few seconds delay (control self- check), blower speed will increase to ignition speed. The blower will run in prepurge for 10 seconds.

[2180] (ignition) After prepurge, the control module opens the gas valve and starts ignition spark.

a.If burner flame proves within 4.5 seconds, burner continues to fire. Burner will fire at start-up rate — 50% of maximum input — for about 10 seconds to allow flame to stabilize.

b.If burner flame does not prove within 4.5 sec- onds, control module attempts ignition sequence

again. Flame must prove within 5 attempts or control will lockout (display will show [E 02]).

c.Verify flame failure operation by closing boiler manual gas cock to prevent gas flow. Open manual gas valve after testing.

Part Number PLUS-E017-A/1206

33

Image 33
Contents Plus Line Hazard definitions Read this page firstContents Zoning with pumps Gold Plus 30/40/60/80 or Plus 40/60/80 Plus 100/110/119 Multiple water heater applications Codes A1 Pre-installationGold Plus 30/40/60/80 or Plus 40/60/80 see Figure Plus 100/110/119 see FigureRestrictions Code restrictions National Standard Plumbing CodeUniform Plumbing Code Temperature & pressure T & P relief valve Water heater pipingAir vent Drain valve A2 Water heater piping Gold Plus 30/40/60/80 Or Plus 40/60/80 Option Plus 100/110/119 Option A2 Water heater piping General piping information Thermal expansion Water hammerBoiler water Water heater wiring Filling the inner domestic water tank A4 Water heater start-upA4 Water heater start-up  General notes A5 Adjusting water heater temperatureA5 Adjusting water heater temperature  Setting the thermostatGold Plus 30/40/60/80 Plus 100/110/119 Plus 40/60/80 Maintenance schedule annual service technician A6 Water heater maintenanceA6 Water heater maintenance  Filling DrainingDraining inner domestic water tank A7 Recirculation and heat tracing · Recirculation· Self-regulating heat tracing Components Gas-fired boiler applications B1. Install system water pipingExpansion tank and make-up water System water piping methodsBoiler circulator Sizing space heat system pipingZoning with zone valves Install system water piping space heatingZoning with circulators B1 Install system water piping space heatingInstall boiler-to-water heater piping Combined space heating/water heating applicationsDedicated water heating-only applications For boilers other than Ultra Gas, see page 67 for ratings Installation must comply with B3 Field wiring Gas boilers onlyWiring boiler circulator Wiring water heater circulatorRouting line voltage wiring Wiring a system circulatorOutdoor temperature sensor Water heater thermostatLow voltage field wiring connections B4 Start-up Gas boilers only Follow boiler manual Water heater operation setupSet space heating operation Water heater operationVerify water heater operation Operating informationReplace jacket front door Boiler-side piping except Gas Boiler-side piping except Gas  Wiring optionsPrimary/secondary piping 60 Pump relays and 3-way priority valve and priority relay 58 or , page 59 Priority using 2-way valve Tions Applications Multiple water heaters This diagram Special considerations Connecting water heater to steam boilerSteam boiler application Boiler-side wiring & controls except Gas Circulators Boiler-side wiring & controls except Gas Zone Valves Boiler ModelsSystem piping Typical wiringPump zones Primary/secondary piping sys- temsBoiler-side wiring & controls except Gas  Zoning with pumps Using pump relays No domestic priority 39 using 2-way water heater zone valve and no priority valve Zoning with 4-wire zone Valves No domestic priority Zoning with 3-wire zone valves No domestic priority Plus 40/60/80 Boiler-side wiring & controls except Gas  39 using 2-way Water heater zone valve and no priority valve Boiler-side wiring & controls except Gas  Room Thermostat Pump relays Replacement parts Series 3 only Gold Plus 30/40/60/80 or Plus 40/60/80 Replacement parts Weil-McLain Part Description Size ManufacturerPlus 100/110/119 Replacement parts Plus 100/110/119 Series Dimensions PLUS-Line indirect water heaters, Series Water heater dimensionsMBH Water heater performance ratingsWeil-McLain Limited Warranties

PLUS-E017-A/1206 specifications

The Weil-McLain PLUS-E017-A/1206 is a high-performance heating boiler that reflects the brand's commitment to quality engineering and advanced technology. This model is renowned for its efficiency and reliability, making it a preferred choice for both residential and commercial heating applications.

One of the standout features of the PLUS-E017-A/1206 is its exceptional efficiency rating. The boiler employs advanced condensing technology, which allows it to utilize the latent heat in exhaust gases. This means it can achieve efficiency levels of over 90%, significantly reducing energy consumption and lowering utility bills. The unit also complies with stringent regulatory standards, making it an environmentally friendly heating solution.

The PLUS-E017-A/1206's compact design is another significant characteristic, allowing for easy installation even in limited spaces. It is built with durable materials that enhance its longevity and efficiency. The sleek appearance of the unit also makes it suitable for various settings, maintaining aesthetic appeal while delivering powerful heating performance.

This boiler is equipped with advanced controls and a user-friendly interface, offering precise temperature management and efficient operation. The control panel showcases a digital display, enabling easy monitoring of system performance. Additionally, it allows for integration with smart home systems, providing users with enhanced control over their heating systems remotely.

Safety features are paramount in the PLUS-E017-A/1206. It includes multiple safety mechanisms designed to prevent overheating and pressure issues, ensuring worry-free operation. These elements, combined with Weil-McLain’s reputation for durable construction, contribute to the boiler’s overall reliability.

The PLUS-E017-A/1206 is designed with ease of maintenance in mind. It features accessible components that can be easily serviced, minimizing downtime and reducing maintenance costs. With Weil-McLain’s extensive network of support, users can rely on expert assistance when needed.

Overall, the Weil-McLain PLUS-E017-A/1206 is a robust heating solution that combines efficiency, safety, and advanced technology. Its range of features makes it an excellent choice for those seeking a dependable boiler that delivers consistent performance and energy savings. Whether for a home or business, the PLUS-E017-A/1206 represents a smart investment in heating technology.