•Non-Combustible Sealant Material
Sealants which will not ignite and burn: Super Calstick
After completing the framing and applying the facing mate-
rial (drywall) over the framing, a bead of
Only
•Cardboard OR Metal Template
A cardboard template of the front is printed on the outside of the shipping box. It measures 1/8 in. (3 mm) bigger all the way around than the actual front. Cut out the template along the outside of the line for use in your installation.
A metal template is also available for more durable continued use remaining accurate over time. See page 64 for catalog number.
F. Mantel
A combustible mantel may be positioned no lower than 60 in. (1524mm) from the base of the fireplace.
The combustible mantel may have a maximum depth of 12 in. (305mm). Combustible trim pieces that project no more than 3/4 in. (19mm) from the face of the fireplace can be placed no closer than 6 in. (152mm) from the side of the decorative front. See Figure 10.9
Combustible trim must not cover:
•the metal surfaces of the fireplace
•where the
•the space between the metal face of the fireplace and framing members.
Refer to page 37 for clearance requirements
Warning Fire Risk!
Maintain clearances
Use only
Framing or finishing material used on the front of, or in front of, the appliance closer than the minimums listed, must be constructed entirely of
WARNING! Fire Risk
Hearth & Home Technologies is not responsible for discol- oration, cracking or other material failures of finishing ma- terials due to heat exposure or smoke.
•Choose finishing materials carefully.
Mantel | Clearances are |
| from bottom of |
| appliance to lower |
| edge of mantel or |
Trim | trim |
60in.
(1524mm)
48in.
(1219mm)
Figure 10.9 Mantel Specifications
4/20/11 | Heatilator • Constitution EPA Fireplace • | Page 57 |