Desa LAME-MAX Golden Oak installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

AIR FOR COMBUSTION AND VENTILATION

7

Ventilation Air

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

(see options 1 and 2, Figure 2). You can also remove door into

Room,

Or

Option 2

adjoining room (see option 3, Figure 2). Follow the National Fuel

Option 1

Remove

Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option 3

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

For morevisit www..com

110399-01B

Image 7
Contents What to do if YOU Smell GAS Unvented VENT-FREE GAS LOG HeaterSafety Information Table of ContentsSafety Information Unpacking Optional Remote Control AccessoriesProduct Identification Local CodesAIR for Combustion and Ventilation Product FeaturesDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationSee options 1 and 2, . You can also remove door into Ventilation AIRVentilation Air From Inside Building Ventilation Air From OutdoorsMeasured at 14 depth InstallationCheck GAS Type LOG Sizing RequirementsMinimum Noncombustible Material Clearances If Not Using MantelFloor Clearances Mantel ClearancesDetermining Minimum Mantel Clearance Area of Various Standard Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Installation Items NeededAttach base assembly to fireplace floor using two masonry Trol accessories, do so at this time Remote-Ready ModelsOnly. Follow all directions provided with accessory Drill holes at marked locations using 3/16 drill bitExternal Regulator With Vent Pointing Down Connecting to GAS SupplyChecking GAS Connections Pressure Testing gas Supply Piping systemClose equipment shutoff valve see , Pressure Testing Heater Gas Connections Installing LogsVintage Oak Two-Piece Log Set Golden Oak One-Piece Log Set Installing Vintage Oak Two-Piece Log SetGolden Oak Five-Piece Log Set Installing Golden Oak 5-Piece Log Set LogLighting Instructions Operating HeaterShutting Off Heater Manual Lighting ProcedureTo Turn OFF GAS to Appliance Thermostat Control OperationVariable Control Operation REMOTE-READY Models For Your Safety Read Before LightingFlame Adjustment Knob Ghrcta Series Operation Optional Remote OperationThermostat Control Operation Ghrc Series OperationMain Burner Inspecting BurnersPilot Flame Pattern Burner Primary AIR HolesWe also recommend that you keep the burner tube and pilot Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole LogsTroubleshooting Clean burner see Cleaning and Mainte Company ODS/pilot is partially clogged Clean ODS/pilot see CleaningGas odor even when control knob is in OFF Low line pressureFor Masonry and FACTORY-BUILT Metal Fireplace Optional Positioning of Thermostat Sensing BulbThermostat-Controlled Models Only Golden Oak Golden Oak 24 Remote-Ready 36 Remote-Ready SpecificationsReplacement Parts Wiring DiagramService Hints Technical ServiceAccessories ODS Pilot Natural Gas ODS Pilot Propane/LP Illustrated Parts BreakdownVariable MANUALLY-CONTROLLED FLAME-MAXVINTAGE OAK LOG Models Parts ListVariable MANUALLY-CONTROLLED FLAME-MAXGOLDEN OAK LOG Models Parts Available not Shown QTY From drawing.4 Natural GasParts Available not Shown THERMOSTAT-CONTROLLED FLAME-MAXGOLDEN OAK LOG Models Auxiliary Thermostat Mounting Clip REMOTE-READY FLAME-MAXGOLDEN OAK LOG Models Parts List VYD36PNA and HD36NR Parts List For . .com Owners Registration Form Postage Required 110399-01B Warranty Information