Desa SVYD18N installation manual TROUBLE- Shooting, Maintenance

Page 22

TROUBLE- SHOOTING

OBSERVED

POSSIBLE

 

PROBLEM

CAUSE

REMEDY

 

 

 

Continued

When ignitor button is pressed, there is spark at ODS/pilot but no ignition

1.Gas supply turned off or manual shutoff valve closed

2.Control knob not in PILOT position

3.Control knob not pressed in while in PILOT position

4.Air in gas lines when installed

5.ODS/pilot is clogged

6.Gas regulator setting is not correct

1.Turn on gas supply or open manual shutoff valve

2.Turn control knob to PILOT position

3.Press in control knob while in PILOT position

4.Continue holding down control knob. Repeat igniting operation until air is removed

5.Clean ODS/pilot (see Cleaning and Mainte- nance, page 21) or replace ODS/pilot assembly

6.Replace gas regulator

22

ODS/pilot lights but

1.

Control knob not fully

1.

Press in control knob

flame goes out when

 

pressed in

 

fully

control knob is

2.

Control knob not

2.

After ODS/pilot lights,

released

 

pressed in long enough

 

keep control knob

 

 

 

 

pressed in 30 seconds

 

3.

Safety interlock system

3.

Wait one minute for

 

 

has been triggered

 

safety interlock system

 

 

 

 

to reset. Repeat ignition

 

 

 

 

operation

 

4.

Manual shutoff valve

4.

Fully open manual

 

 

not fully open

 

shut-off valve

 

5.

Pilot flame not touching

5.

A) Contact local

 

 

thermocouple, which

 

natural gas company

 

 

allows thermocouple to

 

 

 

 

cool, causing pilot flame

 

B) Clean ODS/pilot

 

 

to go out. This problem

 

(see Cleaning and

 

 

could be caused by one

 

Maintenance, page 21)

 

 

or both of the following:

 

or replace ODS/pilot

 

 

A) Low gas pressure

 

assembly

 

 

B) Dirty or partially

 

 

 

 

clogged ODS/pilot

 

 

 

6.

Thermocouple connec-

6.

Hand tighten until

 

 

tion loose at control

 

snug, then tighten 1/4

 

 

valve

 

turn more

 

7.

Thermocouple damaged

7.

Replace thermocouple

 

8.

Control valve damaged

8.

Replace control valve

104024

Image 22
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information For use with this heater Operation Local Codes Product FeaturesSafety Pilot Piezo Ignition SystemVentilation AIR forProviding Adequate Ventilation Determining AIR Flow for Heater Location AIR for Combustion and VentilationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Check GAS Type InstallingMinimum Wall and Ceiling Clearances see Figure Top View Stove Cavity AssemblyFront View Side ViewLaying Down Stove On Side Attaching Stove Legs Attaching Stove Door Installing Installing GAS LOG Heater Into Stove Placing Heater Base In Stove CavityConnecting to GAS Supply Installation Items NeededSide View Back View Checking GAS Connections Gas ConnectionPressure Testing Heater Gas Connections Test Pressures Equal To or Less Than 1/2 PsigFor Your Safety Read Before Lighting Operating HeaterMatch, see Manual Lighting Procedure on HeaterOperating Heater Inspecting Burners Pilot Flame PatternODS/PILOT and Burner Cleaning and Maintenance Trouble ShootingTurn off heater and let cool before cleaning LogsMaintenance, TROUBLE- ShootingRefer to Air for Com Gas leak. See Warning Technical ServiceReplacement HintsIllustrated Parts Breakdown Parts List SCIVFC, Scivfb SCIVFG, Scivfr SCIVFC, Scivfb Accessory Valve GA5010104024 Warranty Information Keep this Warranty