Desa SVYD18N AIR for Combustion and Ventilation, Determining AIR Flow for Heater Location

Page 6

AIR FOR COMBUSTION AND VENTILATION

Continued

6

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

___________________ Btu/Hr

Gas water heater*

 

___________________ Btu/Hr

Gas furnace

 

___________________ Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

Total

= ___________________ Btu/Hr

Example: Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

30,000

Btu/Hr

Total

=

70,000

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200

Btu/Hr (maximum the space can support)

70,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

104024

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information For use with this heater Operation Local Codes Product FeaturesSafety Pilot Piezo Ignition SystemAIR for VentilationProviding Adequate Ventilation AIR for Combustion and Ventilation Determining AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Installing Check GAS TypeMinimum Wall and Ceiling Clearances see Figure Top View Stove Cavity AssemblyFront View Side ViewLaying Down Stove On Side Attaching Stove Legs Attaching Stove Door Installing Installing GAS LOG Heater Into Stove Placing Heater Base In Stove CavityConnecting to GAS Supply Installation Items NeededSide View Back View Checking GAS Connections Gas ConnectionPressure Testing Heater Gas Connections Test Pressures Equal To or Less Than 1/2 PsigFor Your Safety Read Before Lighting Operating HeaterMatch, see Manual Lighting Procedure on HeaterOperating Heater Inspecting Burners Pilot Flame PatternODS/PILOT and Burner Cleaning and Maintenance Trouble ShootingTurn off heater and let cool before cleaning LogsMaintenance, TROUBLE- ShootingRefer to Air for Com Gas leak. See Warning Technical ServiceReplacement HintsIllustrated Parts Breakdown Parts List SCIVFC, Scivfb SCIVFG, Scivfr SCIVFC, Scivfb Accessory Valve GA5010104024 Warranty Information Keep this Warranty