TROUBLE- SHOOTING
Continued
OBSERVED | POSSIBLE |
|
| |
PROBLEM | CAUSE | REMEDY | ||
|
|
|
|
|
Burner does not light | 1. | Inlet gas pressure is | 1. | Contact local natural |
after ODS/pilot is lit |
| too low |
| gas company |
| 2. | Burner orifice clogged | 2. | Clean burner (see |
|
|
|
| Cleaning and Mainte- |
|
|
|
| nance, page 21) or |
| 3. | Burner orifice diameter |
| replace burner orifice |
| 3. | Replace burner orifice | ||
|
| is too small |
|
|
|
|
|
|
|
Delayed ignition | 1. | Manifold pressure is | 1. | Contact local natural |
burner |
| too low |
| gas company |
| 2. | Burner orifice clogged | 2. | Clean burner (see |
|
|
|
| Cleaning and Mainte- |
|
|
|
| nance, page 21) or |
|
|
|
| replace burner orifice |
|
|
|
|
|
Burner backfiring | 1. | Burner orifice is | 1. | Clean burner (see |
during combustion |
| clogged or damaged |
| Cleaning and Mainte- |
|
|
|
| nance, page 21) or |
| 2. | Damaged burner |
| replace burner orifice |
| 2. | Replace damaged | ||
| 3. | Gas regulator defective |
| burner |
| 3. | Replace gas regulator | ||
|
|
|
| |
Slight smoke or odor | 1. Not enough air | 1. | Check burner for dirt | |
during initial opera- |
|
|
| and debris. If found, |
tion |
|
|
| clean burner (see |
|
|
|
| Cleaning and Mainte- |
| 2. | Gas regulator defective |
| nance, page 21) |
| 2. | Replace gas regulator | ||
| 3. | Residues from manu- | 3. | Problem will stop after |
|
| facturing processes |
| a few hours of opera- |
|
| and logs curing |
| tion |
|
|
|
| |
Heater produces a | 1. Turning control knob | 1. | Turn control knob to | |
whistling noise when |
| to HI position when |
| LO position and let |
burner is lit |
| burner is cold |
| warm up for a minute |
| 2. | Air in gas line | 2. | Operate burner until air |
|
|
|
| is removed from line. |
|
|
|
| Have gas line checked |
|
|
|
| by local natural gas |
| 3. | Air passageways on |
| company |
| 3. | Observe minimum | ||
|
| heater blocked |
| installation clearances |
| 4. | Dirty or partially |
| (see pages |
| 4. | Clean burners (see | ||
|
| clogged burner orifice |
| Cleaning and Mainte- |
|
|
|
| nance, page 21) or |
|
|
|
| replace burner orifice |
|
|
|
|
|
Moisture/condensation | 1. | Not enough combus- | 1. | Refer to Air for Com- |
noticed on windows |
| tion/ventilation air |
| bustion and Ventilation |
|
|
|
| requirements (pages |
Continued
104024
23