Desa MSVFBP AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Heater Location

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

__________________ Btu/Hr

 

 

 

 

Gas water heater*

__________________ Btu/Hr

Example:

 

 

 

Gas furnace

__________________ Btu/Hr

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

__________________ Btu/Hr

 

Vent-free heater

+

30,000

Btu/Hr

Gas fireplace logs

__________________ Btu/Hr

 

 

 

 

Total

=

70,000

Btu/Hr

Other gas appliances* + __________________ Btu/Hr

 

 

 

 

Total

= __________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

105986

5

For more information, visit www.desatech.com

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSUN Valley Stove Company Safety InformationLocal Codes Product FeaturesProduct Identification Providing Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsClearances to Combustibles InstallationCheck GAS Type Vent-Free Operation OnlyLift off corrugated box enclosing stove body crating Stove Cavity AssemblyAttaching Stove Legs Fastening Heater Base to Stove Drop Bottom Installing GAS LOG Heater Into StoveInstallation Items Needed Connecting to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Installing Optional Wireless HAND-HELD Remote Control Installing Optional Wall Mounted Thermostat GWMT1Lighting Instructions Msvfbpr REMOTE-READY Models For Your Safety Read Before LightingOperating Heater Optional Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Variable Control Operation Lighting Instructions Msvfbp Variable MANUAL-CONTROL ModelsPilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerCleaning Burner Injector Holder and Pilot AIR Inlet Hole Cleaning and MaintenanceLogs Transporting StoveObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Top Technical Service Specifications Service Hints ReplacementWiring Diagram PartsAccessories Msvfbpr Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListMsvfbp KEY Part Description QTY SUN Valley Stove MC* Series Indicates Color Suffix Designation SUN Valley Stove Mchp Series Hepplewhite Stove Design Hepplewhite Stove Design SUN Valley Stove Mchp SeriesInternational Warranty Information