Quadra-Fire QV36A-FB Vent Information and Diagrams, Vent Table Key, Measuring Standards

Page 13

5 Vent Information and Diagrams

A. Vent Table Key

The abbreviations listed in this vent table key are used in the vent diagrams.

Symbol

Description

V1

First section (closest to appliance) of vertical length

 

 

V2

Second section of vertical length

 

 

H1

First section (closest to appliance) of horizontal length

 

 

H2

Second section of horizontal length

 

 

Vertical

-8 in.1/2

8-1/2 in.

WARNING

Horizontal

Fire Hazard.

 

Explosion Risk.

Figure 5.1

Asphyxiation Risk.

 

Do NOT connect this gas appliance to a chimney

C. Measuring Standards

flue serving a separate solid-fuel or gas burning

appliance.

Vertical and horizontal measurements listed in the vent

• Vent this appliance directly outside.

diagrams were made using the following standards.

• Use separate vent system for this appliance.

1. Pipe measurements are shown using the effective length

May impair safe operation of this appliance or

of pipe (see Figure 5.2).

other appliances connected to the flue.

 

2. Measurements are made from the appliance outer wrap,

B. Use of Elbows

not from the standoffs.

3. Horizontal terminations are measured to the outside

 

CAUTION

mounting surface (flange of termination cap) (see

Figure 4.1).

ALL vent configuration specifications MUST be followed.

4. Vertical terminations are measured to bottom of termi-

nation cap.

• This product is tested and listed to these specifications.

5. Horizontal pipe installed level with no rise.

• Appliance performance will suffer if specifications are not

followed.

 

Diagonal runs have both vertical and horizontal vent as-

 

Pipe

Effective Length

 

Inches

Millimeters

 

 

pects when calculating the effects. Use the rise for the

 

DVP4

4

102

vertical aspect and the run for the horizontal aspect (see

 

DVP6

6

152

Figure 5.1).

Effective

DVP12

12

305

Two 45º elbows may be used in place of one 90º elbow. On

Height/Length

DVP24

24

610

 

 

DVP36

36

914

45º runs, one foot of diagonal is equal to 8-1/2 (216 mm)

 

 

DVP48

48

1219

inches horizontal run and 8-1/2 (216 mm) inches vertical

 

 

DVP6A

3 to 6 76 to 152

run. A length of straight pipe is allowed between two 45º

 

 

 

 

 

elbows (see Figure 5.1).

 

DVP12A

3 to 12

76 to 305

 

 

DVP12MI

3 to 12

76 to 305

 

 

DVP24MI

3 to 24

76 to 610

 

Figure 5.2 DVP Pipe Effective Length

 

 

Quadra-Fire • Expression 36 (QV36A-FB)2062-900 Rev. S • 11/11

 

 

13

Image 13
Contents What to do if you smell gas Model Expression 36 QV36A-FBHot glass will cause burns Homeowner Reference Information CongratulationsTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsGetting Started Design and Installation ConsiderationsTools and Supplies Needed Inspect Appliance and ComponentsInspect Firebox Selecting Appliance Location Framing and ClearancesModel 41-1/2 17-1/4 45-1/4 QV36A-FBClearances Constructing the Appliance ChaseMantel Projections Fire Risk Odor Risk17-1/4 41-1/2 32-1/2 Clearance to Combustibles254 1321 438 1054 825 914 Vent Termination Minimum Clearances Termination LocationsSee .4 for specific clearances Covered Alcove Applications Vent Table Key Vent Information and DiagramsMeasuring Standards Use of ElbowsTop Vent Horizontal Termination One Elbow Two Elbows Vent DiagramsMinimum Maximum 2 ftVT Min HT Max Top Vent Horizontal Termination Three ElbowsMust be installed prior to attaching a 90 elbow Min Max Top Vent Vertical Termination Three ElbowsFeet then the total vent run can be Extended to 40 feetPipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Combustible Wall PenetrationInstalling Attic Shield Installing the Ceiling FirestopVertical Penetration Framing  B. Installing the Optional Heat-ZoneGas Kit Removing Non-combustible Facing Mate- rial AssemblyAppliance Preparation Fire Risk Prevent contact with sagging, loose insulation Securing and Leveling the ApplianceBacker 10 Complete Installation of Non-combustible Installing Non-combustible Facing MaterialAssembly of Vent Sections Installing Vent PipeAttaching Vent to the Firebox Assembly Assembling Pipe SectionsAssembling DVP-12A Slip Sections Assembling Minimum Installations MI SectionsSecuring the Vent Sections Vertical Sections Disassembly of Vent SectionsHorizontal Sections Installing the Horizontal Termination Cap Installing Heat Shield and Horizontal Termination CapHeat Shield Requirements for Horizontal Termination Important Notice Heat shields may not be field constructedRoof Pitch Min. Ft Installing Roof Flashing and Vertical Ter- mination CapFoot minimum in snow regions Sharp Edges Assembling and Installing Storm CollarFuel Conversions Gas Connection Gas InformationGas Pressures Pressure Natural Gas PropaneHigh Altitude Installations Electrical Information Recommendation for WireQWSK-MLT Wall Switch Kit Introduction Optional Accessories RequirementsInstallation precautions To Replace a Light BulbWiring the wall switch Installation instructions Determine locationFor units with factory installed rocker switch Operating InstructionsWall Switch Button Operation Setting Flame Height/manifold pressureTemperature Button SET Set Temperature ButtonJunction Box Detail Junction Box InstallationFacing Material FinishingFacing Requirements FrontsClean the Appliance Appliance SetupAccessories Ember PlacementPositioning the Logs Log Assembly LOGS-2062LOG #2 SRV2062-702 LOG #1 SRV2062-701LOG #3 SRV2062-703 LOG #5 SRV330-704 LOG #4 SRV330-706LOG #6 SRV340-705 Removing Glass Assembly Glass AssemblyReplacing Glass Assembly Burner Removal Only for ServicingGrilles and Trim Air Shutter SettingBefore Lighting Appliance Operating InstructionsFinal inspection by Lighting Appliance IPI IgnitionInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Symptom Possible Cause Corrective Action TroubleshootingIntelliFire Ignition System Noise, but spark may not be present at pilot hoodCracked, damaged, or loose. Verify connection from sensor Maintaining and Servicing Appliance Inspect Maintenance Tasks Maintenance TasksReference Materials Appliance Dimension DiagramLocation Inches Millimeters DVP-AS2 Vent Components DiagramsDVP vent components Horizontal Termination CapRF6M RF12M Log Set Assembly Service PartsAt Depot Direct Vent Gas FireplaceBe ordered from an authorized dealer #17 Valve AssemblyStocked Service Parts ListLimited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Do not Discard this Manual Contact Information

QV36A-FB specifications

The Quadra-Fire QV36A-FB is a remarkable direct vent gas fireplace that combines beauty, efficiency, and innovative technology to create a cozy ambiance in any home. This fireplace is designed for those seeking an aesthetically pleasing yet highly functional heating solution.

One of the standout features of the QV36A-FB is its impressive heating capacity. With the ability to produce up to 34,000 BTUs, it effectively warms spaces of various sizes, making it suitable for both small and large living areas. Its impressive efficiency rating maximizes heat output while minimizing gas consumption, ensuring that homeowners can enjoy warmth without the worry of excessive energy bills.

The QV36A-FB employs a direct venting system, allowing for safe and efficient operation. This system draws air from outside for combustion, which is particularly beneficial for maintaining indoor air quality. The use of direct venting minimizes the loss of heated air, ensuring maximum efficiency and comfort. It also features a versatile installation design that provides flexibility to fit various home layouts.

In terms of aesthetics, the Quadra-Fire QV36A-FB does not disappoint. The fireplace boasts a sleek, contemporary design, available in multiple finishes that easily complement any interior decor. Customers can choose from a variety of logs and ember beds to customize the appearance of the fire, creating a personalized focal point that enhances the ambiance of their living space.

Another significant feature is its advanced ignition system, which ensures reliable and hassle-free starting. The QV36A-FB is equipped with a convenient remote control option that allows users to adjust flame height and heat output with ease, providing exceptional comfort without the need to manually tend to the fire.

This fireplace also incorporates several safety mechanisms, including a flame sensor and a safety shut-off feature, ensuring worry-free operation for families with children or pets. The combination of elegance, efficiency, and state-of-the-art technology makes the Quadra-Fire QV36A-FB a preferred choice for homeowners seeking a premium gas fireplace solution.

In conclusion, the QV36A-FB is more than just a heat source; it is a stylish addition that enhances home aesthetics while delivering reliable warmth. With its impressive features and innovative technologies, it stands out as a dependable choice in the world of gas fireplaces.