Quadra-Fire QV36A-FB owner manual Gas Information, Fuel Conversions Gas Connection, Gas Pressures

Page 29

9 Gas Information

A. Fuel Conversions

C. Gas Connection

Before making gas connections ensure that appliance be- ing installed is compatible with the available gas type.

Any natural or propane gas conversions necessary to meet the appliance and locality needs must be made by a qualified technician using Hearth & Home Technologies specified and approved parts.

Note: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI

223.1.Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

B. Gas Pressures

Proper input pressures are required for optimum appli- ance performance. Gas line sizing requirements need to be made following NFPA54.

WARNING

Fire Risk. Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

WARNING

Verify inlet pressures.

• High pressure may cause overfire condition.

• Low pressure may cause explosion.

Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Note: A listed (and Commonwealth of Massachusetts ap- proved) 1/2 inch (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

Refer to Reference Section 16 for location of gas line access in appliance.

Note: Gas line may be run from either side of the appliance provided the hole in the outer wrap does NOT exceed 2-1/2 inches in diameter and does not penetrate the firebox.

WARNING

Gas Leak Risk

Support control when attaching pipe to prevent bending gas line.

Note: The gap between supply piping and gas access hole may be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with non-combustible, unfaced insulation to prevent cold air infiltration.

Pressure requirements for appliance are shown in the table below. Minimum pressures must be met when other household gas appliances are operating.

Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 inches

11.0 inches

w.c.

w.c.

 

Maximum inlet gas pressure

14.0 inches

14.0 inches

w.c.

w.c.

 

Manifold pressure

3.5 inches

10.0 inches

w.c.

w.c.

 

Quadra-Fire • Expression 36 (QV36A-FB)2062-900 Rev. S • 11/11

29

Image 29
Contents Hot glass will cause burns Model Expression 36 QV36A-FBWhat to do if you smell gas Homeowner Reference Information CongratulationsTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsGetting Started Design and Installation ConsiderationsTools and Supplies Needed Inspect Appliance and ComponentsInspect Firebox Selecting Appliance Location Framing and ClearancesModel 41-1/2 17-1/4 45-1/4 QV36A-FBClearances Constructing the Appliance ChaseMantel Projections Fire Risk Odor Risk254 1321 438 1054 825 914 Clearance to Combustibles17-1/4 41-1/2 32-1/2 See .4 for specific clearances Termination LocationsVent Termination Minimum Clearances Covered Alcove Applications Vent Table Key Vent Information and DiagramsMeasuring Standards Use of ElbowsTop Vent Horizontal Termination One Elbow Two Elbows Vent DiagramsMinimum Maximum 2 ftVT Min HT Max Top Vent Horizontal Termination Three ElbowsMust be installed prior to attaching a 90 elbow Min Max Top Vent Vertical Termination Three ElbowsFeet then the total vent run can be Extended to 40 feetPipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Combustible Wall PenetrationVertical Penetration Framing Installing the Ceiling FirestopInstalling Attic Shield Appliance Preparation Removing Non-combustible Facing Mate- rial Assembly B. Installing the Optional Heat-ZoneGas Kit Backer Securing and Leveling the ApplianceFire Risk Prevent contact with sagging, loose insulation 10 Complete Installation of Non-combustible Installing Non-combustible Facing MaterialAssembly of Vent Sections Installing Vent PipeAttaching Vent to the Firebox Assembly Assembling Pipe SectionsAssembling DVP-12A Slip Sections Assembling Minimum Installations MI SectionsHorizontal Sections Disassembly of Vent SectionsSecuring the Vent Sections Vertical Sections Installing the Horizontal Termination Cap Installing Heat Shield and Horizontal Termination CapHeat Shield Requirements for Horizontal Termination Important Notice Heat shields may not be field constructedFoot minimum in snow regions Installing Roof Flashing and Vertical Ter- mination CapRoof Pitch Min. Ft Sharp Edges Assembling and Installing Storm CollarFuel Conversions Gas Connection Gas InformationGas Pressures Pressure Natural Gas PropaneHigh Altitude Installations Electrical Information Recommendation for WireQWSK-MLT Wall Switch Kit Introduction Optional Accessories RequirementsInstallation precautions To Replace a Light BulbWiring the wall switch Installation instructions Determine locationFor units with factory installed rocker switch Operating InstructionsWall Switch Button Operation Setting Flame Height/manifold pressureTemperature Button SET Set Temperature ButtonJunction Box Detail Junction Box InstallationFacing Material FinishingFacing Requirements FrontsClean the Appliance Appliance SetupAccessories Ember PlacementPositioning the Logs Log Assembly LOGS-2062LOG #3 SRV2062-703 LOG #1 SRV2062-701LOG #2 SRV2062-702 LOG #6 SRV340-705 LOG #4 SRV330-706LOG #5 SRV330-704 Removing Glass Assembly Glass AssemblyReplacing Glass Assembly Burner Removal Only for ServicingGrilles and Trim Air Shutter SettingBefore Lighting Appliance Operating InstructionsFinal inspection by Lighting Appliance IPI IgnitionAfter Appliance is Lit Frequently Asked QuestionsInitial Break-in Procedure Symptom Possible Cause Corrective Action TroubleshootingIntelliFire Ignition System Noise, but spark may not be present at pilot hoodCracked, damaged, or loose. Verify connection from sensor Maintaining and Servicing Appliance Inspect Maintenance Tasks Maintenance TasksLocation Inches Millimeters Appliance Dimension DiagramReference Materials DVP-AS2 Vent Components DiagramsDVP vent components Horizontal Termination CapRF6M RF12M Log Set Assembly Service PartsAt Depot Direct Vent Gas FireplaceBe ordered from an authorized dealer #17 Valve AssemblyStocked Service Parts ListLimited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Do not Discard this Manual Contact Information

QV36A-FB specifications

The Quadra-Fire QV36A-FB is a remarkable direct vent gas fireplace that combines beauty, efficiency, and innovative technology to create a cozy ambiance in any home. This fireplace is designed for those seeking an aesthetically pleasing yet highly functional heating solution.

One of the standout features of the QV36A-FB is its impressive heating capacity. With the ability to produce up to 34,000 BTUs, it effectively warms spaces of various sizes, making it suitable for both small and large living areas. Its impressive efficiency rating maximizes heat output while minimizing gas consumption, ensuring that homeowners can enjoy warmth without the worry of excessive energy bills.

The QV36A-FB employs a direct venting system, allowing for safe and efficient operation. This system draws air from outside for combustion, which is particularly beneficial for maintaining indoor air quality. The use of direct venting minimizes the loss of heated air, ensuring maximum efficiency and comfort. It also features a versatile installation design that provides flexibility to fit various home layouts.

In terms of aesthetics, the Quadra-Fire QV36A-FB does not disappoint. The fireplace boasts a sleek, contemporary design, available in multiple finishes that easily complement any interior decor. Customers can choose from a variety of logs and ember beds to customize the appearance of the fire, creating a personalized focal point that enhances the ambiance of their living space.

Another significant feature is its advanced ignition system, which ensures reliable and hassle-free starting. The QV36A-FB is equipped with a convenient remote control option that allows users to adjust flame height and heat output with ease, providing exceptional comfort without the need to manually tend to the fire.

This fireplace also incorporates several safety mechanisms, including a flame sensor and a safety shut-off feature, ensuring worry-free operation for families with children or pets. The combination of elegance, efficiency, and state-of-the-art technology makes the Quadra-Fire QV36A-FB a preferred choice for homeowners seeking a premium gas fireplace solution.

In conclusion, the QV36A-FB is more than just a heat source; it is a stylish addition that enhances home aesthetics while delivering reliable warmth. With its impressive features and innovative technologies, it stands out as a dependable choice in the world of gas fireplaces.