Vermont Casting RUVS40 manual Vent options to provide additional air

Page 7

3.Add the BTU/Hr ratings of all fuel-burning appli- ances installed in the same space, including the following:

Gas Water Heater

Gas Furnace

Gas Fireplace Logs

Unvented Gas Heater

Vented Gas Heater*

Other Gas Appliances*

*Do not include Direct Vent appliances as these utilize outside air for combustion and vent to the outdoors.

Example:

 

 

Gas Range

55,000

BTU/Hr

Unvented Heater

+33,000

BTU/Hr

Total

88,000

BTU/Hr

4.Compare the maximum BTU/Hr rating the space can support with the total BTU/Hr used by the appliances.

Example:

76,800 BTU/Hr - max. the space can support

88,000 BTU/Hr - total used by appliances

In this example, the maximum BTU/Hr that the space can support is less than the total used by the appliances, the space is considered to be Confined space. Additional air must be provided to meet the requirements of the Unvented heater.

A confined space may be ventilated in two ways:

A)Open up or provide at least two ventilating grilles to an adjoining unconfined space. Use any of the options illustrated in Figure 4.

Vermont Castings Radiance

Each of the two grilles must provide an opening of at least 50 square inches, with all opening dimensions being at least 3". One grille must be located within 12" of the ceiling; the other within 12" of the floor. (If the total exceeds 100,000 BTU/Hr, additional grilles will be required.)

B)Vent the room directly to the outdoors. (Provide one square inch of opening for each 4,000 BTU/hr.

If the total BTU/Hr used by the appliances is less than the maximum BTU/Hr the space is able to sup- port, the room meets the Unconfined space criteria and no further ventilation is required.

For further information on ventilation guidelines and sizing specifications follow the National Fuel Gas Code NFPA 54/ANSI Z223.1 Section 5.3.

WARNING

THIS HEATER SHALL NOT BE INSTALLED IN A CONFINED SPACE UNLESS PROVISIONS ARE PROVIDED FOR ADEQUATE COMBUSTION AND VENTILATION AIR.

IF THE AREA IN WHICH THE HEATER MAY BE OPERATED IS SMALLER THAN THAT DEFINED AS AN UNCONFINED SPACE, PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR BY ONE OF THE METHODS DESCRIBED IN THE NATIONAL FUEL GAS CODE, ANSI Z223.1, 1992, SECTION 5.3.

12”

Option 2 - Remove Door between Adjoining Rooms

Option 1

Vents to

Adjoining

Room

Option 3 -

Vents to Adjoining

Room

12”

ST184

Fig. 4 Vent options to provide additional air.

7

Image 7
Contents Radiance Table of Contents Radiance Unvented Gas Heater RUVS40 SpecificationsFuel Type Carbon Monoxide Poisoning MAY Lead to Death Safety InformationOptional Fan Kit #2767 /FK26 Vent Free FeaturesQuick Installation General InformationUnusually Tight Construction Installation RequirementsFresh Air Requirements for Combustion and Ventilation Provide For Adequate VentilationVent options to provide additional air Alcove Clearances Minimum Clearances to Combustible MaterialsHearth Requirements Freestanding StoveRemove the Front, Screen and Logs AssemblyHardware Bag Contents Unpacking the RadianceAA D Install Optional Fan, #2767/FK26Kit Contents used with the RUVS40 Install the Control Switch. FigResecure the Rear Shroud panels Attach the fan assembly to the fan bracketConnect the Gas Line Thermostat Connection optionalRemove the valve cover plate Install the LogsReplace the front panel Complete the InstallationYour First Fire OperationPilot and Burner Inspection For Your Safety Read Before Lighting Trouble No spark at Pilot when Ignitor is operatedCondition Possible Cause Solution TroubleshootingOdor During Operation Care of Cast Iron Firebox Cleaning and InspectionCleaning Procedure Glass ReplacementReplace the combustor module Clean the combustor moduleCatalytic Combustor Remove the combustor moduleRadiance Vent Free Gas Heater RUVS40 #10-24 X 1/4 Phil. Pn Hd Screw RUVS40Exclusions and Limitations Limited Three Year WarrantyLimited One Year Warranty How To Obtain ServiceVermont Castings Majestic Products Company