7 SERVICE FUNCTIONS

MSZ-D30NA

MSZ-D36NA

MSY-D30NA

MSY-D36NA

7-1. TIMER SHORT MODE

For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.)

Set time : 1-minute 1-second

Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit-of JPG and JPS.)

7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION

A maximum of 4 indoor units with wireless remote controllers can be used in a room.

In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.

How to modify the remote controller P.C. board

Remove batteries before modification.

The board has a print as shown below :

 

NOTE : For modification, take out

 

the batteries and press

 

the OPERATE/STOP (ON/

 

OFF) button twice or 3

 

times at first.

 

After finish modification,

J1 J2

put back the batteries then

press the RESET button.

The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.

Table 1

 

1 unit operation

2 units operation

3 units operation

4 units operation

No. 1 unit

No modification

Same as at left

Same as at left

Same as at left

No. 2 unit

Solder J1

Same as at left

Same as at left

No. 3 unit

Solder J2

Same as at left

No. 4 unit

Solder both J1 and J2

How to set the remote controller exclusively for particular indoor unit

After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit.

The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set.

The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.

10

Image 10
Contents MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Page Technical Changes Accessories Part Names and FunctionsSpecification Operating Range Outlet AIR Speed and Coverage RangeOutlines and Dimensions MSZ-D36NA MSY-D30NA MSY-D36NAWiring Diagram Refrigerant System Diagram UnitinchHow to modify the remote controller P.C. board Service FunctionsTimer Short Mode P.C. Board Modification for Individual OperationAuto Restart Function OperationOperation Indicator lamp Microprocessor ControlFAN Operation MSY Cool OperationHeat Operation MSZ Feel Control Operation MSYMode selection Auto Change Over ··· Auto Mode Operation MSZFuzzy control Auto Vane Operation Vertical vane 3 4 Swing 5Program Timer Changing Temperature Indication F /C Minute Time Delay OperationEMERGENCY/TEST Operation Troubleshooting procedure TroubleshootingBefore troubleshooting, check the following How to replace batteriesFailure Mode Recall Function OFFIndoor unit failure mode table Eration IndicaInstruction of Troubleshooting StartTroubleshooting Check Table Lighted Blinking Not lightedTrouble Criterion of Main Parts Troubleshooting Flow Check of indoor fan motorCheck of remote controller and receiver P.C. board Indoor electronic control P.C. board How to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios Power monitor receiver P.C. board Test Point Diagram and VoltageSW P.C. board Removing the panel Disassembly InstructionsBoard, the power monitor receiver P.C. board and the SW Removing the electrical box, the electronic control P.CRemoving the vertical vane motor Removing the nozzle assemblyRemoving the horizontal vane motor Removing the line flow fan and the indoor fan motor Page Page Distributed in Feb . No. OBH501 New publication, effective FebMade in Japan