•Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.
•OPERATION INDICATOR lamp flashes ON and OFF every
D How to check miswiring and serial signal error
Turn OFF the power supply. |
|
|
| |
|
|
|
|
|
Is there rated voltage AC in |
|
|
| |
|
| Check the power supply. | ||
the power supply? | No |
| ||
|
|
Yes
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and
S2?No
Yes
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Yes
Is serial signal error indicated 6 minutes later?
Yes
Check the wiring.
No
Is there any miswiring, poor contact, or wire disconnec-
No tion of the indoor/outdoor Yes Correct them. connecting wire?
Is fuse (F65) broken? No
A
•Turn OFF
•Turn OFF the power supply and then turn ON again.
•Press EMERGENCY OPERATION switch.
|
| A |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Turn OFF the power supply. |
|
|
|
|
| |
B | Check once more if the indoor/outdoor |
|
|
|
|
| ||
connecting wire is not miswiring. |
| 1. Miswiring may damage indoor electronic control | ||||||
|
|
| P.C. board during the operation. | |||||
|
| and S3. 1 |
| Be sure to confirm the wiring is correct before | ||||
|
|
|
|
| the operation starts. | |||
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Turn ON the power supply. |
|
|
|
|
| |
|
|
|
|
|
|
|
| |
| Does the LED on the inverter P.C. board or |
|
|
|
|
| ||
|
|
|
| Replace the inverter P.C. board or the |
| |||
| the outdoor electronic control P.C. board |
|
|
|
| |||
|
|
|
| outdoor electronic control P.C. board. |
| |||
| repeat |
| No |
|
| |||
|
|
| 2 |
| ||||
| ON quick blinking"? |
| (Lighted |
|
| |||
|
|
|
|
| ||||
|
|
| Yes |
| or not |
| 2. Be careful to the residual | |
|
|
|
| |||||
|
|
|
|
| lighted) |
| voltage of smoothing capacitor. | |
|
|
|
|
|
Turn OFF the power supply. |
|
|
|
|
|
|
| ||
Remove the |
| Is there any error of the in- |
|
|
|
| |||
door terminal block S2 and S3. |
| door/outdoor connecting wire, |
|
|
| Replace the indoor/out- | |||
Turn ON the power supply. |
| such as the damage of the wire, |
|
|
| ||||
No | Yes |
|
| door connecting wire. | |||||
Is there amplitude of 10 to 20 VDC |
| intermediate connection, poor |
|
|
|
| |||
between outdoor terminal block S2 and |
| contact to the terminal block? |
|
|
|
| |||
S3? <Confirmation of serial signal> |
|
| No |
|
|
|
| ||
|
|
|
|
|
| ||||
| Yes |
|
|
|
|
|
|
|
|
|
|
|
| Is there any error of the in- |
|
|
|
| |
Is there rated voltage between |
|
|
|
|
| ||||
| door/outdoor connecting wire, |
|
|
|
|
Is serial signal error indicated 6 minutes later?
Yes
B
No
•Reinstall either the unit or the light each other away.
•Attach a filter on remote control receiv- ing section of the indoor unit.
indoor terminal block S1 and S2? | No | such as the damage of the wire, |
|
| Replace the indoor/out- | |||
Yes |
| door connecting wire. | ||||||
<Confirmation of power voltage> |
| intermediate connection, poor |
|
|
| |||
| Yes |
| contact to the terminal block? |
|
|
| ||
|
|
|
|
| No |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Replace the indoor electronic control P.C. board.
Be sure to release the
28