Vermont Casting MSZ-D36NA, MSZ-D30NA, MSY-D36NA How to check miswiring and serial signal error

Page 28

Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.

OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second. Outdoor unit does not operate.

D How to check miswiring and serial signal error

Turn OFF the power supply.

 

 

 

 

 

 

 

 

Is there rated voltage AC in

 

 

 

 

 

Check the power supply.

the power supply?

No

 

 

 

Yes

Turn ON the power supply.

Is there rated voltage between outdoor terminal block S1 and

S2?No

Yes

Press EMERGENCY OPERATION switch once.

Does the left lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>

Yes

Is serial signal error indicated 6 minutes later?

Yes

Check the wiring.

No

Is there any miswiring, poor contact, or wire disconnec-

No tion of the indoor/outdoor Yes Correct them. connecting wire?

Is fuse (F65) broken? No

A

Turn OFF inverter-controlled lighting equipment.

Turn OFF the power supply and then turn ON again.

Press EMERGENCY OPERATION switch.

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn OFF the power supply.

 

 

 

 

 

B

Check once more if the indoor/outdoor

 

 

 

 

 

connecting wire is not miswiring.

 

1. Miswiring may damage indoor electronic control

 

 

Short-circuit outdoor terminal block S2

 

P.C. board during the operation.

 

 

and S3. 1

 

Be sure to confirm the wiring is correct before

 

 

 

 

 

the operation starts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does the LED on the inverter P.C. board or

 

 

 

 

 

 

 

 

 

Replace the inverter P.C. board or the

 

 

the outdoor electronic control P.C. board

 

 

 

 

 

 

 

 

outdoor electronic control P.C. board.

 

 

repeat "3.6-second-OFF and 0.8-second-

 

No

 

 

 

 

 

2

 

 

ON quick blinking"?

 

(Lighted

 

 

 

 

 

 

 

 

 

 

Yes

 

or not

 

2. Be careful to the residual

 

 

 

 

 

 

 

 

 

lighted)

 

voltage of smoothing capacitor.

 

 

 

 

 

Turn OFF the power supply.

 

 

 

 

 

 

 

Remove the short-circuit between out-

 

Is there any error of the in-

 

 

 

 

door terminal block S2 and S3.

 

door/outdoor connecting wire,

 

 

 

Replace the indoor/out-

Turn ON the power supply.

 

such as the damage of the wire,

 

 

 

No

Yes

 

 

door connecting wire.

Is there amplitude of 10 to 20 VDC

 

intermediate connection, poor

 

 

 

 

between outdoor terminal block S2 and

 

contact to the terminal block?

 

 

 

 

S3? <Confirmation of serial signal>

 

 

No

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

Is there any error of the in-

 

 

 

 

Is there rated voltage between

 

 

 

 

 

 

door/outdoor connecting wire,

 

 

 

 

Is serial signal error indicated 6 minutes later?

Yes

B

No

Reinstall either the unit or the light each other away.

Attach a filter on remote control receiv- ing section of the indoor unit.

indoor terminal block S1 and S2?

No

such as the damage of the wire,

 

 

Replace the indoor/out-

Yes

 

door connecting wire.

<Confirmation of power voltage>

 

intermediate connection, poor

 

 

 

 

Yes

 

contact to the terminal block?

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the indoor electronic control P.C. board.

Be sure to release the failure-mode recall function after checking.

28

Image 28
Contents MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Page Technical Changes Accessories Part Names and FunctionsSpecification Operating Range Outlet AIR Speed and Coverage RangeOutlines and Dimensions MSZ-D36NA MSY-D30NA MSY-D36NAWiring Diagram Refrigerant System Diagram UnitinchService Functions Timer Short ModeHow to modify the remote controller P.C. board P.C. Board Modification for Individual OperationAuto Restart Function OperationOperation Indicator lamp Microprocessor ControlCool Operation Heat Operation MSZFAN Operation MSY Feel Control Operation MSYMode selection Auto Change Over ··· Auto Mode Operation MSZFuzzy control Auto Vane Operation Vertical vane 3 4 Swing 5Program Timer Changing Temperature Indication F /C Minute Time Delay OperationEMERGENCY/TEST Operation Troubleshooting Before troubleshooting, check the followingTroubleshooting procedure How to replace batteriesFailure Mode Recall Function OFFIndoor unit failure mode table Eration IndicaInstruction of Troubleshooting StartTroubleshooting Check Table Lighted Blinking Not lightedTrouble Criterion of Main Parts Troubleshooting Flow Check of indoor fan motorCheck of remote controller and receiver P.C. board Indoor electronic control P.C. board How to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios Power monitor receiver P.C. board Test Point Diagram and VoltageSW P.C. board Disassembly Instructions Board, the power monitor receiver P.C. board and the SWRemoving the panel Removing the electrical box, the electronic control P.CRemoving the vertical vane motor Removing the nozzle assemblyRemoving the horizontal vane motor Removing the line flow fan and the indoor fan motor Page Page Distributed in Feb . No. OBH501 New publication, effective FebMade in Japan