9-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
OPERATION INDICATOR
Lighted
Blinking
Not lighted
No. | Abnormal | Operation indicator lamp | Symptom | Condition | Correspondence | |
point | ||||||
|
|
|
|
| ||
|
| Left lamp flashes. | Indoor unit |
|
| |
|
|
|
| |||
1 | Miswiring or | and outdoor | The serial signal from the outdoor unit is not | • Refer to | ||
| ||||||
| serial signal |
| unit do not | received for a maximum of 6 minutes. | and serial signal error". | |
|
| operate. |
|
| ||
|
|
|
|
| ||
|
| Left lamp flashes. |
|
|
| |
| Indoor coil |
|
|
| ||
| thermistor | Indoor unit |
| • Refer to | ||
|
|
| and outdoor | The indoor coil or the room temperature | ||
2 |
|
| coil thermistor, and the room tempera- | |||
|
| unit do not | thermistor is short or open circuit. | |||
|
| ture thermistor. | ||||
| Room | operate. |
| |||
|
|
|
| |||
| temperature |
|
|
|
| |
| thermistor |
|
|
|
| |
|
| Left lamp flashes. | Indoor unit |
|
| |
| Indoor fan | The rotational frequency feedback signal is not • Refer to | ||||
3 | and outdoor | |||||
motor |
| unit do not | emitted during the indoor fan operation. | tor". | ||
|
| operate. |
|
| ||
|
|
|
|
| ||
|
| Left lamp flashes. | Indoor unit |
|
| |
| Indoor con- | It cannot properly read data in the nonvolatile | • Replace the indoor electronic control | |||
4 |
| and outdoor | ||||
trol system |
| unit do not | memory of the indoor electronic control P.C. | P.C. board. | ||
|
| operate. | board. |
| ||
|
|
|
| |||
|
|
|
|
| ||
|
| Left lamp flashes. |
|
|
| |
| Outdoor | Indoor unit | It consecutively occurs 3 times that the | • Refer to "How to check of inverter/ | ||
|
| and outdoor | compressor stops for overcurrent protection or | compressor". | ||
5 | power sys- |
| ||||
| unit do not | Refer to outdoor unit service manual. | ||||
| tem |
| ||||
|
| operate. | • Check the stop valve. | |||
|
| |||||
|
|
|
|
| ||
|
| Left lamp flashes. | Indoor unit |
|
| |
| Outdoor | The outdoor thermistors short or open circuit | • Refer to "Check of outdoor thermistor". | |||
6 |
| and outdoor | ||||
thermistors |
| unit do not | during the compressor operation. | Refer to outdoor unit service manual. | ||
|
| operate. |
|
| ||
|
|
|
|
| ||
|
| Left lamp flashes. | Indoor unit |
|
| |
7 | Outdoor con- | It cannot properly read data in the nonvola- | • Replace the inverter P.C. board or the | |||
| and outdoor | tile memory of the inverter P.C. board or the | outdoor electronic control P.C. board. | |||
| trol system |
| unit do not | outdoor electronic control P.C. board. | Refer to outdoor unit service manual. | |
|
|
| operate. | |||
|
|
|
| |||
|
|
|
|
| ||
|
| Left lamp flashes. |
|
|
| |
|
| Indoor unit |
| • Confirm the abnormality in detail using | ||
| Other abnor- |
| An abnormality other than above mentioned is | |||
8 |
| and outdoor | ||||
mality |
| unit do not | detected. | the failure mode recall function for | ||
|
| operate. |
| outdoor unit. | ||
|
|
|
| |||
|
|
|
|
|
23