Vermont Casting MSY-D30NA, MSZ-D36NA, MSZ-D30NA, MSY-D36NA Auto Restart Function, Operation

Page 11

7-3. AUTO RESTART FUNCTION

When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically.

Operation

If the main power has been cut, the operation settings remain.

After the power is restored, the unit restarts automatically according to the memory. (However, it takes at least 3 minutes for the compressor to start running.)

How to release “AUTO RESTART FUNCTION”

Turn off the main power of the unit.

Solder the Jumper wire JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)

CN211

JR07

BZ

 

 

CN152

 

CN112

 

CN101

 

 

 

 

CN151

 

 

 

 

 

NOTE:

The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller.

If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is cancelled.

If the unit has been off with the remote controller before power failure, the auto restart function does not work as the power button of the remote controller is off.

To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the same time.

When some air conditioners are connected to the same supply system, if they are operated before power failure, the starting current of all the compressors may flow simultaneously at restart.

Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.

11

Image 11
Contents MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Page Technical Changes Part Names and Functions AccessoriesSpecification Outlet AIR Speed and Coverage Range Operating RangeMSZ-D36NA MSY-D30NA MSY-D36NA Outlines and DimensionsWiring Diagram Unitinch Refrigerant System DiagramP.C. Board Modification for Individual Operation Service FunctionsTimer Short Mode How to modify the remote controller P.C. boardOperation Auto Restart FunctionMicroprocessor Control Operation Indicator lampFeel Control Operation MSY Cool OperationHeat Operation MSZ FAN Operation MSYFuzzy control Auto Change Over ··· Auto Mode Operation MSZMode selection Auto Vane Operation 3 4 Swing 5 Vertical vaneProgram Timer EMERGENCY/TEST Operation Minute Time Delay OperationChanging Temperature Indication F /C How to replace batteries TroubleshootingBefore troubleshooting, check the following Troubleshooting procedureOFF Failure Mode Recall FunctionEration Indica Indoor unit failure mode tableStart Instruction of TroubleshootingLighted Blinking Not lighted Troubleshooting Check TableTrouble Criterion of Main Parts Check of indoor fan motor Troubleshooting FlowCheck of remote controller and receiver P.C. board Indoor electronic control P.C. board How to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios SW P.C. board Test Point Diagram and VoltagePower monitor receiver P.C. board Removing the electrical box, the electronic control P.C Disassembly InstructionsBoard, the power monitor receiver P.C. board and the SW Removing the panelRemoving the horizontal vane motor Removing the nozzle assemblyRemoving the vertical vane motor Removing the line flow fan and the indoor fan motor Page Page Made in Japan New publication, effective FebDistributed in Feb . No. OBH501