3-1.  OPERATING RANGE
(1) POWER SUPPLY
| 
 | Rated voltage | 
 | Guaranteed Voltage | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 208/230 V | Min.187 V 208 V 230 V Max.253 V | ||||
| Indoor unit | 1 phase | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 60 Hz | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
(2) OPERATION
| Mode | Condition | 
 | 
 | Intake air temperature (°F) | 
 | 
 | |
| Indoor | 
 | 
 | Outdoor | ||||
| 
 | 
 | DB | 
 | WB | DB | 
 | WB | 
| 
 | Standard temperature | 80 | 
 | 67 | 95 | 
 | — | 
| Cooling | Maximum temperature | 90 | 
 | 73 | 115 | 
 | — | 
| Minimum temperature | 67 | 
 | 57 | 14 | 
 | — | |
| 
 | 
 | 
 | |||||
| 
 | Maximum humidity | 78 | % | 
 | 
 | — | |
| Heating | Standard temperature | 70 | 
 | 60 | 47 | 
 | 43 | 
| Maximum temperature | 80 | 
 | 67 | 75 | 
 | 65 | |
| 
 | Minimum temperature | 70 | 
 | 60 | 14 | 
 | 13 | 
3-2.  OUTLET AIR SPEED AND COVERAGE RANGE
| Model | Mode | Function | Airlow | Air speed | Coverage | |
| (CFM) | (ft./sec.) | range (ft.) | ||||
| 
 | 
 | 
 | ||||
| HEAT | Dry | 848 | 23.6 | 45.0 | ||
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | Dry | 848 | 23.6 | 45.0 | ||
| COOL | 
 | 
 | 
 | 
 | ||
| Wet | 763 | 21.3 | 40.7 | |||
| 
 | ||||||
| 
 | 
 | |||||
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out horizon- tally from the unit properly at the High speed position.
 The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out horizon- tally from the unit properly at the High speed position.
The coverage range should be used only as a general guideline since it var- ies according to the size of the room and furniture arranged inside the room.
6