An unprotected mantel (“A”, Fig. 15) cannot be more than 9” (230 mm) deep and must have a minimum clearance of 41” (1041 mm), measured from the stove’s top plate. With a ventilated shield, this clearance may be reduced safely to 29” (737 mm).
Unprotected top trim (B) protruding 3/4” (19 mm) or less from the face of the fireplace must be a minimum of 28” (711 mm) from the stove’s top surface. With a ventilated trim shield, this clearance may be reduced safely to 21” (533 mm).
Unprotected side trim (C) that protrudes 3/4” (19 mm) or less from the face of a fireplace must have a minimum clearance of 14” (356 mm), measured from the stove’s top side edge. If the trim extends more than 3/4” (19 mm), it is subject to the requirements for wall clearance.
The charts and sample installations that follow list all the clearances required for the various installation configurations of the Defiant.
Defiant 1610
Side Wall
A B
C C
D
ST253b
Fireplace and Mantel Trim Clearances
| Unprotected | Protected |
A. Mantel | 41” (1041 mm) | 29” (737 mm) |
B. Top Trim | 28” (711 mm) | 21” (533 mm) |
C. Side Trim | 14” (356 mm) | 14” (356 mm) |
D. Side Wall | 26” (660 mm) | 14” (356 mm) |
Fig. 15 Maintain clearances to combustible components of the mantelpiece.