Vermont Casting 1610 installation instructions Fireplace and Mantel Trim Clearances

Page 13

An unprotected mantel (“A”, Fig. 15) cannot be more than 9” (230 mm) deep and must have a minimum clearance of 41” (1041 mm), measured from the stove’s top plate. With a ventilated shield, this clearance may be reduced safely to 29” (737 mm).

Unprotected top trim (B) protruding 3/4” (19 mm) or less from the face of the fireplace must be a minimum of 28” (711 mm) from the stove’s top surface. With a ventilated trim shield, this clearance may be reduced safely to 21” (533 mm).

Unprotected side trim (C) that protrudes 3/4” (19 mm) or less from the face of a fireplace must have a minimum clearance of 14” (356 mm), measured from the stove’s top side edge. If the trim extends more than 3/4” (19 mm), it is subject to the requirements for wall clearance.

The charts and sample installations that follow list all the clearances required for the various installation configurations of the Defiant.

Defiant 1610 Non-Catalytic Woodburning Stove

Side Wall

A B

C C

D

ST253b

Fireplace and Mantel Trim Clearances

 

Unprotected

Protected

A. Mantel

41” (1041 mm)

29” (737 mm)

B. Top Trim

28” (711 mm)

21” (533 mm)

C. Side Trim

14” (356 mm)

14” (356 mm)

D. Side Wall

26” (660 mm)

14” (356 mm)

Fig. 15 Maintain clearances to combustible components of the mantelpiece.

30002850

13

Image 13
Contents Defiant Save These Instructions for Future Reference WelcomeInstallation Accessories Table of ContentsStory of the Defiant Defiant, Model SpecificationsOutside Air InstallationChimney Height Masonry Chimneys What Kind of Chimney to UsePrefabricated Chimneys Chimney SizeSingle-wall Chimney Connectors Chimney Connector GuidelinesSecuring the Single-wall Connector to a Masonry Chimney Freestanding InstallationsAbove the Fireplace Fireplace InstallationsWall Pass-Throughs Through the FireplaceAn approved wall pass-through for Canada Floor ProtectionKeep the Stove a Safe Distance From Surrounding Materials Floor Protection for Fireplace InstallationWall Shields Safe Ways to Reduce ClearancesFireplace and Mantel Trim Shields Fireplace and Mantel Trim Clearances Stove Clearance Unprotected Surfaces Protected Surfaces1 Defiant NC Clearance Chart for 6 Connections onlyStove Clearance1 Unprotected Surfaces Protected Surfaces Defiant NC Clearance Chart for 8 Connections onlyUnprotected Surfaces Protected Surfaces Defiant NC Clearance DiagramsRefer to Important 1220 mm Note on This Defiant With Flue Collar Heat Shield Only Installations34³⁄₈ Set Up Your Stove AssemblyInstall Stove Legs Install the Bottom Heat ShieldAdjust the Leg Levellers Install the Optional Ash Door Heat ShieldReverse the Flue Collar If necessary Attach the Damper HandleOperation Fan Kit InstallationDefiant Controls Single Air Control Regulates Heat Output and Burn TimeTwo Ways to Add Fuel Damper Directs Air Flow Within the StoveInfra-Red Reflective Glass Panels For Clear Fire Viewing Use the Air Control Settings that Work Best for YouAndirons Help Protect the Glass Burn Only High-Quality WoodConditioning Your Stove Defiant Control SettingsStarting and Maintaining a Wood Fire Add larger pieces of wood as the fire begins to burn Refuel While the Embers Are Still HotAsh Disposal Steel Chimney Draft ManagementIndoor/Outdoor Location Flue SizingSingle Venting Draft TestingCreosote FuelConclusion Maintenance How to Adjust the Door Latches Adjust the Damper as NeededTighten the Damper Handle as Needed Replace the Stove Gaskets as NeededAll Gasketed Construction Gaskets Chimney SystemChimney Connector Maintenance Schedule StoveDefiant Woodburning Stove Defiant Woodburning Stove Model Shell Enamel Parts Defiant Model Defiant 1610 Non-Catalytic Woodburning Stove Limited Lifetime Warranty CFM Corporation