|
|
|
| C |
D |
|
|
|
|
|
| B |
|
|
E |
| E | E | E |
| F |
|
| F |
| A |
|
| A |
| U.S. |
| Canada |
|
A. | 44” | 48” | (1219 mm) |
|
B. | 46” | 50” | (1270 mm) |
|
C. | 12” | 12” | (305 mm) | 8” Connector |
| 10” | 10” | (250 mm) | 6” Connector |
D. | 6” | 8” | (203 mm) |
|
E. | 6” | 8” | (203 mm) |
|
F. | 16” | 18” | (460 mm) | ST500 |
Fig. 12 Required floor protection dimensions.
Procedure:
1.Convert specifications to
i.
ii.
iii.
inches: R = | 1 |
| x T | |
K x 12 | ||||
|
|
iv.
2. Determine the
i. Use the formula in Step 1 to convert values not expressed as R.
ii. For multiple layers, add
3. If the overall
EXAMPLE: The specified floor protector should be 1/2- inch thick material with
Step a: Use formula above to convert specification to
4” brick of r = 0.2, therefore: Rbrick = 0.2 x 4 = 0.8
1/8” mineral board of k = 0.29, therefore 1
Rmineralboard = 0.29 x 0.125 = 0.431
Rtotal = Rbrick + Rmineralboard = 0.8 + 0.431 = 1.231
Defiant 1610
Step c: Compare proposed system Rtotal of 1.231 to specified R of 0.59. Since proposed system Rtotal is greater than required, the system is acceptable.
Definitions |
|
|
|
|
|
|
|
|
|
R = | (ft2)(hr)(°F) | k = | (Btu)(in) |
| = K x 12 | ||||
|
|
|
|
| |||||
| Btu | (ft2)(hr)(°F) | |||||||
|
|
|
|
|
| ||||
K = |
| (Btu)(ft) |
| r = | (ft2)(hr)(°F) | = | 1 |
| |
| (ft2)(hr)(°F) |
|
| (Btu)(in) |
|
| k |
Floor Protection for Fireplace Installation
Do not assume that your fireplace hearth is completely noncombustible. Many fireplace hearths do not satisfy the “completely noncombustible” requirement because the brick or concrete in front of the fireplace opening is supported by heavy wood framing. Because heat passes readily through brick or concrete, it can easily pass through to the wood. As a result, such fireplace hearths can be a fire hazard and are considered a com- bustible floor.
For all fireplace installations, follow the floor protec- tion guidelines described above, including the need for bottom and ash door heat shields. Keep in mind that many raised hearths will extend less than the required clearance from the front of the heater. In such cases, sufficient floor protection as described above must be added in front of the hearth to satisfy the minimum floor protector requirement from the front of the stove: 16” (410 mm) in the United States and 18” (460 mm) in Canada. Hearth rugs do not satisfy the requirement for floor protection as they are not fire proof.
Fireplace installations also have special clearance requirements to the side walls, side decorative trim and fireplace mantel. Refer to the information on fireplace and mantel trim shields in this section.
Keep the Stove a Safe Distance
From Surrounding Materials
Both a stove and its chimney connector radiate heat in all directions when operating, and nearby combustible materials can overheat dangerously if they are too close to the heat source. A safe installation requires that ad- equate clearance be maintained between the hot stove and its connector and nearby combustibles.
Clearance is the distance between either your stove or chimney connector, and nearby walls, floors, the ceiling, and any other fixed combustible surface. The Defiant has specific clearance requirements that have been established after careful research and testing. These clearance requirements must be strictly observed.
In addition, keep furnishings and other combustible materials away from the stove. In general, a distance of 48” (1219 mm) must be maintained between the stove and moveable combustible items such as drying
30002850 | 11 |