Vermont Casting 1610 installation instructions Safe Ways to Reduce Clearances, Wall Shields

Page 12

Defiant 1610 Non-Catalytic Woodburning Stove

clothes, furniture, newspapers, firewood, etc. Keep- ing those clearance areas empty assures that nearby surfaces and objects will not overheat.

Safe Ways to Reduce Clearances

Clearance requirements are established to meet every installation possibility, and they involve the combination of these variables:

When the stove pipe has no listed heat shield mounted on it.

When the wall has no heat shield mounted on it.

When the wall has a heat shield mounted on it.

When the wall and stove pipe have heat shields. In general, the greatest clearance is required when you place a stove and its connector near a wall with no heat shield.

For example, when the Defiant is installed parallel to the rear wall with 8” pipe and no connector shield is used, it must be at least 35” (889 mm) from the wall behind it and at least 23” (584 mm) from walls on either side. These dimensions are measured from the top edge of the stove to the combustible wall.

If the Defiant is installed in a corner and no shield is used, the corners of the stove top must be at least 25” (635 mm) from nearby walls when using 8” connector pipe.

Clearances may be reduced only by means approved by the regulatory authority, and in accordance with the clearances listed in this manual. Refer to Pages 10 - 13 for approved clearance reduction specifications.

NOTE: Clearance requirements differ for 8” and 6” con- nector pipe installation. A minimum ceiling height of 8 feet (2.4 m) is required for all installations of the Defiant NC.

NOTE: Installation of the Defiant is not permitted in alcoves.

Wall Shields

One way to reduce clearances is with a wall shield constructed of 24 gauge or heavier sheet metal, or of another noncombustible material such as 1/2” (13 mm) insulation board such as Durock® or Wonderboard®, or common brick “laid on flat,” with the 3¹⁄₂" (90 mm) side down.

Shields must be spaced out from the combustible surface 1" (25 mm) on noncombustible spacers, as in Figure 13. The spacers should not be directly behind the stove or chimney connector.

Air must be able to flow between the wall and the shield. At least 50% of the bottom 1" (25 mm) of the shield must be open, and the shield must be open at the top. Metal screening across the top will keep small stray objects from being trapped behind the shield. (Fig. 13)

With 6” connections and chimneys, the shield must be a minimum of 48" (1219 mm) tall, and must extend at least 19" (483 mm) higher than the top of the stove, whichever is higher. The shield behind the chimney connector must be 30" (760 mm) wide, centered behind the pipe; for installations that use an approved prefab- ricated chimney to pass through the ceiling, the shield behind the chimney connector must stop 1" (25 mm) below the ceiling.

With 8” connections and chimneys, because of poten- tially higher pipe temperatures, the shield must extend the full height of the wall (up to 9’ (2.7 m)) and stop 1” (25 mm) below the ceiling.

Air Flow

 

Screen

 

Wall Shield

 

Stud Wall

 

Framing

 

Noncombus-

 

tible Spacers

Shield

and Fasteners

 

 

Metal Spacer

Drywall

 

Air Flow

 

 

ST248

Fig. 13 Approved wall shield construction.

Fireplace and Mantel Trim Shields

A fireplace installation requires special clearance between the side of the stove and the right and left walls, between the side of the stove and the decorative side trim on the fireplace face, and between the top of the stove and the mantel.

Noncombustible shields

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installed 1” (25 mm) away

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from the combustible surface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on noncombustible spacers,

 

 

 

 

 

 

 

 

 

 

 

 

 

1" (25mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

called ventilated shields,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

may be used to reduce

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

clearances.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To protect a mantel from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat of a stove in a fireplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installation, use a custom-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

made ventilated mantel

ST501

 

 

 

 

 

1/4" (6mm)

shield that is at least 48”

 

 

 

 

 

 

 

 

 

 

 

 

(1220 mm) long, centered

Fig. 14 A custom-formed

over the stove. (Fig. 14)

mantel shield.

Ventilated shields for side

trim must extend the full length of the trim.

12

30002850

Image 12
Contents Defiant Welcome Save These Instructions for Future ReferenceTable of Contents Installation AccessoriesStory of the Defiant Specifications Defiant, ModelInstallation Outside AirChimney Height What Kind of Chimney to Use Masonry ChimneysPrefabricated Chimneys Chimney SizeChimney Connector Guidelines Single-wall Chimney ConnectorsSecuring the Single-wall Connector to a Masonry Chimney Freestanding InstallationsFireplace Installations Above the FireplaceThrough the Fireplace Wall Pass-ThroughsFloor Protection An approved wall pass-through for CanadaFloor Protection for Fireplace Installation Keep the Stove a Safe Distance From Surrounding MaterialsSafe Ways to Reduce Clearances Wall ShieldsFireplace and Mantel Trim Shields Fireplace and Mantel Trim Clearances Defiant NC Clearance Chart for 6 Connections only Stove Clearance Unprotected Surfaces Protected Surfaces1Defiant NC Clearance Chart for 8 Connections only Stove Clearance1 Unprotected Surfaces Protected SurfacesDefiant NC Clearance Diagrams Unprotected Surfaces Protected SurfacesRefer to Important 1220 mm Note on This Installations Defiant With Flue Collar Heat Shield Only34³⁄₈ Assembly Set Up Your StoveInstall Stove Legs Install the Bottom Heat ShieldInstall the Optional Ash Door Heat Shield Adjust the Leg LevellersReverse the Flue Collar If necessary Attach the Damper HandleFan Kit Installation OperationDefiant Controls Single Air Control Regulates Heat Output and Burn TimeDamper Directs Air Flow Within the Stove Two Ways to Add FuelUse the Air Control Settings that Work Best for You Infra-Red Reflective Glass Panels For Clear Fire ViewingAndirons Help Protect the Glass Burn Only High-Quality WoodDefiant Control Settings Conditioning Your StoveStarting and Maintaining a Wood Fire Refuel While the Embers Are Still Hot Add larger pieces of wood as the fire begins to burnAsh Disposal Draft Management Steel ChimneyIndoor/Outdoor Location Flue SizingDraft Testing Single VentingCreosote FuelConclusion Maintenance Adjust the Damper as Needed How to Adjust the Door LatchesTighten the Damper Handle as Needed Replace the Stove Gaskets as NeededChimney System All Gasketed Construction GasketsMaintenance Schedule Stove Chimney ConnectorDefiant Woodburning Stove Defiant Woodburning Stove Model Shell Enamel Parts Defiant Model Defiant 1610 Non-Catalytic Woodburning Stove Limited Lifetime Warranty CFM Corporation