Vanguard Heating VMH10TN AIR for, Determining FRESH-AIR Flow for Fireplace Location

Page 7

AIR FOR

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

COMBUSTION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

AND

Space: Includes the room in which you will install fireplace plus any adjoining rooms

VENTILATION

with doorless passageways or ventilation grills between the rooms.

 

Continued

1. Determine the volume of the space (length x width x height).

 

 

 

 

 

 

 

 

 

 

Length x Width x Height =

___________________

cu. ft. (volume of space)

 

Example:

Space size 16 ft. (length) x 14 ft. (width) x 8 ft. (ceiling height) =

 

 

1792 cu. ft. (volume of space)

 

 

 

If additional ventilation to adjoining room is supplied with grills or openings, add the

 

volume of these rooms to the total volume of the space.

 

 

 

2. Multiply the space volume by 1000 Btu/Hr per 50 cubic feet to determine the maximum

 

Btu/Hr the space can support.

 

 

 

 

 

 

 

 

______________ (volume of space) x 1000 Btu/Hr = (Maximum Btu/Hr the space can support)

 

 

 

 

 

 

 

 

 

 

 

 

 

50 Cubic Feet

 

 

 

Example: 1792 Cubic Feet (volume of space) x 1000 Btu/Hr = 35,840 Btu/Hr

 

 

 

 

 

 

 

50 Cubic Feet

 

This is the maximum Btu/Hr the space can support.

 

 

 

3. Add the Btu/Hr of all fuel burning appliances in the space.

 

 

 

 

Vent-free fireplace

 

 

___________________ Btu/Hr

 

 

Gas water heater*

 

 

 

___________________ Btu/Hr

 

 

Gas furnace

 

 

 

___________________ Btu/Hr

 

 

Vented gas heater

 

 

 

___________________ Btu/Hr

 

 

Gas fireplace logs

 

 

 

___________________ Btu/Hr

 

 

Other gas appliances*

 

+ ___________________ Btu/Hr

 

 

Total

 

 

= ___________________ Btu/Hr

 

Example:

Gas water heater

 

 

 

30,000

 

Btu/Hr

 

 

Vent-free fireplace

+

10,000

 

Btu/Hr

 

 

 

 

=

 

 

 

 

 

 

Total

 

40,000

 

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 35,840

Btu/Hr (maximum the space can support)

40,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 9.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

Continued 7

103670

Image 7
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSafety Information ContentsSafety Product FeaturesProduct Identification Local CodesInstalling Log AssemblyAssembling Fireplace Ventilation AIR for CombustionProviding Adequate Ventilation Determining FRESH-AIR Flow for Fireplace Location AIR forDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRTion and ventilation air by one of the methods described Cable local codesVentilation Air From Outdoors AIR for Combustion and VentilationLocating Fireplace InstallationInstallation Items Check GAS TypeInstallation BUILT-IN Fireplace Installation InstallingGas Supply, Mantel Clearances for Built-In InstallationAttaching Brass Trim to Fireplace Optional Mantel InstallationAttaching Wood Base to Solid Floor Assembling Brass Trim Brass trim shipped with mantelFollow all local codes ConnectingTo GAS SupplyInstallation Items Needed Connecting Fireplace to GAS SupplyConnections Pressure Testing GAS Supply Piping SystemPressure Testing Fireplace GAS Connections Checking GASFireplace Pilot Operating FireplaceShutting Off Burner Only pilot stays lit Shutting Off FireplacePilot Flame Pattern Inspecting BurnerCorrect Burner Flame Pattern Burner Flame PatternCabinet Cleaning and Maintenance Trouble ShootingObserved Possible Problem Cause Remedy ODS/PILOT and BurnerSee Cleaning TROUBLE- Shooting Top Ing statement atHints ServiceReplacement TechnicalAccessories VMH10TN Model VMH10TN Parts ListLimited Warranty Warranty InformationVENT-FREE Natural GAS Compact Classic HEARTHâ Fireplace