Vanguard Heating VMH10TN Ventilation AIR, Cable local codes, Ventilation Air From Inside Building

Page 8

AIR FOR

WARNING ICONG 001WARNING

COMBUSTION

 

If the area in which the heater may be operated is smaller than

AND

that defined as an unconfined space, provide adequate combus-

tion and ventilation air by one of the methods described in the

VENTILATION

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or appli-

Continued

cable local codes.

VENTILATION AIR

 

 

Ventilation Air From Inside Building

 

This fresh air would come from an adjoining unconfined space. When ventilating to

 

an adjoining unconfined space, you must provide two permanent openings: one within

 

12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces

 

(see options 1 and 2, Figure 4). You can also remove door into adjoining room (see

 

option 3, Figure 4). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1,

 

Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills

 

or ducts.

 

 

 

WARNING ICONG 001WARNING

 

Rework worksheet, adding the space of the adjoining unconfined

 

space. The combined spaces must have enough fresh air to supply all

 

appliances in both spaces.

 

 

12"

 

Ventilation Grills

Ventilation

Into Adjoining Room,

Option 2

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Figure 4 - Ventilation Air from Inside Building Shown with Optional Mantel

8

103670

Image 8
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety InformationSafety Features Product IdentificationLocal Codes ProductAssembling Fireplace AssemblyInstalling Log Providing Adequate Ventilation AIR for CombustionVentilation Determining if You Have a Confined or Unconfined Space AIR forDetermining FRESH-AIR Flow for Fireplace Location Ventilation AIR Tion and ventilation air by one of the methods describedCable local codes Ventilation Air From Inside BuildingAIR for Combustion and Ventilation Ventilation Air From OutdoorsInstallation Installation ItemsCheck GAS Type Locating FireplaceInstallation Installing BUILT-IN Fireplace InstallationMantel Clearances for Built-In Installation Gas Supply,Optional Mantel Installation Attaching Brass Trim to FireplaceAssembling Brass Trim Brass trim shipped with mantel Attaching Wood Base to Solid FloorConnecting To GASSupply Follow all local codesConnecting Fireplace to GAS Supply Installation Items NeededPressure Testing GAS Supply Piping System Pressure Testing Fireplace GAS ConnectionsChecking GAS ConnectionsFireplace Operating Fireplace PilotShutting Off Fireplace Shutting Off Burner Only pilot stays litInspecting Burner Pilot Flame PatternBurner Flame Pattern Correct Burner Flame PatternCleaning and Maintenance Trouble Shooting Observed Possible Problem Cause RemedyODS/PILOT and Burner CabinetSee Cleaning TROUBLE- Shooting Ing statement at TopService ReplacementTechnical HintsAccessories VMH10TN Parts List Model VMH10TNVENT-FREE Natural GAS Compact Classic HEARTHâ Fireplace Warranty InformationLimited Warranty