Vanguard Heating VMH26TPB installation manual Determining FRESH-AIR Flow for Fireplace Location

Page 7

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr

the space can support)

 

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. =

51.2 or 51,200 (maximum

Btu/Hr the space can support)

 

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

Gas water heater*

 

___________________ Btu/Hr

Gas furnace

 

___________________ Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

Total

= ___________________ Btu/Hr

Example: Gas water heater

 

30,000

Btu/Hr

Vent-free fireplace

+

26,000

Btu/Hr

Total

=

 

Btu/Hr

56,000

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200

Btu/Hr (maximum the space can support)

56,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 9.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

Continued 7

102886

Image 7
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualContents Safety Information Safety Information Thermostatic Heat Control Local Codes Product Features UnpackingSafety Pilot Piezo Ignition SystemInstalling Log AssemblyConfined and Unconfined Space AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Fireplace LocationVentilation Air From Inside Building Ventilation AIRVentilation Air from Outdoors Shown with Optional Mantel Ventilation Air From OutdoorsLocating Fireplace InstallationInstallation Items Check GAS TypeCeiling BUILT-IN Fireplace Installation InstallingSide Firebox Mantel Shelf Mantel Clearances for Built-In InstallationAttaching Brass Trim to Fireplace Optional Mantel InstallationAttaching Wood Base to Solid Floor Assembling Brass Trim Brass trim shipped with mantelExternal Regulator with Vent Pointing Down Connecting to GAS SupplyInstallation Items Needed Connecting Fireplace to GAS SupplyPressure Testing GAS Supply Piping System Connecting to GAS Supply Checking GAS ConnectionsManual Shutoff Valve Pressure Testing Fireplace GAS ConnectionsOperating Fireplace Pilot Shutting Off Burner Only pilot stays lit Shutting Off FireplacePilot Flame Pattern Inspecting BurnerCorrect Burner Flame Pattern Burner Flame PatternODS/PILOT and Burner Cleaning and Maintenance Trouble ShootingCabinet TROUBLE- Shooting See CleaningObserved Possible Remedy Problem Cause Connections, Ing statement at topParts Not Under Warranty Technical ServiceService Hints Parts Under WarrantyVMH26TP Model VMH26TP Parts ListUnfinished GM921U Finished GM920F AccessoriesValve GA5010 GA3400T102886 102886 102886 Keep this Warranty Warranty Information