Vanguard Heating VN18TA, VP26TA VN30A Check GAS Type, Installation Items, Locating Heater

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent open- ings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-con- trolled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

INSTALLATION

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri- mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

WARNING: A qualified ser- vice person must install heater. Follow all local codes.

CHECK GAS TYPE

Use only the correct type of gas (natural or pro- pane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.

INSTALLATION ITEMS

Before installing heater, make sure you have the items listed below.

for propane/LP gas, external regulator (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

ground joint union

sediment trap

tee joint

pipe wrench

for natural gas, test gauge connection*

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. The optional CSA design- certified equipment shutoff valve can be purchased from your dealer. See Accessories, page 33.

LOCATING HEATER

WARNING: Maintain the mini- mum clearances shown in Figure 4. Ifyoucan,providegreaterclearances from floor, ceiling, and joining wall.

You can locate heater on the floor, away from a wall. A wall mounting bracket and floor base stand are included with this heater. Determine which method is best for your application.

CEILING

36"

10"Minimum Minimum

From Sides Of Heater

Left

Right

Side

Side

2" Minimum To

Top Surface

FLOOROf Carpeting,

Tile Or Other

Combustible

Material

Figure 4 - Mounting Clearances As

Viewed From Front of Heater

113052-01A

www.desatech.com

7

Image 7
Contents Model VN30A Shown VN30A, VN30TA, VP16ITA, VP22ITATable of Contents Safety Information Unpacking Product FeaturesLocal Codes Product IdentificationProviding Adequate Ventilation AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Building Ventilation AIRLocating Heater InstallationInstallation Items Check GAS TypeRemoving Front Panel Of Heater Installing Heater to WallThermostat Sensing Bulb Mounting BracketMarking Screw Locations Methods For Attaching Mounting Bracket To WallPlaque Heater Placing Heater On Mounting Bracket Installing Bottom Mounting ScrewsMounting Base Feet to Heater Connecting to GAS SupplyMounting Base Feet to Floor Where required by local code Mounting Heater to FloorGas Connection Checking GAS ConnectionsPressurize supply piping system by either Pressure Testing Gas Supply Piping SystemOperating Heater NON-THERMOSTAT Models For Your Safety Read Before LightingLighting Instructions To Turn OFF GAS To Appliance Manual Lighting ProcedureThermostat Models For Your Safety Read Before Lighting To Select Heating LevelVP16TA VP26TA Plaque Thermostat OperationPilot Flame Pattern Inspecting HeaterBurner Flame Pattern Cabinet Cleaning MaintenanceCleaning Burner Pilot AIR Inlet ODS/PILOT and BurnerObserved Problem Possible Cause Remedy TroubleshootingPress in control knob fully Metal expanding while heating or contracting while cooling Gas leak. See WarningSpecifications Cabinet Body Models Illustrated Parts BreakdownParts List Cabinet Body Models VP16ITA and VP22ITA KEY Part Number VP16ITA VP22ITA Description Burner Assembly Models VP16A and VN18A Illustrated Parts Breakdown and Parts ListODS/Pilot Burner Assembly VP26A, VN30A Burner Assembly Models VP26A and VN30ABurner Assembly VP16ITA Burner Assembly Models VP16ITA and VP22ITABurner Assembly Models VP16TA, VN18TA, VP26TA, and VN30TA Parts Under Warranty Replacement PartsService Publications Service Hints Technical ServiceEquipment Shutoff Valve GA5010 AccessoriesParts Central FAN Kits GA3250T113052-01A 113052-01A Keep this Warranty Warranty InformationLimited Warranty Vanguard VENT-FREE Infrared GAS Heaters