Goodman Mfg VC8 instruction manual START-UP Procedure and Adjustment

Page 22

START-UP PROCEDURE AND ADJUSTMENT

A closed return duct system must be used, with the return duct connected to the furnace. NOTE: Ductwork must never be attached to the back of the furnace. For installations requiring more than 1800 CFM, use a bottom return or two sided return. Supply and return connections to the furnace may be made with flexible joints to reduce noise transmission. To prevent the blower from interfering with combustion air or draft when a cen- tral return is used, a connecting duct must be installed be- tween the unit and the utility room wall. A room, closet, or alcove must not be used as a return air chamber.

When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool position.

When the furnace is installed without a cooling coil, it is rec- ommended that a removable access panel be provided in the outlet air duct. This opening shall be accessible when the fur- nace is installed and shall be of such a size that the heat exchanger can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream. The ac- cess panel must be made to prevent air leaks when the furnace is in operation.

When the furnace is heating, the temperature of the return air entering the furnace must be between 55°F and 100°F.

When a furnace is installed so that supply ducts carry air cir- culated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct sealed to the furnace casing and terminating outside the space con- taining the furnace.

CHECKING DUCT STATIC

Refer to your furnace rating plate for the maximum ESP (exter- nal duct static) rating.

Total external static refers to everything external to the furnace cabinet. Cooling coils, filters, ducts, grilles, registers must all be considered when reading your total external static pres- sure. The supply duct pressure must be read between the fur- nace and the cooling coil. This reading is usually taken by removing the “A” shaped block off plate from the end on the coil; drilling a test hole in it and reinstalling the block off plate. Take a duct static reading at the test hole. Tape up the test hole after your test is complete. The negative pressure must be read between the filter and the furnace blower.

To determine total external duct static pressure, proceed as follows;

1.With clean filters in the furnace, use a draft gauge (inclined manometer) to measure the static pressure of the return duct at the inlet of the furnace. (Negative Pressure)

2.Measure the static pressure of the supply duct. (Positive Pressure)

3.The difference between the two numbers is .4” w.c. Example:

static reading from return duct = -.1" w.c. static reading from supply duct = .3" w.c.

total external static pressure on this system = .4" w.c.

NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired. If an air conditioner coil or Electronic Air Cleaner is used in conjunction with the furnace, the readings must also include theses components, as shown in the following drawing.

4. Consult proper tables for the quantity of air.

If the total external static pressure exceeds the maximum listed on the furnace rating plate, check for closed dampers, regis- ters, undersized and/or oversized poorly laid out duct work.

Checking Static Pressure

(80% Furnace Shown, 90% Similar)

Too much external static pressure will result in insufficient air that can cause excessive temperature rise. This can cause limit switch tripping and heat exchanger failure.

FILTERS - READ THIS SECTION BEFORE INSTALLING THE RETURN AIR DUCTWORK

Filters must be used with this furnace. Discuss filter mainte- nance with the building owner. Filters do not ship with this furnace, but must be provided by the installer. Filters must com-

22

Image 22
Contents Installation Instructions for *D, MVC8 GAS Furnace Upright Installations Table of Contents Safety Precautions What to do if YOU Smell GASProduct Application Keep this literature in a safe place for future referenceLocation Requirements and Considerations Product DescriptionCSA International National Fire Protection Association, IncClearances and Accessibility Following vent testing procedure is reproduced from Combustion & Ventilation CategoryExterior Masonry Chimneys Category I Furnaces only Category I Venting Vertical VentingExteriormasonrychimneyscategoryifurnacesonly Proper Chimney Termination? Check Check 3 Chimney Crown Condition Electrical Connections High Voltage Important Note Thermostat Wiring Diagrams Single Stage Heating with Single Stage CoolingAccessories Wiring GAS Supply and PipingCirculating AIR and Filters Gas Altitude Kit Orifice Manifold PressureGeneral Furnace Layout Propane Gas Installation Typ START-UP Procedure and Adjustment Checking Static Pressure 80% Furnace Shown, 90% SimilarUpright Installations White-Rodgers Model 36G54 Connected to Manometer White-Rodgers Model 36G54 Two-StageHoneywell Model VR9205 Connected to Manometer Honeywell Model VR9205 Two-StageMeasuring Inlet Gas Pressure Alt. Method Temperature Rise Measurement ExampleSwitch Bank S4 Switch Bank S4 Heat Off Delay DipswitchesComfortnet System Comfortnet SystemSystem Wiring using Four-Wires CTK01AATo step to the next item Configuration Cool Airflow CL CFM Operational Checks & Safety Circuit Description Normal Sequence of OperationOperational Checks Safety Circuit Description Troubleshooting & MaintenanceTroubleshooting Maintenance MiscellaneousBefore Leaving AN Installation Repair and Replacement PartsTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes DIP Switches AIR Flow DataMVC8AA Wiring Diagram RD WHMVC8AB, *DVC8AA Wiring Diagram

VC8 specifications

Goodman Manufacturing has established itself as a leading provider of quality heating, ventilation, and air conditioning (HVAC) systems. Among its impressive lineup is the Goodman VC8, a versatile and efficient variable-capacity air conditioner that stands out due to its innovative design and advanced technologies.

The Goodman VC8 is known for its superior energy efficiency, featuring a SEER (Seasonal Energy Efficiency Ratio) rating higher than 20. This means that it operates efficiently across various climatic conditions, ensuring optimal cooling with minimal energy consumption. The high SEER rating not only translates to lower energy bills but also contributes to a reduced environmental footprint, making it a smart choice for eco-conscious consumers.

One of the standout features of the VC8 is its variable-speed compressor, which allows the system to adjust its output based on the cooling needs of the space. This technology enables the unit to run at lower speeds for longer periods, maintaining a consistent temperature while reducing energy usage. The variable-speed operation also contributes to quieter operation compared to traditional air conditioning systems. Homeowners can enjoy a peaceful indoor environment without the disruptive noise commonly associated with air conditioning units.

In terms of comfort, the Goodman VC8 employs advanced humidity control features, ensuring that moisture is efficiently managed within the space. This not only enhances comfort levels but also helps to prevent issues related to excessive humidity, such as mold growth and structural damage.

The VC8 is designed for reliable performance and durability, with its robust construction and dependable components. Goodman manufactures its products with high-quality materials to withstand the rigors of daily use and various weather conditions, ensuring long-lasting operation.

Additionally, the VC8 incorporates smart technology features, including compatibility with Wi-Fi-enabled thermostats. Homeowners can easily monitor and control their system remotely, providing convenience and peace of mind.

The Goodman VC8 is an exemplary solution for those looking for an energy-efficient, advanced air conditioning system. With its variable-speed compressor, excellent humidity control, durable construction, and smart features, it promises comfort and reliability suitable for any residential space. By choosing Goodman, homeowners can invest in a quality HVAC system designed to meet modern needs and preferences.