Goodman Mfg VC8 instruction manual Troubleshooting & Maintenance, Safety Circuit Description

Page 36

TROUBLESHOOTING & MAINTENANCE

Burner Flame

SAFETY CIRCUIT DESCRIPTION

A number of safety circuits are employed to ensure safe and proper furnace operation. These circuits serve to control any potential safety hazards and serve as inputs in the monitoring and diagnosis of abnormal function. These circuits are con- tinuously monitored during furnace operation by the integrated control module.

INTEGRATED CONTROLMODULE

The integrated control module is an electronic device which, if a potential safety concern is detected, will take the necessary precautions and provide diagnostic information through an LED.

PRIMARY LIMIT

The primary limit control is located on the partition panel and monitors heat exchanger compartment temperatures. It is a normally-closed (electrically), automatic reset, temperature-ac- tivated sensor. The limit guards against overheating as a result of insufficient conditioned air passing over the heat exchanger.

AUXILIARY LIMIT

The auxiliary limit controls are located on or near the circulator blower and monitors blower compartment temperatures. They are a normally-closed (electrically), auto-reset sensors. These limits guard against overheating as a result of insufficient con- ditioned air passing over the heat exchanger.

ROLLOUT LIMIT

The rollout limit controls are mounted on the burner/manifold assembly and monitor the burner flame. They are normally- closed (electrically), manual-reset sensors. These limits guard against burner flames not being properly drawn into the heat exchanger.

PRESSURE SWITCHES

The pressure switches are normally-open (closed during op- eration) negative air pressure-activated switches. They moni- tor the airflow (combustion air and flue products) through the heat exchanger via pressure taps located on the induced draft blower and the coil front cover. These switches guard against insufficient airflow (combustion air and flue products) through the heat exchanger and/or blocked condensate drain condi- tions.

FLAME SENSOR

The flame sensor is a probe mounted to the burner/manifold assembly which uses the principle of flame rectification to de- termine the presence or absence of flame.

TROUBLESHOOTING

ELECTROSTATIC DISCHARGE (ESD)PRECAUTIONS

NOTE: Discharge body’s static electricity before touching unit. An electrostatic discharge can adversely affect electrical components.

Use the following precautions during furnace installation and servicing to protect the integrated control module from dam- age. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid expos- ing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) furnaces.

1.Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.

2.Firmly touch a clean, unpainted, metal surface of the furnace away from the control. Any tools held in a person’s hand during grounding will be discharged.

3.Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.

4.Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.

DIAGNOSTIC CHART

WARNING

HIGH VOLTAGE !

TO AVOID PERSONAL INJURY OR DEATH DUE TO

ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER

BEFORE PERFORMING ANY SERVICE OR MAINTENANCE.

Refer to the Troubleshooting Chart at the end of this manual for assistance in determining the source of unit operational prob- lems. The dual 7-segment LED display will display an error code that may contain a letter and number. The error code may be used to assist in troubleshooting the unit.

36

Image 36
Contents Installation Instructions for *D, MVC8 GAS Furnace Upright Installations Table of Contents Safety Precautions What to do if YOU Smell GASProduct Application Keep this literature in a safe place for future referenceLocation Requirements and Considerations Product DescriptionCSA International National Fire Protection Association, IncClearances and Accessibility Following vent testing procedure is reproduced from Combustion & Ventilation CategoryExterior Masonry Chimneys Category I Furnaces only Category I Venting Vertical VentingExteriormasonrychimneyscategoryifurnacesonly Proper Chimney Termination? Check Check 3 Chimney Crown Condition Electrical Connections High Voltage Important Note Thermostat Wiring Diagrams Single Stage Heating with Single Stage CoolingAccessories Wiring GAS Supply and PipingCirculating AIR and Filters Gas Altitude Kit Orifice Manifold PressureGeneral Furnace Layout Propane Gas Installation Typ START-UP Procedure and Adjustment Checking Static Pressure 80% Furnace Shown, 90% SimilarUpright Installations White-Rodgers Model 36G54 Two-Stage Honeywell Model VR9205 Connected to ManometerWhite-Rodgers Model 36G54 Connected to Manometer Honeywell Model VR9205 Two-StageMeasuring Inlet Gas Pressure Alt. Method Temperature Rise Measurement ExampleSwitch Bank S4 Switch Bank S4 Heat Off Delay DipswitchesComfortnet System Comfortnet SystemSystem Wiring using Four-Wires CTK01AATo step to the next item Configuration Cool Airflow CL CFM Operational Checks & Safety Circuit Description Normal Sequence of OperationOperational Checks Troubleshooting & Maintenance Safety Circuit DescriptionTroubleshooting Maintenance MiscellaneousBefore Leaving AN Installation Repair and Replacement PartsTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes DIP Switches AIR Flow DataMVC8AA Wiring Diagram RD WHMVC8AB, *DVC8AA Wiring Diagram

VC8 specifications

Goodman Manufacturing has established itself as a leading provider of quality heating, ventilation, and air conditioning (HVAC) systems. Among its impressive lineup is the Goodman VC8, a versatile and efficient variable-capacity air conditioner that stands out due to its innovative design and advanced technologies.

The Goodman VC8 is known for its superior energy efficiency, featuring a SEER (Seasonal Energy Efficiency Ratio) rating higher than 20. This means that it operates efficiently across various climatic conditions, ensuring optimal cooling with minimal energy consumption. The high SEER rating not only translates to lower energy bills but also contributes to a reduced environmental footprint, making it a smart choice for eco-conscious consumers.

One of the standout features of the VC8 is its variable-speed compressor, which allows the system to adjust its output based on the cooling needs of the space. This technology enables the unit to run at lower speeds for longer periods, maintaining a consistent temperature while reducing energy usage. The variable-speed operation also contributes to quieter operation compared to traditional air conditioning systems. Homeowners can enjoy a peaceful indoor environment without the disruptive noise commonly associated with air conditioning units.

In terms of comfort, the Goodman VC8 employs advanced humidity control features, ensuring that moisture is efficiently managed within the space. This not only enhances comfort levels but also helps to prevent issues related to excessive humidity, such as mold growth and structural damage.

The VC8 is designed for reliable performance and durability, with its robust construction and dependable components. Goodman manufactures its products with high-quality materials to withstand the rigors of daily use and various weather conditions, ensuring long-lasting operation.

Additionally, the VC8 incorporates smart technology features, including compatibility with Wi-Fi-enabled thermostats. Homeowners can easily monitor and control their system remotely, providing convenience and peace of mind.

The Goodman VC8 is an exemplary solution for those looking for an energy-efficient, advanced air conditioning system. With its variable-speed compressor, excellent humidity control, durable construction, and smart features, it promises comfort and reliability suitable for any residential space. By choosing Goodman, homeowners can invest in a quality HVAC system designed to meet modern needs and preferences.