Goodman Mfg VC8 instruction manual Check 3 Chimney Crown Condition

Page 13

EXTERIOR MASONRY CHIMNEYS - CATEGORY I FURNACES ONLY

Liquid fuel appliances include oil furnaces, oil-fired boilers and oil-fired water heaters.

Appliances which burn propane (sometimes referred to as LP (liquefied petroleum)) gas are considered gas-fired appliances.

CHECK 3 - CHIMNEY CROWN CONDITION.

Damage from condensate usually shows up first in the crown. If any of the following trouble signs are present, the condition of the crown is not satisfactory:

a)Crown leaning

b)Bricks missing

c)Mortar missing

d)Tile liner cracked

e)No tile liner

f)Salt staining at mortar joints. (White stains, and mortar becomes sandy and/or erodes.)

For problems a, b, or c, see Fix 3. If problems d, e, or f are present, see Fix 4. IMPORTANT: It may be necessary to follow both Fix 3 and Fix 4.

CHECK 4 - DEBRIS IN CLEANOUT.

A cleanout (dropleg) must be present such that the upper edge of the cleanout cover is at least 12 inches below the lower edge of the lowest chimney inlet opening.

A chimney without a cleanout could become partially blocked by debris. If no cleanout is present, the chimney must be re- lined (Fix 4). Remove the cleanout cover, and examine the cleanout for debris. If significant amounts of any of the following are found:

Fuel oil residue

Bricks

Mortar or sand

Pieces of the tile liner

Rusted pieces of the metallic liner - reline the chimney (Fix 4).

CHECK 5 - LINER CONDITION.

If a metal liner is present, it must be checked. It cannot be assumed that all existing metal liners are correctly installed and in good condition.

Remove the lowest existing vent connector, and examine the inside of the elbow or tee at the base of the liner. A small amount of soot may be considered acceptable, provided the installer vacuums it away. If rusted pieces of the liner have collected here, the metal liner must be removed and replaced (Fix 4).

Next, gently tap the inside of the liner with a Phillips screw- driver. If the screwdriver perforates the liner, or if the tapping does not sound like metal hitting metal, the liner must be re- moved and replaced (Fix 4).

Remember that all appliances must be vented inside the liner. Venting one appliance inside the liner and another appliance outside the liner is not acceptable.

Next, use a flashlight and small mirror to sight up the liner. B vent must be supported so as to not come into direct contact with the chimney walls or tile liner. If it is not, it can probably be rehung so as to be acceptable. A thimble or fire stop may be helpful here.

Flexible liners should be hung straight or nearly straight. If it is spiraled in the chimney and in good condition, it should be rehung. To do this, break the top seal; pull up and cut off the excess liner length, and refit the top seal. Use caution when doing this, as the cut edges of flexible liners may be sharp.

The surfaces of the liner must be physically sound. If gaps or holes are present, the metal liner must be removed and re- placed (Fix 4). Finally, confirm that the metal liner is the cor- rect size for the appliances to be installed. Use the GAMA tables and rules.

If a metal liner is not present, a clay tile liner must be present, or the chimney must be lined (Fix 4).

Use a flashlight and small mirror at the cleanout or vent con- nector to inspect the clay tile liner. If any of the following prob- lems are present:

Tile sections misaligned

Tile sections missing

Gaps between tile sections

Signs of condensate drainage at the cleanout or vent connectors

Mortar protruding from between tile sections

Use of sewer pipe or drainage pipe rather than an approved fire clay tile reline the chimney (Fix 4).

Next, measure the size of the liner. It may be possible to do this from the cleanout. The liner must be at least as large as the minimum size established by the tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments. If the liner is too small or too large, then the chimney must be relined (Fix 4).

CHECK 6 - DILUTION AIR.

If gas-fired appliances are to be vented into a clay tile liner, a source of dilution air is required.

Dilution air cannot be obtained through:

Induced draft appliances

Natural draft appliances with vent dampers

Sufficient dilution air can ordinarily be obtained through the draft hood of a natural draft appliance only if the appliance’s vent connector does not include a vent damper. If dilution air will not be available, the chimney must be relined (Fix 4).

CHECK 7 - COMPLETE THE INSTALLATION.

If Checks 1 through 6 have been satisfactory, and the liner is an acceptable size as determined by the tables in National Fuel

13

Image 13
Contents Installation Instructions for *D, MVC8 GAS Furnace Upright Installations Table of Contents What to do if YOU Smell GAS Safety PrecautionsKeep this literature in a safe place for future reference Product ApplicationProduct Description Location Requirements and ConsiderationsNational Fire Protection Association, Inc CSA InternationalClearances and Accessibility Combustion & Ventilation Category Following vent testing procedure is reproduced fromCategory I Venting Vertical Venting Exterior Masonry Chimneys Category I Furnaces onlyExteriormasonrychimneyscategoryifurnacesonly Proper Chimney Termination? Check Check 3 Chimney Crown Condition Electrical Connections High Voltage Important Note Single Stage Heating with Single Stage Cooling Thermostat Wiring DiagramsGAS Supply and Piping Accessories WiringGas Altitude Kit Orifice Manifold Pressure Circulating AIR and FiltersGeneral Furnace Layout Propane Gas Installation Typ Checking Static Pressure 80% Furnace Shown, 90% Similar START-UP Procedure and AdjustmentUpright Installations Honeywell Model VR9205 Connected to Manometer White-Rodgers Model 36G54 Two-StageWhite-Rodgers Model 36G54 Connected to Manometer Honeywell Model VR9205 Two-StageMeasuring Inlet Gas Pressure Alt. Method Example Temperature Rise MeasurementSwitch Bank S4 Heat Off Delay Dipswitches Switch Bank S4Comfortnet System Comfortnet SystemCTK01AA System Wiring using Four-WiresTo step to the next item Configuration Cool Airflow CL CFM Normal Sequence of Operation Operational Checks & Safety Circuit DescriptionOperational Checks Safety Circuit Description Troubleshooting & MaintenanceTroubleshooting Miscellaneous MaintenanceRepair and Replacement Parts Before Leaving AN InstallationInternal Troubleshooting ChartLimit Message ChartInvalid Trips Status Codes AIR Flow Data DIP SwitchesRD WH MVC8AA Wiring DiagramMVC8AB, *DVC8AA Wiring Diagram

VC8 specifications

Goodman Manufacturing has established itself as a leading provider of quality heating, ventilation, and air conditioning (HVAC) systems. Among its impressive lineup is the Goodman VC8, a versatile and efficient variable-capacity air conditioner that stands out due to its innovative design and advanced technologies.

The Goodman VC8 is known for its superior energy efficiency, featuring a SEER (Seasonal Energy Efficiency Ratio) rating higher than 20. This means that it operates efficiently across various climatic conditions, ensuring optimal cooling with minimal energy consumption. The high SEER rating not only translates to lower energy bills but also contributes to a reduced environmental footprint, making it a smart choice for eco-conscious consumers.

One of the standout features of the VC8 is its variable-speed compressor, which allows the system to adjust its output based on the cooling needs of the space. This technology enables the unit to run at lower speeds for longer periods, maintaining a consistent temperature while reducing energy usage. The variable-speed operation also contributes to quieter operation compared to traditional air conditioning systems. Homeowners can enjoy a peaceful indoor environment without the disruptive noise commonly associated with air conditioning units.

In terms of comfort, the Goodman VC8 employs advanced humidity control features, ensuring that moisture is efficiently managed within the space. This not only enhances comfort levels but also helps to prevent issues related to excessive humidity, such as mold growth and structural damage.

The VC8 is designed for reliable performance and durability, with its robust construction and dependable components. Goodman manufactures its products with high-quality materials to withstand the rigors of daily use and various weather conditions, ensuring long-lasting operation.

Additionally, the VC8 incorporates smart technology features, including compatibility with Wi-Fi-enabled thermostats. Homeowners can easily monitor and control their system remotely, providing convenience and peace of mind.

The Goodman VC8 is an exemplary solution for those looking for an energy-efficient, advanced air conditioning system. With its variable-speed compressor, excellent humidity control, durable construction, and smart features, it promises comfort and reliability suitable for any residential space. By choosing Goodman, homeowners can invest in a quality HVAC system designed to meet modern needs and preferences.