Goodman Mfg VC8 instruction manual General Furnace Layout

Page 20

GAS SUPPLY AND PIPING

Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is installed, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace.

Tighten all joints securely.

Connect the furnace to the building piping by one of the following methods:

Rigid metallic pipe and fittings.

Semi-rigid metallic tubing and metallic fittings.

Aluminum alloy tubing must not be used in exterior locations.

Use listed gas appliance connectors in accordance

with their instructions. Connectors must be fully in the same room as the furnace.

Protect connectors and semi-rigid tubing against

physical and thermal damage when installed. Ensure aluminum-alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.

Location of Manual Valve

(Installed Ahead of

Ground Joint Pipe Union)

When the gas piping enters through the left side of the furnace, the installer must supply the following fittings (starting from the gas valve):

90 degree elbow.

Straight pipe to reach the exterior of the furnace.

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also need to supply a transition piece from 1/2 inch to another pipe size.

COUNTERFLOW INSTALLATIONS

When the gas piping enters through the left side of the furnace, the installer must supply a straight pipe and a 90 degree elbow to reach the exterior of the furnace.

A ground joint union, drip leg and manual shutoff valve must also be supplied by the installer. In most cases, the installer may also need to supply a transition piece from ½” to another pipe size. When the gas piping enters through the right side of the furnace, the installer must supply the following fittings (start- ing at the gas valve):

Close Nipple

90 Degree Elbow

Straight Pipe to Reach Exterior of Furnace.

GAS PIPING CHECKS

Height Required

By Local Code

Ground Joint Pipe Union

To Be Installed Ahead of

Gas Valve

Drip Leg

Reducing Coupling 1/2” x 1/8” with 1/8” Pipe Plug to Measure Line Gas Pressure

``

Before placing unit in operation, leak test the unit and gas con- nections.

WARNING

TO AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.

Check for leaks using an approved chloride-free soap and wa- ter solution, an electronic combustible gas detector, or other approved testing methods.

General Furnace Layout

UPFLOW INSTALLATIONS

When the gas piping enters through the right side of the fur- nace, the installer must supply the following fittings (starting from the gas valve):

Close nipple.

90 degree elbows.

Straight pipe to reach the exterior of the furnace .

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also need to supply a transition piece from 1/2" to another pipe size.

NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.

Disconnect this unit and shutoff valve from the gas supply pip- ing system before pressure testing the supply piping system with pressures in excess of 1/2 psig (3.48 kPa).

This unit must be isolated from the gas supply system by clos- ing its manual shutoff valve before pressure testing of gas sup- ply piping system with test pressures equal to or less than 1/2 psig (3.48 kPa).

20

Image 20
Contents Installation Instructions for *D, MVC8 GAS Furnace Upright Installations Table of Contents Safety Precautions What to do if YOU Smell GASProduct Application Keep this literature in a safe place for future referenceLocation Requirements and Considerations Product DescriptionCSA International National Fire Protection Association, IncClearances and Accessibility Following vent testing procedure is reproduced from Combustion & Ventilation CategoryExterior Masonry Chimneys Category I Furnaces only Category I Venting Vertical VentingExteriormasonrychimneyscategoryifurnacesonly Proper Chimney Termination? Check Check 3 Chimney Crown Condition Electrical Connections High Voltage Important Note Thermostat Wiring Diagrams Single Stage Heating with Single Stage CoolingAccessories Wiring GAS Supply and PipingCirculating AIR and Filters Gas Altitude Kit Orifice Manifold PressureGeneral Furnace Layout Propane Gas Installation Typ START-UP Procedure and Adjustment Checking Static Pressure 80% Furnace Shown, 90% SimilarUpright Installations White-Rodgers Model 36G54 Two-Stage Honeywell Model VR9205 Connected to ManometerWhite-Rodgers Model 36G54 Connected to Manometer Honeywell Model VR9205 Two-StageMeasuring Inlet Gas Pressure Alt. Method Temperature Rise Measurement ExampleSwitch Bank S4 Switch Bank S4 Heat Off Delay DipswitchesComfortnet System Comfortnet SystemSystem Wiring using Four-Wires CTK01AATo step to the next item Configuration Cool Airflow CL CFM Operational Checks & Safety Circuit Description Normal Sequence of OperationOperational Checks Troubleshooting Troubleshooting & MaintenanceSafety Circuit Description Maintenance MiscellaneousBefore Leaving AN Installation Repair and Replacement PartsTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes DIP Switches AIR Flow DataMVC8AA Wiring Diagram RD WHMVC8AB, *DVC8AA Wiring Diagram

VC8 specifications

Goodman Manufacturing has established itself as a leading provider of quality heating, ventilation, and air conditioning (HVAC) systems. Among its impressive lineup is the Goodman VC8, a versatile and efficient variable-capacity air conditioner that stands out due to its innovative design and advanced technologies.

The Goodman VC8 is known for its superior energy efficiency, featuring a SEER (Seasonal Energy Efficiency Ratio) rating higher than 20. This means that it operates efficiently across various climatic conditions, ensuring optimal cooling with minimal energy consumption. The high SEER rating not only translates to lower energy bills but also contributes to a reduced environmental footprint, making it a smart choice for eco-conscious consumers.

One of the standout features of the VC8 is its variable-speed compressor, which allows the system to adjust its output based on the cooling needs of the space. This technology enables the unit to run at lower speeds for longer periods, maintaining a consistent temperature while reducing energy usage. The variable-speed operation also contributes to quieter operation compared to traditional air conditioning systems. Homeowners can enjoy a peaceful indoor environment without the disruptive noise commonly associated with air conditioning units.

In terms of comfort, the Goodman VC8 employs advanced humidity control features, ensuring that moisture is efficiently managed within the space. This not only enhances comfort levels but also helps to prevent issues related to excessive humidity, such as mold growth and structural damage.

The VC8 is designed for reliable performance and durability, with its robust construction and dependable components. Goodman manufactures its products with high-quality materials to withstand the rigors of daily use and various weather conditions, ensuring long-lasting operation.

Additionally, the VC8 incorporates smart technology features, including compatibility with Wi-Fi-enabled thermostats. Homeowners can easily monitor and control their system remotely, providing convenience and peace of mind.

The Goodman VC8 is an exemplary solution for those looking for an energy-efficient, advanced air conditioning system. With its variable-speed compressor, excellent humidity control, durable construction, and smart features, it promises comfort and reliability suitable for any residential space. By choosing Goodman, homeowners can invest in a quality HVAC system designed to meet modern needs and preferences.