Goodman Mfg VC8 instruction manual Switch Bank S4, Heat Off Delay Dipswitches

Page 28

START-UP PROCEDURE AND ADJUSTMENT

7.Select the heating speed for your model from the heating speed chart in the Specification Sheet. The adjust setting (already established by the cooling speed selection) determines which set of speeds are available. The selected speed must provide a temperature rise within the rise range listed with the particular model.

Example: The *MVC80704BX is set for 990 CFM on cooling, the “ADJUST” is set to “+” (plus). The four heating speeds available are “A Plus”, “B Plus”, “C Plus”, and “D Plus”. “A Plus” has a rise of 38°F for both stages which is within the 20-50°F rise range for the *MVC80704BX . This setting will keep electrical consumption to a minimum. Set the “Heat” speed DIP switches to “A”.

Switch Bank: S4

Heating

DIP Switch No.

Airflow

7

8

A

OFF

OFF

B*

ON

OFF

C

OFF

ON

D

ON

ON

(*Indicates factory setting)

8.Select the desired “heating” speed tap by positioning switches 7 and 8 appropriately. Refer to figure above. Verify CFM by noting the number displayed on the dual 7-segment LED display.

In general lower heating speeds will: reduce electrical consump- tion, lower operating sound levels of the blower, and increase the outlet air temperature delivered to the home. The speeds available allow the blower performance to be optimized for the particular homeowner’s needs.

BLOWER HEAT OFF DELAY TIMINGS

The integrated control module provides a selectable heat off delay function. The heat off delay period may be set to 90, 120, 150, 180 seconds using the DIP switches or jumper provided on the control module. The delay is factory shipped at 150 seconds but may be changed to suit the installation require- ments and/or homeowner preference. Refer to the following fig- ures for switch positions and corresponding delay times.

Switch Bank: S1

Heat OFF Delay

DIP Switch No.

1

2

 

90 seconds

OFF

OFF

120 seconds

ON

OFF

150 seconds*

OFF

ON

180 seconds

ON

ON

(*Indicates factory setting)

Heat Off Delay Dipswitches

 

 

 

Speed Selection Dip Switches

 

Model

Tap

Low Stage

High Stage

Low Stage

High Stage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool

Cool

Heat

Heat

 

 

 

Cool

 

Adjust

 

Profile

Heat

 

 

 

 

 

 

 

 

 

 

 

 

A

390

600

735

1050

 

 

 

Selection

 

Selection

 

Selection

Selection

 

 

 

 

Switches

 

Switches

 

Switches

Switches

*DVC80703BX*

B

520

800

805

1150

 

TAP

 

1

2

 

3

 

4

 

5

 

6

 

7

 

8

C

650

1000

875

1250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

780

1200

935

1350

 

A

 

OFF

OFF

 

OFF

OFF

 

OFF

 

OFF

OFF

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

520

800

945

1350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

ON

OFF

 

ON

OFF

 

ON

 

OFF

ON

 

OFF

 

 

 

 

 

 

 

*DVC80905CX*

B

715

1100

1015

1450

 

C

 

OFF

ON

 

OFF

ON

 

OFF

 

ON

OFF

 

ON

C

910

1400

1085

1550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

1170

1800

1155

1650

 

D

 

ON

ON

 

ON

ON

 

ON

 

ON

ON

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

553

850

1085

1550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Profiles

 

Pre-Run

 

 

Short-Run

 

 

OFF Delay

 

 

 

 

 

 

 

*DVC81155CX*

B

748

1150

1155

1650

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

-------

 

 

 

 

--------

 

 

 

60 sec/100%

C

943

1450

1225

1750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

1203

1850

1260

1800

 

B

 

-------

 

 

30 sec/50%

 

60 sec/100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

390

600

875

1250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

-------

 

 

7.5 min/82%

 

 

60 sec/100%

*MVC80704BX*

 

 

 

 

 

 

B

520

800

945

1350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

30 sec/50%

7.5 min/82%

 

 

30 sec/50%

 

C

715

1100

1015

1450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

910

1400

1085

1550

To set airflow: (1) Select model and desired

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

high stage cooling airflow.

Determine the corresponding tap

 

A

520

800

1050

1500

 

( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate

 

*MVC80905CX*

B

715

1100

1120

1600

ON / OFF positions. (2) Select model and desired high stage

 

 

 

 

 

 

 

 

 

 

C

910

1400

1190

1700

heating airflow. Determine the corresponding tap ( A, B, C, or

 

 

 

 

 

 

 

 

 

 

 

D

1170

1800

1260

1800

D ). Set dip switches 7 and 8 to the appropriate ON / OFF

 

 

positions. (3) Select the airflow adjustment factor taps A and

 

 

 

 

 

 

 

A

520

800

1210

1725

D are 1; Tap B is +10%; Tap C -10%. Set dip switches 3 and 4

 

to the appropriate ON / OFF positions.

 

 

 

 

 

*MVC81155CX*

B

715

1100

1225

1750

To set Comfort Mode: Select desired Comfort Mode profile

 

 

 

C

910

1400

1245

1775

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(see profiles above). Set switches 5 and 6 to the appropriate

 

 

 

D

1175

1800

1260

1800

 

ON / OFF positions.

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Airflow data shown applies to legacy mode operation only. For a fully communicating system, please see the outdoor unit’s installation instructions for cooling and pump heating airflow data. See ComfortNet™ System - Airflow Consideration section for details.

28

Image 28
Contents Installation Instructions for *D, MVC8 GAS Furnace Upright Installations Table of Contents Safety Precautions What to do if YOU Smell GASProduct Application Keep this literature in a safe place for future referenceLocation Requirements and Considerations Product DescriptionCSA International National Fire Protection Association, IncClearances and Accessibility Following vent testing procedure is reproduced from Combustion & Ventilation CategoryExterior Masonry Chimneys Category I Furnaces only Category I Venting Vertical VentingExteriormasonrychimneyscategoryifurnacesonly Proper Chimney Termination? Check Check 3 Chimney Crown Condition Electrical Connections High Voltage Important Note Thermostat Wiring Diagrams Single Stage Heating with Single Stage CoolingAccessories Wiring GAS Supply and PipingCirculating AIR and Filters Gas Altitude Kit Orifice Manifold PressureGeneral Furnace Layout Propane Gas Installation Typ START-UP Procedure and Adjustment Checking Static Pressure 80% Furnace Shown, 90% SimilarUpright Installations White-Rodgers Model 36G54 Two-Stage Honeywell Model VR9205 Connected to ManometerWhite-Rodgers Model 36G54 Connected to Manometer Honeywell Model VR9205 Two-StageMeasuring Inlet Gas Pressure Alt. Method Temperature Rise Measurement ExampleSwitch Bank S4 Switch Bank S4 Heat Off Delay DipswitchesComfortnet System Comfortnet SystemSystem Wiring using Four-Wires CTK01AATo step to the next item Configuration Cool Airflow CL CFM Operational Checks & Safety Circuit Description Normal Sequence of OperationOperational Checks Safety Circuit Description Troubleshooting & MaintenanceTroubleshooting Maintenance MiscellaneousBefore Leaving AN Installation Repair and Replacement PartsTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes DIP Switches AIR Flow DataMVC8AA Wiring Diagram RD WHMVC8AB, *DVC8AA Wiring Diagram

VC8 specifications

Goodman Manufacturing has established itself as a leading provider of quality heating, ventilation, and air conditioning (HVAC) systems. Among its impressive lineup is the Goodman VC8, a versatile and efficient variable-capacity air conditioner that stands out due to its innovative design and advanced technologies.

The Goodman VC8 is known for its superior energy efficiency, featuring a SEER (Seasonal Energy Efficiency Ratio) rating higher than 20. This means that it operates efficiently across various climatic conditions, ensuring optimal cooling with minimal energy consumption. The high SEER rating not only translates to lower energy bills but also contributes to a reduced environmental footprint, making it a smart choice for eco-conscious consumers.

One of the standout features of the VC8 is its variable-speed compressor, which allows the system to adjust its output based on the cooling needs of the space. This technology enables the unit to run at lower speeds for longer periods, maintaining a consistent temperature while reducing energy usage. The variable-speed operation also contributes to quieter operation compared to traditional air conditioning systems. Homeowners can enjoy a peaceful indoor environment without the disruptive noise commonly associated with air conditioning units.

In terms of comfort, the Goodman VC8 employs advanced humidity control features, ensuring that moisture is efficiently managed within the space. This not only enhances comfort levels but also helps to prevent issues related to excessive humidity, such as mold growth and structural damage.

The VC8 is designed for reliable performance and durability, with its robust construction and dependable components. Goodman manufactures its products with high-quality materials to withstand the rigors of daily use and various weather conditions, ensuring long-lasting operation.

Additionally, the VC8 incorporates smart technology features, including compatibility with Wi-Fi-enabled thermostats. Homeowners can easily monitor and control their system remotely, providing convenience and peace of mind.

The Goodman VC8 is an exemplary solution for those looking for an energy-efficient, advanced air conditioning system. With its variable-speed compressor, excellent humidity control, durable construction, and smart features, it promises comfort and reliability suitable for any residential space. By choosing Goodman, homeowners can invest in a quality HVAC system designed to meet modern needs and preferences.