Goodman Mfg VC8 instruction manual Upright Installations

Page 23

START-UP PROCEDURE AND ADJUSTMENT

ply with UL900 or CAN/ULCS111 standards. If the furnace is installed without filters, the warranty will be voided.

NOTE: An undersized opening will cause reduced airflow. The bottom return is set up as a knock out.

UPRIGHT INSTALLATIONS

Depending on the installation and/or customer preference, dif- fering filter arrangements can be applied. Filters can be in- stalled in the central return register or a side panel external filter rack kit (upflows), or the ductwork above a downflow fur- nace. As an alternative, a media air filter or electronic air cleaner can be used as the primary filter.

CIRCULATION AIR FILTERS

One of the most common causes of a problem in a forced air heating system is a blocked or dirty filter. Circulating air filters must be inspected monthly for dirt accumulation and replaced if necessary. Failure to maintain clean filters can cause prema- ture heat exchanger failure.

A new home may require more frequent replacement until all construction dust and dirt is removed. Circulating air filters are to be installed in the return air duct external to the furnace cabinet.

M INIM UM FILTER SIZES for DISPOSABLE FILTERS

FURNACE INPUT

FILTER SIZE

70M

768 in2

90M

960 in2

115M

1022 in2

DISP OSA B LE NOM INA L 300 F .M . FA CE VELOCITY

HORIZONTAL INSTALLATIONS

Filters must be installed in either the central return register or in the return air duct work.

START-UP PROCEDURE AND ADJUSTMENT

Furnace must have a 115 VAC power supply properly connected and grounded. Proper polarity must be maintained for correct operation. In addition to the following start-up and adjustment items, refer to further information in Operational Checks sec- tion.

HEAT ANTICIPATOR SETTING

The heat anticipator in the room thermostat must be correctly adjusted to obtain the proper number of cycles per hour and to prevent “overshooting” of the setting. Set the heat anticipator setting to 0.7 amps. Follow the thermostat manufacturer’s instructions on how to adjust the heat anticipator setting.

FURNACEOPERATION

Purge gas lines of air prior to startup. Be sure not purge lines into an enclosed burner compartment.

Check for leaks using an approved chloride-free soap and wa- ter solution, an electronic combustible gas detector, or other

approved method. Verify that all required kits (propane gas, high altitude, etc.) have been appropriately installed.

FURNACE STARTUP

1.Close the manual gas shutoff valve external to the furnace.

2.Turn off the electrical power to the furnace.

3.Set the room thermostat to the lowest possible setting.

4.Remove the burner compartment door.

NOTE: This furnace is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

5.Move the furnace gas valve manual control to the OFF position.

6.Wait five minutes then smell for gas. Be sure check near the floor as some types of gas are heavier than air.

7.If you smell gas after five minutes, immediately follow the Safety Instructions on page 2 of this manual. If you do not smell gas after five minutes, move the furnace gas valve manual control to the ON position.

8.Replace the burner compartment door.

9.Open the manual gas shutoff valve external to the furnace.

10.Turn on the electrical power to the furnace.

11.Adjust the thermostat to a setting above room temperature.

12.After the burners are lit, set the thermostat to desired temperature.

FURNACE SHUTDOWN

1.Set the thermostat to the lowest setting.

The integrated control will close the gas valve and extinguish flame. Following a 15 second delay, the induced draft blower will be de-energized. After a 120, 150, 180 or 210-second delay period (field selectable delay OFF [90, 120, 150, 180] plus 30-second ramp down), the circulator blower de-energizes.

2.Remove the burner compartment door and move the furnace gas valve manual control to the OFF position.

3.Close the manual gas shutoff valve external to the furnace.

4.Replace the burner compartment door.

GAS SUPPLY PRESSURE MEASUREMENT

CAUTION

TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.

The line pressure supplied to the gas valve must be within the range specified below. The supply pressure can be measured at the gas valve inlet pressure boss or at a hose fitting installed in the gas piping drip leg. The supply pressure must be mea- sured with the burners operating. To measure the gas supply pressure, use the following procedure.

23

Image 23
Contents Installation Instructions for *D, MVC8 GAS Furnace Upright Installations Table of Contents What to do if YOU Smell GAS Safety PrecautionsKeep this literature in a safe place for future reference Product ApplicationProduct Description Location Requirements and ConsiderationsNational Fire Protection Association, Inc CSA InternationalClearances and Accessibility Combustion & Ventilation Category Following vent testing procedure is reproduced fromCategory I Venting Vertical Venting Exterior Masonry Chimneys Category I Furnaces onlyExteriormasonrychimneyscategoryifurnacesonly Proper Chimney Termination? Check Check 3 Chimney Crown Condition Electrical Connections High Voltage Important Note Single Stage Heating with Single Stage Cooling Thermostat Wiring DiagramsGAS Supply and Piping Accessories WiringGas Altitude Kit Orifice Manifold Pressure Circulating AIR and FiltersGeneral Furnace Layout Propane Gas Installation Typ Checking Static Pressure 80% Furnace Shown, 90% Similar START-UP Procedure and AdjustmentUpright Installations Honeywell Model VR9205 Two-Stage White-Rodgers Model 36G54 Two-StageHoneywell Model VR9205 Connected to Manometer White-Rodgers Model 36G54 Connected to ManometerMeasuring Inlet Gas Pressure Alt. Method Example Temperature Rise MeasurementSwitch Bank S4 Heat Off Delay Dipswitches Switch Bank S4Comfortnet System Comfortnet SystemCTK01AA System Wiring using Four-WiresTo step to the next item Configuration Cool Airflow CL CFM Normal Sequence of Operation Operational Checks & Safety Circuit DescriptionOperational Checks Troubleshooting Troubleshooting & MaintenanceSafety Circuit Description Miscellaneous MaintenanceRepair and Replacement Parts Before Leaving AN InstallationInternal Troubleshooting ChartLimit Message ChartInvalid Trips Status Codes AIR Flow Data DIP SwitchesRD WH MVC8AA Wiring DiagramMVC8AB, *DVC8AA Wiring Diagram

VC8 specifications

Goodman Manufacturing has established itself as a leading provider of quality heating, ventilation, and air conditioning (HVAC) systems. Among its impressive lineup is the Goodman VC8, a versatile and efficient variable-capacity air conditioner that stands out due to its innovative design and advanced technologies.

The Goodman VC8 is known for its superior energy efficiency, featuring a SEER (Seasonal Energy Efficiency Ratio) rating higher than 20. This means that it operates efficiently across various climatic conditions, ensuring optimal cooling with minimal energy consumption. The high SEER rating not only translates to lower energy bills but also contributes to a reduced environmental footprint, making it a smart choice for eco-conscious consumers.

One of the standout features of the VC8 is its variable-speed compressor, which allows the system to adjust its output based on the cooling needs of the space. This technology enables the unit to run at lower speeds for longer periods, maintaining a consistent temperature while reducing energy usage. The variable-speed operation also contributes to quieter operation compared to traditional air conditioning systems. Homeowners can enjoy a peaceful indoor environment without the disruptive noise commonly associated with air conditioning units.

In terms of comfort, the Goodman VC8 employs advanced humidity control features, ensuring that moisture is efficiently managed within the space. This not only enhances comfort levels but also helps to prevent issues related to excessive humidity, such as mold growth and structural damage.

The VC8 is designed for reliable performance and durability, with its robust construction and dependable components. Goodman manufactures its products with high-quality materials to withstand the rigors of daily use and various weather conditions, ensuring long-lasting operation.

Additionally, the VC8 incorporates smart technology features, including compatibility with Wi-Fi-enabled thermostats. Homeowners can easily monitor and control their system remotely, providing convenience and peace of mind.

The Goodman VC8 is an exemplary solution for those looking for an energy-efficient, advanced air conditioning system. With its variable-speed compressor, excellent humidity control, durable construction, and smart features, it promises comfort and reliability suitable for any residential space. By choosing Goodman, homeowners can invest in a quality HVAC system designed to meet modern needs and preferences.