Johnson Controls TM9V MP installation manual ID Models OD Models

Page 15

438335-UIM-B-0509

HP 24A Two Stage Heat Pump – Two Stage Variable Speed Furnace (Hot Heat Pump or Conventional)

THERMOSTAT

*PP32U71124

*PP32U72124

C

24 – Volt Common

Y1

First Stage Compressor

R

24 – Volt Hot

G

Fan

W2

Second Stage

Aux. Heat

O

Reversing Valve

Energized in Cool

L

Malfunction Light

Y2

Second Stage

Compressor

E/W1

First Stage Aux. Heat

DHM

Dehumidistat

HM

Humidistat

Step 1 of the Thermostat Installer Table must be set to Heat Pump

Step 2 of the Thermostat Installer Table must be set to 2

E2/P Switch must be in the

E2 position

24VAC Humidifier

(Optional)

 

 

ID MODELS

 

 

 

 

 

 

 

OD MODELS

 

 

PV(8/9)

 

 

 

 

 

 

 

YZE

 

 

(F/L)*(8/9)V

 

 

 

 

 

 

 

YZH

 

 

(G/L)*(8/9)V

 

 

 

 

 

 

 

 

H*5

 

 

 

TM(8/9)V

 

 

 

 

 

 

 

 

H*8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWO STAGE

 

 

 

 

 

 

 

TWO STAGE

 

 

 

VARIABLE SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT PUMP

 

 

 

FURNACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

TWO STAGE

 

 

 

 

1

 

YORKGUARD VI

 

 

VARIABLE SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

FURNACE CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

C

 

 

 

24 – Volt Common

 

 

 

 

 

 

 

24 – Volt Common

 

 

 

Y1

 

 

 

 

 

 

 

Y1

 

 

 

Single Stage

 

 

 

 

 

 

 

Single Stage

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

Compressor

 

 

 

R

 

 

 

 

 

 

 

 

R

 

 

 

24 – Volt Hot

 

 

 

 

 

 

 

24 – Volt Hot

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

W/W1

 

 

 

 

 

 

 

W1 OUT

 

 

 

First Stage Heat

 

 

 

 

 

 

 

First Stage Heat

 

 

 

W2

 

 

 

 

 

 

 

W2 OUT

 

 

 

Second Stage Heat

 

 

 

 

 

 

 

Second Stage Heat

 

 

 

Y/Y2

 

 

 

 

 

 

 

Y2 OUT

 

 

 

Second or Full

 

 

 

 

 

 

 

Second Stage

 

 

 

 

 

 

 

 

 

 

 

 

Stage Compressor

 

 

 

 

 

 

 

Compressor

 

 

 

O

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

Reversing Valve

 

 

 

Reversing Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energized in Cool

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X/L

 

 

 

 

 

 

 

X/L

 

 

 

Malfunction Light

 

 

 

 

 

 

 

Malfunction Light

 

 

 

 

 

 

 

 

 

 

 

 

Y2

 

 

 

 

 

 

 

 

 

 

 

 

Second Stage

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

Auxiliary Heat

 

 

 

DHUM

 

 

 

 

 

 

 

BSG

 

 

 

Dehumidification

 

Bonnet Sensor Kit

 

 

 

Bonnet Sensor

 

 

 

 

 

 

 

 

 

 

 

 

(Optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S1-37309243000

 

 

 

BS

 

 

 

 

 

 

 

 

 

 

 

 

Bonnet Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Change FFuel jumper

 

Move HEAT PUMP

 

on the heat pump control

 

jumper to “YES”

 

to “ON”

 

Move DHUM

 

Change Hot Heat Pump

 

jumper to “YES”

 

jumper on the heat pump

 

if humidistat is to be used.

 

control to “ON” if Hot Heat

 

 

 

Pump Operation is desired.

 

 

 

 

 

 

1

Part Numbers:

 

 

SAP = Legacy

 

 

 

2

Part Numbers:

 

126768 = 031-09137

 

18395 = 031-01996

 

SAP = Legacy

 

 

265904 = 031-09169

 

340512 = 031-09178

 

449572

 

 

FIGURE 21: Thermostat Chart - Two Stage HP with Two Stage Variable Speed Furnace (Hot Heat Pump or Conventional)

Johnson Controls Unitary Products

15

Image 15
Contents List of Tables Section I SafetyList of Sections List of FiguresSpecific Safety Rules and Precautions Safety RequirementsCombustion AIR Quality List of Contaminants Codes and Standards InspectionDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Section II Ductwork Furnace Location and ClearancesDuctwork General Information Furnace Assembly MC & FC Series Coils Floor Base and Ductwork Installation DownflowCoil Installation COIL/FURNACE Assembly MC/FC/PC Series CoilsCoil Size Dimension C Inch Furnace Assembly MC Series Coils onlyFurnace Assembly PC Series Coils Coil / Furnace Assembly HC Series CoilsHorizontal Application Downflow Duct Connectors Attic InstallationBottom Return and Attic Installations Suspended Furnace / Crawl Space InstallationSide Return Filter InstallationAttempt to install filters inside the furnace Section III FiltersSection IV GAS Piping First Stage Manifold Pressures in. w.c Section V Electrical PowerElectrical Power Connections Manifold Pressures in. w.c Manifold Pressures kPaLbs LOW Voltage Control Wiring ConnectionsSupply Voltage Connections AfueAC 9A TWO Stage Variable Speed Furnace OD Models Optional Harness AC 24CID Models OD Models Twinning Accessory ConnectionsElectronic AIR Cleaner Connection Humidifier ConnectionCondensate Drain Trap and Drain Freeze Protection Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Combustion AIR and Vent Safety Section VII Combustion AIR and Vent SystemCombustion AIR/VENT Pipe Sizing Furnace Vent Connection Sizes Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting Fitting Equivalent LengthHome Layout Vent ClearancesVent System Vent Applications and TerminationVenting Multiple Units Ambient Combustion Air Supply Combustion AIR SupplyOutdoor Combustion Air Combustion Air Source From Outdoors13 cm Air Supply Openings and DuctsFree Area Vertical Duct orVent Blower Rotation Specially Engineered InstallationsVentilated Combustion Air Ventilated Combustion Air TerminationCalculating the Furnace Input Natural GAS Section Viii START-UP AdjustmentsGAS Piping Leak Check Ignition System SequenceSeconds For Size of Test Dial Revolution Cu Ft Seconds ForRevolution Cu Ft Inlet GAS Pressure Range Adjustment of Manifold GAS Pressure & Input RateRead the inlet gas pressure Read the manifold gas pressureSection IX Safety Controls Sequence of Operation Limit ControlsSlow Green Flash Normal operation TroubleshootingFurnace Control Diagnostics Hot Surface Ignition SystemDiagnostic Fault Code Storage and Retrieval Section X Replacement Parts List Replacement Part Contact InformationDescription Section XI Wiring Diagram Supersedes 438335-UIM-A-0209 Johnson Controls Unitary Products York Drive Norman, OK

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.