Johnson Controls TM9V MP Accessory Connections, Electronic AIR Cleaner Connection, Twinning

Page 16

438335-UIM-B-0509

ACCESSORY CONNECTIONS

The furnace control will allow power-switching control of various accessories.

ELECTRONIC AIR CLEANER CONNECTION

Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during circulating blower operation.

HUMIDIFIER CONNECTION

Two 1/4” (6.4 mm) spade terminals (HUM and NEUTRAL) for humidifier connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during heating system operation.

A mounting hole is provided on the control panel next to the furnace control board for mounting a humidifier transformer if required.

TWINNING

These furnaces are not to be twinned. If more than one furnace is needed in an application, each furnace must have its own complete duct system and its own wall thermostat.

SECTION VI: CONDENSATE PIPING AND FURNACE VENTING CONFIGURATION

CONDENSATE DRAIN LOCATION

As shipped from the factory:

For all 060, & 080K input furnaces the main drain is plumbed through the casing right-side opening when viewed from the front of the furnace.

For all 100 & 120K input furnaces the main drain is plumbed through the casing left-side opening when viewed from the front of the furnace.

NOTE: The Figures 24 - 27 show the condensate drain arrange- ment for the various possible furnace and vent blower positions.

The condensate hoses must slope downwards at all points.

The furnace condensate pan is self priming and con- tains an internal trap to prevent flue gas leaking. Do not install an external condensate trap.

When drain hose routing changes are required (shown in Figures 24- 27), be sure to cap all un-used openings.

If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate - which will cause the furnace to not operate.

No hose clamps are needed for connecting to the condensate pan.

The furnace, evaporator coil, and humidifier drains may be com- bined and drained together. The evaporator coil drain must have an external, field-supplied trap prior to the furnace drain connec- tion. All drain connections (furnace, evaporator coil, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible.

Condensate must be disposed of properly. Follow local plumbing or wastewater codes. The drain line must maintain a 1/4" per foot (21 mm/m) downward slope to the drain.

If an external vent tee is being installed, then it must have its own condensate trap before it is disposed into an open or vented drain.

This is not to be considered as a second trap as referenced elsewhere in this document.

Open Stand Pipe (Anti-siphon air vent)

5” Min.

Tee

To Open Or

Vented Drain

FIGURE 22: Typical. Condensate drain, vertical installation.

The condensate will flow to the drain better if an open stand pipe is installed in the drain line. See Figure 23.

If evaporator coil or humidifier drains are combined with the furnace drain, then the open stand pipe could be raised higher, above the 5” minimum.

It is possible for condensation to form inside the combustion air (intake) pipe in the summer months if significant length of combus- tion air pipe passes through conditioned space. This problem can be averted by the addition of a simple drain tee, or a drain tee with a drain on the combustion air pipe as close to the furnace as possi- ble, as shown in Figure 24. This is true for all long horizontal vent- ing in any furnace configuration. This will prevent the condensate from entering the furnace.

16

Johnson Controls Unitary Products

Image 16
Contents Section I Safety List of SectionsList of Figures List of TablesSafety Requirements Specific Safety Rules and PrecautionsCombustion AIR Quality List of Contaminants Inspection Codes and StandardsDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Furnace Location and Clearances Section II DuctworkDuctwork General Information Floor Base and Ductwork Installation Downflow Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsFurnace Assembly MC Series Coils only Furnace Assembly PC Series CoilsCoil / Furnace Assembly HC Series Coils Coil Size Dimension C InchDownflow Duct Connectors Attic Installation Bottom Return and Attic InstallationsSuspended Furnace / Crawl Space Installation Horizontal ApplicationFilter Installation Attempt to install filters inside the furnaceSection III Filters Side ReturnSection IV GAS Piping Section V Electrical Power Electrical Power ConnectionsManifold Pressures in. w.c Manifold Pressures kPa First Stage Manifold Pressures in. w.cLOW Voltage Control Wiring Connections Supply Voltage ConnectionsAfue LbsAC 9A TWO Stage Variable Speed Furnace OD Models AC 24C Optional HarnessID Models OD Models Accessory Connections Electronic AIR Cleaner ConnectionHumidifier Connection TwinningCondensate Drain Termination Condensate Drain Trap and Drain Freeze ProtectionWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Section VII Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Combustion AIR and Vent Piping Assembly Combustion AIR / VentingFitting Equivalent Length Furnace Vent Connection SizesVent Clearances Home LayoutVent Applications and Termination Vent SystemVenting Multiple Units Combustion AIR Supply Outdoor Combustion AirCombustion Air Source From Outdoors Ambient Combustion Air SupplyAir Supply Openings and Ducts Free AreaVertical Duct or 13 cmSpecially Engineered Installations Ventilated Combustion AirVentilated Combustion Air Termination Vent Blower RotationSection Viii START-UP Adjustments GAS Piping Leak CheckIgnition System Sequence Calculating the Furnace Input Natural GASSeconds For Seconds For Size of Test Dial Revolution Cu FtRevolution Cu Ft Adjustment of Manifold GAS Pressure & Input Rate Read the inlet gas pressureRead the manifold gas pressure Inlet GAS Pressure RangeSection IX Safety Controls Limit Controls Sequence of OperationTroubleshooting Furnace Control DiagnosticsHot Surface Ignition System Slow Green Flash Normal operationDiagnostic Fault Code Storage and Retrieval Replacement Part Contact Information Section X Replacement Parts ListDescription Section XI Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK Supersedes 438335-UIM-A-0209

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.