SECTION VII: COMBUSTION AIR AND VENT SYSTEM

COMBUSTION AIR AND VENT SAFETY

This Category IV, dual certified direct vent furnace is designed for resi- dential application. It may be installed without modification to the con- densate system in a basement, garage, equipment room, alcove, attic or any other indoor location where all required clearance to combusti- bles and other restrictions are met. The combustion air and the venting system must be installed in accordance with Section 5.3, Air for Com- bustion and Ventilation, of the National Fuel Gas Code Z223.1/NFPA 54 (latest edition), or Sections 7.2, 7.3 or 7.4 of CSA B149.1, National Gas and Propane Codes (latest edition) or applicable provisions of the local building code and these instructions.

The VENT SYSTEM must be installed as specified in these instruc- tions for Residential and non-HUD Modular Homes. The direct vent system is the only configuration that can be installed in a non-HUD Modular Home.

This furnace may not be common vented with any other appliance, since it requires separate, properly sized air intake and vent lines. The furnace shall not be connected to any type of B, BW or L vent or vent connector, and not connected to any portion of a factory- built or masonry chimney

The furnace shall not be connected to a chimney flue serving a sep- arate appliance designed to burn solid fuel.

When combustion air pipe is installed above a suspended ceiling or when it passes through a warm and humid space, the pipe must be insulated with 1/2” Armaflex or other heat resistant type insulation if two feet or more of pipe is exposed.

Vent piping must be insulated if it will be subjected to freezing tem- peratures such as routing through unheated areas or through an unused chimney.

COMBUSTION AIR/VENT PIPE SIZING

The size of pipe required will be determined by the furnace model, the total length of pipe required and the number of elbows required.

Table 8 lists the maximum equivalent length of pipe allowed for each model of furnace. The equivalent length of elbows is shown in Table 10. The equivalent length of the vent system is the total length of straight pipe PLUS the equivalent length of all of the elbows.

The following rules must also be followed:

1.Long radius (sweep) elbows are recommended. Standard elbows may be used, but since they have a longer equivalent length, they will reduce the total length of pipe that will be allowed. Short radius (plumbing vent) elbows are not allowed. The standard dimensions of the acceptable elbows are shown below.

2.The maximum equivalent length listed in Table 8 is for the vent pip- ing and the air intake piping separately. For example, if the table allows 65 equivalent feet for a particular model, then the vent can have 65 equivalent feet of pipe, AND the combustion air intake can have another 65 equivalent feet of pipe.

3.Three vent terminal elbows (two for the vent and one for the com- bustion air intake) are already accounted for and need not be included in the equivalent length calculation.

4.All combustion air and vent pipe must conform to American National Standards Institute (ANSI) and American Society for Test- ing and Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core), D2261 (ABS-DWV) or F628 (Schedule 40 ABS). Pipe cement and primer must conform to ASTM Standard D2546 (PVC) or D2235 (ABS). If ABS pipe is to be used, any joint where ABS pipe is joined to PVC pipe must be glued with cement that is approved for use with BOTH materials. Metallic materials must not be used for venting or air intake.

5.If a flexible connector is used in the vent system, it must be made of a material that is resistant to acidic exposure and to at least 225°F (107.2°C) temperature. Flexible connectors are also allowed in the combustion air pipe.

6.All models are supplied with 2" (5.1 cm) vent connections. When the pipe must be increased to 3" (7.6 cm) diameter, the transition from 2" to 3" must be done as close to the furnace as possible. For upflow models, the transition from 2" to 3" should be done immedi- ately above the furnace. For downflow or horizontal models, the transition from 2" to 3" pipe should be done immediately after exit- ing the furnace.

7.In Canada, vents shall be certified to ULC S636, Standard for Type BH Gas Venting Systems. IPEX System 636 PVC is certified to this standard.

8.In Canada, the first three feet (91.4 cm) of the vent must be readily accessible for inspection.

9.For single pipe systems it is recommended to install the combus- tion air coupling provided and install approximately 18” of PVC pipe on the furnace.

10.Minimum vent length for all models is 5 feet (1.5 m).

TABLE 8: Maximum Equivalent Pipe Length

 

Model Input

 

 

 

 

Pipe Size

 

 

Maximum

 

 

 

 

 

 

 

Equivalent

 

 

BTUH (kW)

 

 

 

 

Inches (cm)

 

 

 

 

 

 

 

 

 

length feet (m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60,000 (17.6)

 

 

 

 

2 (5.1)

 

 

 

65 (19.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60,000 (17.6)

 

 

 

 

3 (7.6)

 

 

 

90 (27.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80,000 (23.4)

 

 

 

 

2 (5.1)

 

 

 

65 (19.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80,000 (23.4)

 

 

 

 

3 (7.6)

 

 

 

90 (27.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100,000 (29.3)

 

 

 

 

2 (5.1)

 

 

 

30 (9.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100,000 (29.3)

 

 

 

 

3 (7.6)

 

 

 

90 (27.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120,000 (35.1)

 

 

 

 

2 (5.1)

 

 

 

30 (9.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120,000 (35.1)

 

 

 

 

3 (7.6)

 

 

 

90 (27.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD ELBOW

 

LONG (SWEEP) ELBOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 28: Dimensions

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 9: Elbow Dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elbow

"A" Dimension

 

 

 

 

 

 

 

 

2" Standard

2-5/16"

 

 

 

 

 

 

 

 

 

 

 

 

3" Standard

3-1/16"

 

 

 

 

 

 

 

 

 

 

 

 

2" Sweep

3-1/4"

 

 

 

 

 

 

 

 

 

 

 

 

3" Sweep

4-1/16"

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions are those required in Standard ASTM D-3311.

22

Johnson Controls Unitary Products

Image 22
Contents List of Figures Section I SafetyList of Sections List of TablesSafety Requirements Specific Safety Rules and PrecautionsCombustion AIR Quality List of Contaminants Inspection Codes and StandardsDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Furnace Location and Clearances Section II DuctworkDuctwork General Information COIL/FURNACE Assembly MC/FC/PC Series Coils Floor Base and Ductwork Installation DownflowCoil Installation Furnace Assembly MC & FC Series CoilsCoil / Furnace Assembly HC Series Coils Furnace Assembly MC Series Coils onlyFurnace Assembly PC Series Coils Coil Size Dimension C InchSuspended Furnace / Crawl Space Installation Downflow Duct Connectors Attic InstallationBottom Return and Attic Installations Horizontal ApplicationSection III Filters Filter InstallationAttempt to install filters inside the furnace Side ReturnSection IV GAS Piping Manifold Pressures in. w.c Manifold Pressures kPa Section V Electrical PowerElectrical Power Connections First Stage Manifold Pressures in. w.cAfue LOW Voltage Control Wiring ConnectionsSupply Voltage Connections LbsAC 9A TWO Stage Variable Speed Furnace OD Models AC 24C Optional HarnessID Models OD Models Humidifier Connection Accessory ConnectionsElectronic AIR Cleaner Connection TwinningCondensate Drain Termination Condensate Drain Trap and Drain Freeze ProtectionWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Section VII Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Fitting Equivalent Length Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting Furnace Vent Connection SizesVent Clearances Home LayoutVent Applications and Termination Vent SystemVenting Multiple Units Combustion Air Source From Outdoors Combustion AIR SupplyOutdoor Combustion Air Ambient Combustion Air SupplyVertical Duct or Air Supply Openings and DuctsFree Area 13 cmVentilated Combustion Air Termination Specially Engineered InstallationsVentilated Combustion Air Vent Blower RotationIgnition System Sequence Section Viii START-UP AdjustmentsGAS Piping Leak Check Calculating the Furnace Input Natural GASSeconds For Seconds For Size of Test Dial Revolution Cu FtRevolution Cu Ft Read the manifold gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the inlet gas pressure Inlet GAS Pressure RangeSection IX Safety Controls Limit Controls Sequence of OperationHot Surface Ignition System TroubleshootingFurnace Control Diagnostics Slow Green Flash Normal operationDiagnostic Fault Code Storage and Retrieval Replacement Part Contact Information Section X Replacement Parts ListDescription Section XI Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK Supersedes 438335-UIM-A-0209

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.