Johnson Controls TM9V MP Combustion AIR and Vent Piping Assembly, Combustion AIR / Venting

Page 23

438335-UIM-B-0509

TABLE 10: Equivalent Length of Fittings

Fitting

Equivalent Length

 

 

2" 90º sweep elbow

5 feet of 2" pipe

2" 45º sweep elbow

2-1/2 feet of 2" pipe

2" 90º standard elbow

10 feet of 2" pipe

2" 45º standard elbow

5 feet of 2" pipe

3" 90º sweep elbow

5 feet of 3" pipe

3" 45º sweep elbow

2-1/2 feet of 3" pipe

3" 90º standard elbow

10 feet of 3" pipe

3" 45º standard elbow

5 feet of 3" pipe

2" corrugated connector

10 feet of 2" pipe

3" corrugated connector

10 feet of 3" pipe

Example:

An 80,000 BTUH furnace requires 32 feet of pipe and four 90º elbows. Using 2" pipe and standard elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

4 - 90º standard 2" elbows = (4x10) =

40 equivalent feet

Total =

72 equivalent feet of 2" pipe

This exceeds the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus not acceptable.

By using sweep elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

4 - 90º sweep 2" elbows = (4x5) =

20 equivalent feet

Total =

52 equivalent feet of 2" pipe

This is less than the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus acceptable.

Alternatively, using 3" pipe and standard elbows, the total equivalent length will be:

32 feet of 3" pipe =

32 equivalent feet

4 - 90º standard 2" elbows = (4x5) =

40 equivalent feet

Total =

72 equivalent feet of 3" pipe

This is less than the 90 foot maximum equivalent length of 3" pipe allowed for that model and is thus acceptable.

TABLE 11: Combustion Air Intake and Vent Connection Size at Furnace (All Models)

FURNACE VENT CONNECTION SIZES

Furnace Input

40 - 100 MBH

120 - 130 MBH

(17.5 - 29.3 kW)

(35.2 - 39.6 kW)

 

 

 

 

Intake Pipe Size

2” (5.1 cm)

3” (7.6 cm)

Vent Pipe Size

2” (5.1 cm)

2” (5.1 cm)

*. Vent pipe size must be increased to 3” diameter after connection to furnace on this model.

Accessory concentric vent / intake termination kits 1CT0302 and 1CT0303 are available and approved for use with these furnaces. Horizontal sidewall vent terminations kits 1HT0901 & 1HT0902 are also approved for use with these furnaces.

Furnace vent pipe connections are sized for 2” (5.1 cm). pipe. Any pipe size change must be made outside the furnace casing in a ver- tical pipe section to allow proper drainage of condensate. An offset using two 45º (degree) elbows will be required for plenum clear- ance when the vent is increased to 3” (7.6 cm).

COMBUSTION AIR AND VENT PIPING ASSEMBLY

The final assembly procedure for the combustion air and vent piping is as follows:

1.Cut piping to the proper length beginning at the furnace.

2.Deburr the piping inside and outside.

3.Chamfer (bevel) the outer edges of the piping.

4.Dry-fit the vent piping assembly from the furnace to the outside ter- mination checking for proper fit support and slope.

5.Dry-fit the combustion air piping assembly checking for proper fit, support and slope on the following systems:

a.Sealed combustion air systems from the furnace to the out- side termination.

b.Ventilated combustion air systems from the furnace to the attic or crawl space termination.

Solvent cements are flammable and must be used in well-ventilated areas only. Keep them away from heat, sparks and open flames. Do not breathe vapors and avoid contact with skin and eyes.

6.Disassemble the combustion air and vent piping, apply cement primer and the cement per the manufactures instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS piping.

7.All joints must provide a permanent airtight and watertight seal.

8.Support the combustion air and vent piping such that it is angled a minimum of 1/4” per foot (21 mm/m) so that condensate will flow back towards the furnace. Piping should be supported with pipe hangers to prevent sagging.

9.Seal around the openings where the combustion air and / or vent piping pass through the roof or sidewalls.

COMBUSTION AIR / VENTING

The vent must be installed with the minimum required clearances, and must comply with local codes and requirements.

Johnson Controls Unitary Products

23

Image 23
Contents List of Tables Section I SafetyList of Sections List of FiguresCombustion AIR Quality List of Contaminants Specific Safety Rules and PrecautionsSafety Requirements Directly BELOW. Keep Clear of ALL OBSTRUC- Tions Codes and StandardsInspection Ductwork General Information Section II DuctworkFurnace Location and Clearances Furnace Assembly MC & FC Series Coils Floor Base and Ductwork Installation DownflowCoil Installation COIL/FURNACE Assembly MC/FC/PC Series CoilsCoil Size Dimension C Inch Furnace Assembly MC Series Coils onlyFurnace Assembly PC Series Coils Coil / Furnace Assembly HC Series CoilsHorizontal Application Downflow Duct Connectors Attic InstallationBottom Return and Attic Installations Suspended Furnace / Crawl Space InstallationSide Return Filter InstallationAttempt to install filters inside the furnace Section III FiltersSection IV GAS Piping First Stage Manifold Pressures in. w.c Section V Electrical PowerElectrical Power Connections Manifold Pressures in. w.c Manifold Pressures kPaLbs LOW Voltage Control Wiring ConnectionsSupply Voltage Connections AfueAC 9A TWO Stage Variable Speed Furnace OD Models Optional Harness AC 24CID Models OD Models Twinning Accessory ConnectionsElectronic AIR Cleaner Connection Humidifier ConnectionCondensate Drain Trap and Drain Freeze Protection Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Combustion AIR/VENT Pipe Sizing Combustion AIR and Vent SafetySection VII Combustion AIR and Vent System Furnace Vent Connection Sizes Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting Fitting Equivalent LengthHome Layout Vent ClearancesVenting Multiple Units Vent SystemVent Applications and Termination Ambient Combustion Air Supply Combustion AIR SupplyOutdoor Combustion Air Combustion Air Source From Outdoors13 cm Air Supply Openings and DuctsFree Area Vertical Duct orVent Blower Rotation Specially Engineered InstallationsVentilated Combustion Air Ventilated Combustion Air TerminationCalculating the Furnace Input Natural GAS Section Viii START-UP AdjustmentsGAS Piping Leak Check Ignition System SequenceRevolution Cu Ft Seconds For Size of Test Dial Revolution Cu FtSeconds For Inlet GAS Pressure Range Adjustment of Manifold GAS Pressure & Input RateRead the inlet gas pressure Read the manifold gas pressureSection IX Safety Controls Sequence of Operation Limit ControlsSlow Green Flash Normal operation TroubleshootingFurnace Control Diagnostics Hot Surface Ignition SystemDiagnostic Fault Code Storage and Retrieval Description Section X Replacement Parts ListReplacement Part Contact Information Section XI Wiring Diagram Supersedes 438335-UIM-A-0209 Johnson Controls Unitary Products York Drive Norman, OK

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.