Johnson Controls TM9V MP installation manual Section IV GAS Piping

Page 9

438335-UIM-B-0509

HORIZONTAL APPLICATION

Horizontal Filters

All filters and mounting provision must be field supplied. All installa- tions must have a filter installed.

Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum before the filter. The use of straps and/or supports is required to support the weight of the external filter box.

Downflow Filters

Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air plenum or duct. Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum above the filter height.

Filter(s) may be located in the duct system external to the furnace using an external duct filter box attached to the furnace plenum or at the end of the duct in a return filter grille(s). The use of straps and/or supports is required to support the weight of the external filter box.

SECTION IV: GAS PIPING

GAS SAFETY

An overpressure protection device, such as a pressure regulator, must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0.5 psig [14" w.c. (3.48 kPa)]. Pressures exceed- ing 0.5 psig [14” w.c. (3.48 kPa)] at the gas valve will cause damage to the gas valve, resulting in a fire or explosion or cause damage to the furnace or some of its components that will result in property damage and loss of life.

HIGH STAGE REGULATOR

ADJUSTMENT

 

OUTLET

 

PRESSURE

 

PORT

VENT

 

PORT

INLET

OUTLET

 

WRENCH

 

BOSS

 

INLET

 

PRESSURE

 

PORT

LOW STAGE REGULATOR

ON OFF

SWITCH

ADJUSTMENT

FIGURE 14: Gas Valve

Plan your gas supply before determining the correct gas pipe entry. Use 90-degree service elbow(s), or short nipples and conventional 90-degree elbow(s) to enter through the cabinet access holes.

GAS PIPING INSTALLATION

Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. If local codes allow the use of a flexible gas appliance connection, always use a new listed con- nector. Do not use a connector that has previously serviced another gas appliance.

Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace - only use those approved gases. The instal- lation of a drip leg and ground union is required. Refer to Figures 15.

External Manual

Shutoff Valve

To Gas

 

 

 

 

 

To Gas

Supply

 

 

 

 

 

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drip Leg

Grounded Joint Union

may be Installed

 

 

Inside or Outside Unit.

FIGURE 15: Upflow/Downflow Gas Piping

Manual

Shut-off

Valve

 

 

Drip

 

Gas

Leg

 

 

 

Pipe

Gas Burners

 

 

Gas

 

Gas Valve

 

 

Pipe

 

 

Drip

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

 

Leg

 

 

 

 

 

Shut-off Valve

FIGURE 16: Horizontal Gas Piping

An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet (1.8 m) of the furnace.

The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 0.5 psig (3.5 kPa).

The gas valve body is a very thin casting that cannot take any external pressure. Never apply a pipe wrench to the body of the gas valve when installing piping. A wrench must be placed on the octa- gon hub located on the gas inlet side of the valve. Placing a wrench to the body of the gas valve will damage the valve causing improper operation and/or the valve to leak.

Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace. Refer to Figures 12.

GAS ORIFICE CONVERSION FOR PROPANE (LP)

This furnace is constructed at the factory for natural gas-fired operation, but may be converted to operate on propane (LP) gas by using a factory-supplied LP conversion kit. Follow the instructions supplied with the LP kit.

HIGH ALTITUDE GAS ORIFICE CONVERSION

This furnace is constructed at the factory for natural gas-fired operation at 0 –5,000 feet (0 – 1,524 m) above sea level.

The manifold pressure must be changed in order to maintain proper and safe operation when the furnace is installed in a location where the altitude is greater than 5,000 feet (1,524 m) above sea level. Refer to Table 5 for proper manifold pressure settings.

HIGH ALTITUDE PRESSURE SWITCH CONVERSION

For installation where the altitude is less than 5,000 feet (1,524m), it is not required that the pressure switch be changed unless you are in an area subject to low pressure inversions.

Johnson Controls Unitary Products

9

Image 9
Contents List of Sections Section I SafetyList of Figures List of TablesSpecific Safety Rules and Precautions Safety RequirementsCombustion AIR Quality List of Contaminants Codes and Standards InspectionDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Section II Ductwork Furnace Location and ClearancesDuctwork General Information Coil Installation Floor Base and Ductwork Installation DownflowCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsFurnace Assembly PC Series Coils Furnace Assembly MC Series Coils onlyCoil / Furnace Assembly HC Series Coils Coil Size Dimension C InchBottom Return and Attic Installations Downflow Duct Connectors Attic InstallationSuspended Furnace / Crawl Space Installation Horizontal ApplicationAttempt to install filters inside the furnace Filter InstallationSection III Filters Side ReturnSection IV GAS Piping Electrical Power Connections Section V Electrical PowerManifold Pressures in. w.c Manifold Pressures kPa First Stage Manifold Pressures in. w.cSupply Voltage Connections LOW Voltage Control Wiring ConnectionsAfue LbsAC 9A TWO Stage Variable Speed Furnace OD Models Optional Harness AC 24CID Models OD Models Electronic AIR Cleaner Connection Accessory ConnectionsHumidifier Connection TwinningCondensate Drain Trap and Drain Freeze Protection Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Combustion AIR and Vent Safety Section VII Combustion AIR and Vent SystemCombustion AIR/VENT Pipe Sizing Combustion AIR / Venting Combustion AIR and Vent Piping AssemblyFitting Equivalent Length Furnace Vent Connection SizesHome Layout Vent ClearancesVent System Vent Applications and TerminationVenting Multiple Units Outdoor Combustion Air Combustion AIR SupplyCombustion Air Source From Outdoors Ambient Combustion Air SupplyFree Area Air Supply Openings and DuctsVertical Duct or 13 cmVentilated Combustion Air Specially Engineered InstallationsVentilated Combustion Air Termination Vent Blower RotationGAS Piping Leak Check Section Viii START-UP AdjustmentsIgnition System Sequence Calculating the Furnace Input Natural GASSeconds For Size of Test Dial Revolution Cu Ft Seconds ForRevolution Cu Ft Read the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Inlet GAS Pressure RangeSection IX Safety Controls Sequence of Operation Limit ControlsFurnace Control Diagnostics TroubleshootingHot Surface Ignition System Slow Green Flash Normal operationDiagnostic Fault Code Storage and Retrieval Section X Replacement Parts List Replacement Part Contact InformationDescription Section XI Wiring Diagram Supersedes 438335-UIM-A-0209 Johnson Controls Unitary Products York Drive Norman, OK

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.