VENT SYSTEM

This furnace is certified to be installed with one of two possible vent configurations.

1.Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows.

2.Vertical vent system. This vent system can be installed completely vertical or a combination of horizontal, vertical, or offset using elbows.

VENT APPLICATIONS AND TERMINATION

When selecting the location for a combustion air / vent termination, the following should be considered:

1.

Observe all clearances listed in vent clearances in these instruc-

 

tions.

2.

Termination should be positioned where vent vapors will not dam-

 

age plants or shrubs or air conditioning equipment.

12” MIN.

12” MIN.

12” Minimum below overhang

12” Minimum separation between bottom of combustion air intake and bottom of vent

Maintain 12” minimumclearance above highest anticipated snow level or grade, whichever is higher

3.

Termination should be located where it will not be affected by wind

 

gusts, light snow, airborne leaves or allow recirculation of flue

 

gases.

4.

Termination should be located where it will not be damaged or

 

exposed to flying stones, balls, etc.

5.

Termination should be positioned where vent vapors are not objec-

 

tionable.

6.

Horizontal portions of the vent system must slope upwards and be

 

supported to prevent sagging.

7.

Direct vent systems must be installed so the vent and the combus-

 

tion air pipes terminate in the same atmospheric zone. Refer to

 

Figures 13 or 14.

Maintain 12” minimum clearance above highest anticipated snow level. Maximum 24” above roof.

12” Min.

12” Min.

FIGURE 30: Termination Configuration - 1 Pipe

FIGURE 32: Termination Configuration - 2 Pipe Basement

VENTING MULTIPLE UNITS

Multiple units can be installed in a space or structure as either a single pipe configuration or a two-pipe configuration.

The combustion air side of the single pipe configuration shown in Figure 29 is referred to in these instructions as ambient combustion air supply. Follow the instructions for ambient combustion air installations, paying particular attention to the section on air source from inside the building. The vent for a single pipe system must be installed as specified in the venting section of these instructions with the vent terminating as shown in Figure 29. Each furnace must have a separate vent pipe. Under NO circumstances can the two vent pipes be tied together.

The combustion air side of the two-pipe configuration shown in Figure 30 can be installed so the combustion air pipe terminates as described in outdoor combustion air or ventilated combustion air sections in these instructions. Follow the instructions for outdoor combustion air or venti- lated combustion air and the instructions for installing the vent system with the vent terminating as shown in Figures 32 or 33. The two-pipe system must have a separate combustion air pipe and a separate vent pipe for each furnace. Under NO circumstances can the two combus- tion air or vent pipes be tied together. The combustion air and vent pipes must terminate in the same atmospheric zone.

VENT

Maintain 12” minimum clearance above highest anticipated snow level.

12” vertical separation

 

between combustion air

12” minimum

intake and vent.

below overhang

 

 

12” minimum

 

separation between

 

bottom of

 

combustion air pipe

 

and bottom of vent.

 

Maintain 12”

 

minimum clearance

 

above highest

 

anticipated snow

 

level or grade,

 

whichever is higher.

COMBUSTION AIR

2”

MIN.

FIGURE 33: Double Horizontal Combustion Air Intake and Vent Termination

MIN.6”

FIGURE 31: Termination Configuration - 2 Pipe

FIGURE 34: Double Vertical Combustion Air Intake and Vent

Termination

Johnson Controls Unitary Products

25

Image 25
Contents List of Sections Section I SafetyList of Figures List of TablesSafety Requirements Specific Safety Rules and PrecautionsCombustion AIR Quality List of Contaminants Inspection Codes and StandardsDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Furnace Location and Clearances Section II DuctworkDuctwork General Information Coil Installation Floor Base and Ductwork Installation DownflowCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsFurnace Assembly PC Series Coils Furnace Assembly MC Series Coils onlyCoil / Furnace Assembly HC Series Coils Coil Size Dimension C InchBottom Return and Attic Installations Downflow Duct Connectors Attic InstallationSuspended Furnace / Crawl Space Installation Horizontal ApplicationAttempt to install filters inside the furnace Filter InstallationSection III Filters Side ReturnSection IV GAS Piping Electrical Power Connections Section V Electrical PowerManifold Pressures in. w.c Manifold Pressures kPa First Stage Manifold Pressures in. w.cSupply Voltage Connections LOW Voltage Control Wiring ConnectionsAfue LbsAC 9A TWO Stage Variable Speed Furnace OD Models Optional Harness AC 24CID Models OD Models Electronic AIR Cleaner Connection Accessory ConnectionsHumidifier Connection TwinningCondensate Drain Trap and Drain Freeze Protection Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Section VII Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Combustion AIR / Venting Combustion AIR and Vent Piping AssemblyFitting Equivalent Length Furnace Vent Connection SizesHome Layout Vent ClearancesVent Applications and Termination Vent SystemVenting Multiple Units Outdoor Combustion Air Combustion AIR SupplyCombustion Air Source From Outdoors Ambient Combustion Air SupplyFree Area Air Supply Openings and DuctsVertical Duct or 13 cmVentilated Combustion Air Specially Engineered InstallationsVentilated Combustion Air Termination Vent Blower RotationGAS Piping Leak Check Section Viii START-UP AdjustmentsIgnition System Sequence Calculating the Furnace Input Natural GASSeconds For Seconds For Size of Test Dial Revolution Cu FtRevolution Cu Ft Read the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Inlet GAS Pressure RangeSection IX Safety Controls Sequence of Operation Limit ControlsFurnace Control Diagnostics TroubleshootingHot Surface Ignition System Slow Green Flash Normal operationDiagnostic Fault Code Storage and Retrieval Replacement Part Contact Information Section X Replacement Parts ListDescription Section XI Wiring Diagram Supersedes 438335-UIM-A-0209 Johnson Controls Unitary Products York Drive Norman, OK

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.